2020-09-28 08:46:59 | 3RD REVIEW FBC-2017 RES. |
| PERMIT- 20060955 |
| 9/25/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COMMENTS PROM THE PREVIOUS REVIEWS HAVE NOT BEEN |
| ADDRESSED. |
| |
| 1) REVISE THE RISER TO SHOW THE COMPLETE PIPING SYSTEM |
| INCLUDING PIPE RUNS TO ALL NEW AND EXISTING APPLIANCES |
| AND EQUIPMENT, AND SHOW THE CORRECT TOTAL AND |
| INDIVIDUAL LOADS OF THE SYSTEM- SECTIONS G2412.3, |
| G2412.4, & G2413.2 FBC RES. INCLUDE THE TOTAL LENGTH OF |
| THE INTERIOR PIPING RUN AND THE TOTAL DEVELOPED LENGTH |
| OF THE ENTIRE SYSTEM- SECTIONS G2413.4.1 AND G2413.4.2 |
| FBC RES. THE DRAWING SHALL INDICATE THE TYPE AND SIZE |
| OF MAIN SUPPLY PIPE FROM THE METER TO THE TEE. PER CITY |
| RECORDS AT A MINIMUM THERE IS AN EXISTING GAS WATER |
| HEATER BUT ALL CONNECTED EXISTING HAPPLIANCES AVE TO BE |
| ACCOUNTED FOR WHETHER LEGALLY PERMITTED OR NOT- SECTION |
| 107.2.1 WPB. |
| |
| A) THE SUBMITTED SPECS FOR THE KOHLER 20 KW INDICATE A |
| FULL LOAD CAPACITY OF 340,000 BTUH AND AN INPUT |
| PRESSURE AT 3.5-11 IN. W.C. PLEASE CORRECT THE LOAD ON |
| THE DRAWING. |
| |
| B) AS PREVIOUSLY REQUESTED SHOW THE LOCATION OF THE |
| REGULATOR AT THE GENERATOR, AND INDICATE THE MAKE AND |
| MODEL. SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| EITHER SIDE; SHOW THE SHUTOFF VALVE, AND THE DRIP LEG- |
| SECTIONS 2420.5, 2421.2, 2421.2(7), AND 2419.2 FBC RES. |
| PLEASE SUBMIT MARKED UP OR HIGHLIGHTED SPECS FOR THE |
| REGULATOR TO SHOW IT IS SUITABLE FOR OUTDOOR USE, |
| INDICATE THE SELECTED MODEL, INLET AND OUTLET |
| PRESSURES, AND ORIFICE SIZE. |
| |
| E) PIPE SIZING FOR THE SYSTEM SHALL BE IN ACCORDANCE |
| WITH SECTION G2413.3 FBC RES. PLEASE SEE TABLES |
| G2413.4(1)- G2413.4(8) AND LIST THE PIPE SIZING TABLE |
| FOR EACH TYPE OF PIPING IN THE SYSTEM. TYPICALLY TABLE |
| G2413.4(1) [402.4(2)] IS USED FOR LOW PRESSURE SCHED. |
| 40 METALLIC PIPE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |