Plan Review Details - Permit 20060954
Plan Review Stops For Permit 20060954
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-06 Cont ID  
Sent By rmcdouga Date 2020-08-06 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2020-08-06 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-08 Cont ID  
Sent By rmcdouga Date 2020-07-08 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2020-07-08 Time 08:54 Sent To  
Notes
2020-07-08 08:56:27 
 PLAN
 REVIEW COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN
 ADDRESSED.
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) I AM NOT ABLE TO REVIEW DUE TO THE MISSING AND
 INACCURATE INFORMATION THAT HAS BEEN PROVIDED. THE
 INSTALLATION SCHEDULE IS INCORRECT AND MISSING
 INFORMATION. THE OPENING SIZE IS TO BE THE WIDTH AND
 HEIGHT OF THE OPENING IN INCHES. THE SHUTTER SPANS ARE
 NOT PROVIDED. FBC 107
  
 2) HI LIGHT OR CIRCLE THE ITEMS THAT APPLY TO THIS
 PROJECT IN THE PRODUCT APPROVAL FOR THE STORM PANELS.
 SPECIFY THE MOUNT TYPE SECTIONS THAT WILL BE USED FOR
 EACH OF THE OPENINGS, THEY HAVE CAPITAL LETTERS IN
 FRONT OF THEM IN THE PRODUCT APPROVAL DRAWINGS. THIS IS
 NOT THE SAME AS THE CONNECTION TYPES (SUCH AS C1 OR
 C2). FBC 107
  
 3) HI LIGHT OR CIRCLE THE APPROPRIATE ITEMS IN THE
 ANCHOR SPACING TABLES. MARK THE ANCHOR, THE DESIGN
 PRESSURE, THE SPAN, THE SPACING, ETC ON THE PROPER
 TABLE. FBC 107

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-23 Cont ID  
Sent By rmcdouga Date 2020-06-23 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2020-06-23 Time 16:19 Sent To  
Notes
2020-06-23 16:42:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) I AM NOT ABLE TO REVIEW DUE TO THE MISSING AND
 INACCURATE INFORMATION THAT HAS BEEN PROVIDED. THE
 INSTALLATION SCHEDULE IS INCORRECT AND MISSING
 INFORMATION. THE OPENING SIZE IS TO BE THE WIDTH AND
 HEIGHT OF THE OPENING IN INCHES. THE SHUTTER SPANS ARE
 NOT PROVIDED. FBC 107
  
 2) HI LIGHT OR CIRCLE THE ITEMS THAT APPLY TO THIS
 PROJECT IN THE PRODUCT APPROVAL FOR THE STORM PANELS.
 SPECIFY THE MOUNT TYPE SECTIONS THAT WILL BE USED FOR
 EACH OF THE OPENINGS, THEY HAVE CAPITAL LETTERS IN
 FRONT OF THEM IN THE PRODUCT APPROVAL DRAWINGS. THIS IS
 NOT THE SAME AS THE CONNECTION TYPES (SUCH AS C1 OR
 C2). FBC 107
  
 3) HI LIGHT OR CIRCLE THE APPROPRIATE ITEMS IN THE
 ANCHOR SPACING TABLES. MARK THE ANCHOR, THE DESIGN
 PRESSURE, THE SPAN, THE SPACING, ETC ON THE PROPER
 TABLE. FBC 107

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-06 Cont ID  
Sent By rmcdouga Date 2020-08-06 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2020-07-29 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-08 Cont ID  
Sent By lmarchan Date 2020-07-08 Time 09:11 Rev Time 0.00
Received By lmarchan Date 2020-07-02 Time 13:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-23 Cont ID  
Sent By rmcdouga Date 2020-06-23 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2020-06-18 Time 14:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-06-23 Cont ID  
Sent By rmcdouga Date 2020-06-23 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2020-06-23 Time 16:19 Sent To  
Notes
***NONE***