Plan Review Details - Permit 20060761
Plan Review Stops For Permit 20060761
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-08-25 Cont ID  
Sent By rmcdouga Date 2021-08-25 Time 13:41 Rev Time 0.00
Received By rmcdouga Date 2021-08-25 Time 13:41 Sent To  
Notes
2021-08-25 13:44:40NOT RESOLVED. A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR ON LETTERHEAD IS REQUIRED. SEE COMMENT FROM
 FIRST REVIEW THAT FOLLOWS.
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By rmcdouga Date 2020-07-17 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2020-07-17 Time 14:30 Sent To  
Notes
2020-07-17 14:34:52PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-27 Cont ID  
Sent By rmcdouga Date 2021-08-27 Time 15:13 Rev Time 0.00
Received By rmcdouga Date 2021-08-25 Time 10:25 Sent To  
Notes
2021-08-27 14:40:362ND REVIEW FBC-2017 BUILDING
 PERMIT- 20060761
 8/27/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) [NOT RESOLVED.] THE PLANS THAT WERE SUBMITTED ONLY
 HAVE A FEW DIMENSIONS ON THEM. SUBMIT DRAWINGS WITH ALL
 DIMENSIONS SPECIFIED ON THEM. FBC 107.2.1
  
 2) [NOT RESOLVED.] SPECIFY THE EXISTING OCCUPANCY TYPE
 FOR THIS SPACE ON THE PLANS. FBC 107.2.1
  
 3) [THIS WILL BE A PROVISO TO BE VERIFIED BY THE FIELD
 INSPECTOR.] VERIFY THAT THE TENANT SEPARATION WALLS ON
 EACH SIDE OF THE SPACE ARE 2 HOUR FIRE RESISTIVE RATED.
 FBC 706
  
 4) [NOT RESOLVED. THE CONSTRUCTION TYPE IS SPECIFIED AS
 TYPE IV ON THE PLANS IN THE CITY'S RECORDS. THE PLANS
 FOR THE BUILDING HAS NON-COMBUSTIBLE FLOORS, BEARING
 WALLS, AND ROOF CONSTRUCTION. THE CONSTRUCTION TYPES IN
 THE BUILDING CODES HAVE CHANGED SINCE THIS BUILDING WAS
 CONSTRUCTED. BASED ON THE 2017 FBC THE CONSTRUCTION
 TYPE FOR THIS BUILDING IS TYPE II-B. PLEASE CHANGE THE
 CONSTRUCTION TYPE ON THE PLANS FROM V-B TO II-B.] THE
 TYPE OF CONSTRUCTION FOR THIS BUILDING IS SPECIFIED AS
 TYPE V ON SHEET LS.100. SPECIFY IF IT IS TYPE V-A OR
 V-B CONSTRUCTION. BASED ON MY RESEARCH THIS SPACE IS
 LOCATED IN A 14,400 SQUARE FOOT WAREHOUSE BUILDING. IT
 IS LOCATED IN BUILDING #4 IN A GROUP OF OTHER WAREHOUSE
 BUILDINGS. THE ORIGINAL OCCUPANCY WAS BUSINESS AND
 WAREHOUSE. IT DOES NOT APPEAR THAT THIS BUILDING IS
 TYPE V CONSTRUCTION. PLEASE VERIFY THE CONSTRUCTION
 TYPE. FBC 601
  
 5) [RESOLVED.] ONE SHEET LS.100 YOU HAVE INCLUDED THE
 CELLAR AND BAR SERVICE AREAS WITH THE F-2 OCCUPANCY. IT
 APPEARS THAT THE BAR SERVICE AREA AND POSSIBLY THE
 CELLAR AREA SHOULD BE INCLUDED WITH THE A2 OCCUPANCY.
 PLEASE CLARIFY THE INTENDED USE OF THE CELLAR. EXPLAIN
 WHY THE BAR SERVICE AREA AND THE CELLAR SHOULD NOT BE
 PART OF THE ASSEMBLY AREA.
  
 6) [RESOLVED.] THE SECTION THAT ALLOWS ASSEMBLY AREAS
 WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS TO BE
 CLASSIFIED AS A GROUP B OCCUPANCY DOES NOT ALLOW THE
 OCCUPANT LOAD FOR THE ASSEMBLY AREA TO BE RECALCULATED
 USING THE OCCUPANT LOAD FACTOR FOR A BUSINESS
 OCCUPANCY. THE NUMBER OF OCCUPANTS STAYS THE SAME AS
 CALCULATED FOR AN ASSEMBLY AREA. PLEASE CORRECT. FBC
 1004 & FBC 303.1.1 SMALL BUILDINGS AND TENANT SPACES A
 BUILDING OR TENANT SPACE USED FOR ASSEMBLY PURPOSES
 WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS SHALL BE
 CLASSIFIED AS A GROUP B OCCUPANCY.
  
 7) [NOT RESOLVED. THE RESPONSE LETTER STATES THAT THIS
 IS A NON-SEPARATED MIXED USE OCCUPANCY. SPECIFY THIS ON
 THE PLANS AND REMOVE THE STATEMENT ON SHEET ON SHEET
 LS.100 THAT SPECIFIES THAT THE ASSEMBLY OCCUPANCY IS
 ACCESSORY TO THE F-2 OCCUPANCY.] FBC 508.2.3 STATES
 THAT AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT OCCUPY
 MORE THAN 10 PERCENT OF THE FLOOR AREA OF THE STORY IN
 WHICH THEY ARE LOCATED. SINCE THE FLOOR AREA OF THE
 ASSEMBLY AREAS IS MORE THAN 10 PERCENT THIS CAN NOT BE
 AN ACCESSORY OR ANCILLARY OCCUPANCY. THIS IS A MIXED
 USE OCCUPANCY. YOU WILL NEED TO DETERMINE IF IT WILL BE
 A NON-SEPARATED OCCUPANCY OR A SEPARATED OCCUPANCY PER
 FBC508.3 OR 508.4.
  
 8) [NOT RESOLVED. CHANGE THIS TO SPECIFY 2017 FBC
 SECTION 1006.2.] ON SHEET LS.100 UNDER EGRESS
 REQUIREMENTS THE NUMBER OF REQUIRED EXITS SPECIFIES FBC
 2014 SECTION 1021.2(2). PLEASE CORRECT THIS TO
 REFERENCE THE 2017 FBC AND THE APPROPRIATE SECTION.
  
 FLORIDA ACCESSIBILITY COMMENTS : THIS IS A CHANGE OF
 OCCUPANCY AND IS TREATED AS NEW CONSTRUCTION FOR THE
 APPLICATION OF ACCESSIBILITY REQUIREMENTS. FBC EXISTING
 BUILDING 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 9) [ NOT RESOLVED. PROVIDE A COST BREAKDOWN TO SHOW HOW
 THE 20% DISPROPORTIONATE COSTS WILL BE SPENT TOWARD
 IMPROVING ACCESSIBILITY.] SHOW ACCESSIBLE PARKING
 SPACES, ACCESSIBLE ROUTE TO ACCESSIBLE ENTRANCE AND
 THROUGH PRIMARY SERVICE AREA. FBC - ACCESSIBILITY 206
 AND 208
  
 10) [NOT RESOLVED. PROVIDE DETAILED DRAWINGS,
 ELEVATIONS, ETC. TO SHOW THAT THE BATHROOMS COMPLY WITH
 ACCESSIBILITY.] SHOW THAT BATHROOMS MEET ACCESSIBILITY
 REQUIREMENTS. 603 TOILET AND BATHING ROOMS. 603.1
 GENERAL. TOILET AND BATHING ROOMS SHALL COMPLY WITH 603
  
 11) [NOT RESOLVED. THE RESPONSE LETTER STATES THAT THE
 BAR TOP WILL BE USED FOR BEVERAGE SERVICE AND THE FLOOR
 PLAN SHOWS SEATING AT THE BAR TOP. THIS BAR IS NEW
 CONSTRUCTION AND IT WILL HAVE TO COMPLY WITH
 ACCESSIBILITY.] SHOW ACCESSIBLE AREAS AT THE BARS. FBC
 - ACCESSIBILITY 226.1 GENERAL. WHERE DINING SURFACES
 ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT
 LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING
 SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902. IN
 ADDITION, WHERE WORK SURFACES ARE PROVIDED FOR USE BY
 OTHER THAN EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY
 WITH 902.
  
 12) [RESOLVED.] SHOW ACCESSIBLE SEATING DISPERSED
 THROUGHOUT TASTING AREAS. FBC - A 226.2 DISPERSION.
 DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES AND WORK SURFACES.
  
 13) [ NOT RESOLVED. THE BAR TOP WILL BE USED AS A
 SERVICE COUNTER AND WILL HAVE TO COMPLY WITH FBC
 ACCESSIBILITY.] SHOW THAT THE SALES/SERVICE COUNTER
 COMPLIES WITH ACCESSIBILITY. FBC - A 904.4 SALES AND
 SERVICE COUNTERS. SALES COUNTERS AND SERVICE COUNTERS
 SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE
 PORTION OF THE COUNTER TOP SHALL EXTEND THE SAME DEPTH
 AS THE SALES OR SERVICE COUNTER TOP.
  
 14) NEW COMMENT.THE TOTAL NUMBER OF OCCUPANTS IS
 SPECIFIED AS 46.2 PERSONS ON SHEET LS.100. SINCE THERE
 CAN NOT BE A FRACTION OF A PERSON, THE TOTAL NEEDS TO
 BE ROUNDED UP TO THE NEXT HIGHER WHOLE NUMBER WHICH IS
 47 PERSONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By rmcdouga Date 2020-07-22 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2020-07-16 Time 06:51 Sent To  
Notes
2020-07-14 12:07:131ST REVIEW FBC-2017 BUILDING
 PERMIT- 20060761
 7/21/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS THAT WERE SUBMITTED ONLY HAVE A FEW
 DIMENSIONS ON THEM. SUBMIT DRAWINGS WITH ALL DIMENSIONS
 SPECIFIED ON THEM. FBC 107.2.1
  
 2) SPECIFY THE EXISTING OCCUPANCY TYPE FOR THIS SPACE
 ON THE PLANS. FBC 107.2.1
  
 3) VERIFY THAT THE TENANT SEPARATION WALLS ON EACH SIDE
 OF THE SPACE ARE 2 HOUR FIRE RESISTIVE RATED. FBC 706
  
 4) THE TYPE OF CONSTRUCTION FOR THIS BUILDING IS
 SPECIFIED AS TYPE V ON SHEET LS.100. SPECIFY IF IT IS
 TYPE V-A OR V-B CONSTRUCTION. BASED ON MY RESEARCH THIS
 SPACE IS LOCATED IN A 14,400 SQUARE FOOT WAREHOUSE
 BUILDING. IT IS LOCATED IN BUILDING #4 IN A GROUP OF
 OTHER WAREHOUSE BUILDINGS. THE ORIGINAL OCCUPANCY WAS
 BUSINESS AND WAREHOUSE. IT DOES NOT APPEAR THAT THIS
 BUILDING IS TYPE V CONSTRUCTION. PLEASE VERIFY THE
 CONSTRUCTION TYPE. FBC 601
  
 5) ONE SHEET LS.100 YOU HAVE INCLUDED THE CELLAR AND
 BAR SERVICE AREAS WITH THE F-2 OCCUPANCY. IT APPEARS
 THAT THE BAR SERVICE AREA AND POSSIBLY THE CELLAR AREA
 SHOULD BE INCLUDED WITH THE A2 OCCUPANCY. PLEASE
 CLARIFY THE INTENDED USE OF THE CELLAR. EXPLAIN WHY THE
 BAR SERVICE AREA AND THE CELLAR SHOULD NOT BE PART OF
 THE ASSEMBLY AREA.
  
 6) THE SECTION THAT ALLOWS ASSEMBLY AREAS WITH AN
 OCCUPANT LOAD OF LESS THAN 50 PERSONS TO BE CLASSIFIED
 AS A GROUP B OCCUPANCY DOES NOT ALLOW THE OCCUPANT LOAD
 FOR THE ASSEMBLY AREA TO BE RECALCULATED USING THE
 OCCUPANT LOAD FACTOR FOR A BUSINESS OCCUPANCY. THE
 NUMBER OF OCCUPANTS STAYS THE SAME AS CALCULATED FOR AN
 ASSEMBLY AREA. PLEASE CORRECT. FBC 1004 & FBC 303.1.1
 SMALL BUILDINGS AND TENANT SPACES A BUILDING OR TENANT
 SPACE USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD
 OF LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS A GROUP
 B OCCUPANCY.
  
 7) ON SHEET LS.100 IT IS STATED THAT THE ASSEMBLY
 OCCUPANCY IS ACCESSORY TO THE F-2 OCCUPANCY. FBC
 508.2.3 STATES THAT AGGREGATE ACCESSORY OCCUPANCIES
 SHALL NOT OCCUPY MORE THAN 10 PERCENT OF THE FLOOR AREA
 OF THE STORY IN WHICH THEY ARE LOCATED. SINCE THE FLOOR
 AREA OF THE ASSEMBLY AREAS IS MORE THAN 10 PERCENT THIS
 CAN NOT BE AN ACCESSORY OR ANCILLARY OCCUPANCY. THIS IS
 A MIXED USE OCCUPANCY. YOU WILL NEED TO DETERMINE IF IT
 WILL BE A NON-SEPARATED OCCUPANCY OR A SEPARATED
 OCCUPANCY PER FBC508.3 OR 508.4.
  
 8) ON SHEET LS.100 UNDER EGRESS REQUIREMENTS THE NUMBER
 OF REQUIRED EXITS SPECIFIES FBC 2014 SECTION 1021.2(2).
 PLEASE CORRECT THIS TO REFERENCE THE 2017 FBC AND THE
 APPROPRIATE SECTION.
  
 FLORIDA ACCESSIBILITY COMMENTS : THIS IS A CHANGE OF
 OCCUPANCY AND IS TREATED AS NEW CONSTRUCTION FOR THE
 APPLICATION OF ACCESSIBILITY REQUIREMENTS. FBC EXISTING
 BUILDING 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 9) SHOW ACCESSIBLE PARKING SPACES, ACCESSIBLE ROUTE TO
 ACCESSIBLE ENTRANCE AND THROUGH PRIMARY SERVICE AREA.
 FBC - ACCESSIBILITY 206 AND 208
  
 10) SHOW THAT BATHROOMS MEET ACCESSIBILITY
 REQUIREMENTS. 603 TOILET AND BATHING ROOMS. 603.1
 GENERAL. TOILET AND BATHING ROOMS SHALL COMPLY WITH 603
  
 11) SHOW ACCESSIBLE AREAS AT THE BARS. FBC -
 ACCESSIBILITY 226.1 GENERAL. WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
  
 12) SHOW ACCESSIBLE SEATING DISPERSED THROUGHOUT
 TASTING AREAS. FBC - A 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 13) SHOW THAT THE SALES/SERVICE COUNTER COMPLIES WITH
 ACCESSIBILITY. FBC - A 904.4 SALES AND SERVICE
 COUNTERS. SALES COUNTERS AND SERVICE COUNTERS SHALL
 COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION
 OF THE COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE
 SALES OR SERVICE COUNTER TOP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-08-09 Cont ID  
Sent By jleahy Date 2021-08-09 Time 11:22 Rev Time 0.00
Received By jleahy Date 2021-08-09 Time 11:17 Sent To  
Notes
2021-08-09 11:25:26ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 IF A CHANGE OF OCCUPANY IS BEING REQUESTED THIS ALL
 COULD NOT HAVE BEEN EXISTING,
  
 PLEASE INDICATE ON THE PLANS THE NEW ELECTRICAL WORK
 FOR THE BREWING EQUIPMENT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By jleahy Date 2020-07-08 Time 12:00 Rev Time 0.00
Received By jleahy Date 2020-07-08 Time 11:54 Sent To  
Notes
2020-07-08 12:01:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL LAYOUT OF FLOOR AREA OUTLETS,
 EQUIPMENT(ELECTRIC) LIGHTING

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-07-30 Cont ID  
Sent By pleduc Date 2021-07-30 Time   Rev Time 0.00
Received By pleduc Date 2021-07-30 Time 14:50 Sent To  
Notes
2021-07-30 14:50:511) SHEET LS .100 - THERE IS NO INDICATION OF WHETHER
 THIS IS A MIXED OR SEPARATED OCCUPANCY.
  
 THERE IS AN INDICATION THAT THE ASSEMBLY AREA IS
 ACCESSORY; HOWEVER, PER NFPA 101, IT DOES NOT APPEAR TO
 BE ACCESSORTY.
  
 PER NFPA 101
  
 PER TABLE 6.1.14.4.1 (B)
  
 THE REQUIRED SEPARATION OF AN INDUSTRIAL GENERAL
 HAZARD/SPECIAL HAZARD AND MERCANTILE/ASSEMBLY IS 2
 HOURS.
  
 IS THE FIRE CODE REQUIREMENT IS MORE
 RESTRICTIVE/STRINGENT THAN THE BUILDING CODE CITED,
 THEN THE FIRE CODE APPLIES.
  
 A 2 HOUR FIRE RATED SEPARATION IS REQUIRED.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND FOR THE REQUIRED
 SEPARATION.
  
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By pleduc Date 2020-06-25 Time   Rev Time 0.00
Received By pleduc Date 2020-06-22 Time 12:59 Sent To  
Notes
2020-06-22 16:17:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET LS .100 - THERE IS NO INDICATION OF WHETHER
 THIS IS A MIXED OR SEPARATED OCCUPANCY.
  
 THERE IS AN INDICATION THAT THE ASEMBLY AREA IS
 ACCESSORY; HOWEVER, PER NFPA 101, IT DOES NOT APPEAR TO
 BE ACCESSORTY.
  
 PER NFPA 101
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR
 STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL
 BE CLASSIFIED IN
 ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY
 CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A
 QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL
 CASE.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF
 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED
 OCCUPANCY.
 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY,
 AREAS USED AS
 FOLLOWS SHALL BE PERMITTED TO BE CONSIDERED PART OF THE
 PREDOMINANT
 OCCUPANCY AND SHALL BE SUBJECT TO THE PROVISIONS OF THE
 CODE THAT APPLY
 TO THE PREDOMINANT OCCUPANCY:
 (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE
 (2) *NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER
 THAN THAT
 ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY THRESHOLD
 (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR
 FOR CUSTOMARY
 NON-HAZARDOUS USES NECESSARY FOR TRANSACTING THE
 PRINCIPAL
 BUSINESS IN STORAGE AND INDUSTRIAL OCCUPANCIES NEED NOT
 BE
 SEPARATED FROM THE PRINCIPAL USE.
 (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING
 LOW HAZARD
 PRODUCTS IN ACCORDANCE WITH SUBDIVISION 6.2.2 NEED NOT
 BE
 SEPARATED BY FIRE-RESISTANT CONSTRUCTION FROM THE
 OCCUPANCIES TO
 WHICH THEY ARE ACCESSORY.
 6.1.14.1.3.1 INCIDENTAL USE AREAS SHALL BE SEPARATED AS
 REQUIRED BY TABLE
 508.2.5 OF THE FLORIDA BUILDING CODE WHERE TABLE
 508.2.5 PERMITS AN
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE
 BARRIER, THE INCIDENTAL
 USE AREA SHALL BE SEPARATED BY CONSTRUCTION CAPABLE OF
 RESISTING THE
 PASSAGE OF SMOKE.
 6.1.14.1.4 THE FOLLOWING ACCESSORY OCCUPANCIES SHALL
 NOT BE REQUIRED TO
 BE SEPARATED FROM THE PRIMARY OCCUPANCY AS REQUIRED IN
 6.1.14.4:
 (1) A KITCHEN IN AN ASSEMBLY OCCUPANCY DOES NOT
 CONSTITUTE A MIXED
 OCCUPANCY.
 (2) ACCESSORY USES IN INDUSTRIAL AND STORAGE
 OCCUPANCIES AS OTHERWISE
 PROVIDED IN 6.1.14.1.3(1)
 (3) ROOMS OR SPACES USED FOR CUSTOMARY STORAGE OF
 NON-HAZARDOUS
 MATERIALS IN ASSEMBLY, BUSINESS, EDUCATIONAL,
 INDUSTRIAL,
 MERCANTILE, HOTEL AND DORMITORY, AND APARTMENT
 OCCUPANCIES WHICH
 IN AGGREGATE DO NOT EXCEED 10% OF THE MAJOR FLOOR AREA
 IN WHICH
 THEY ARE LOCATED. PROTECTION FROM HAZARDS SHALL BE AS
 OTHERWISE
 PROVIDED IN THE SPECIFIC OCCUPANCY CHAPTER
  
  
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF
 HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A
 BUILDING OR STRUCTURE,
 THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION,
 UNLESS
 HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED
 IN SECTION
 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH
 43.
  
  
 PLEASE REVIEW AND PROVIDE DETAILS AND FOR THE REQUIRED
 SEPARATION.
  
  
  
 1A) SHEET A.100 - THE TASTING ROOM APPEARS TO BE MORE
 OF A BAR THAN A ROOM IS MORE THAN INCIDENTAL TO THE
 OCCUPANCY.
  
 PER NFPA 101, TABLE 6.1.14.4.1(B) A 2 HOUR SEPARATION
 IS REQUIRED
  
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF
 HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A
 BUILDING OR STRUCTURE,
 THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION,
 UNLESS
 HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED
 IN SECTION
 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH
 43.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 2) SHEET S 7 OF 8 - FERMENTOR CO2 VENT SYSTEM - THERE
 IS AN INDICATION OF A VENTING SYSTEM THAT INDICATES
 GOING UNDER A BAY DOOR.
  
 THERE NEEDS TO BE A BETTER PLAN OF VENTING TO THE
 OUTSIDE AND ONE THAT HELPS DISPERSE THE CO2 FROM
 NEIGBORING BUSINESSES.
  
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2A) THERE DOES NOT APPEAR TO AN INDICATION OF THE
 VENTING MATERIAL AND HOW IT WILL BE SUPPORTED.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2B) THERE DOES NOT APPEAR TO BE ANY CO2 DETECTION
 DEVICES THROUGHOUT THE OCCUPANCY.
  
 AS A INDUSTRIAL THAT PRODUCES CO2 AS PART OF ITS
 PROCESSES CO2 DETECTION IS REQUIRED FOR LIFE SAFETY
 PURPOSES. INSTALLATION OF CO2 AND O2 ALARMS MAY BE
 REQUIRED.
  
 PLEASE REVIEW AND CORECT.
  
  
  
 2C) FOR CONFIRMATION PURPOSES, THERE DOES NOT APPEAR TO
 BE ANY CO2 STORAGE BOTTLES/CONTAINORS WITHIN IN THE
 OCCUPANCY THAT COULD BE USED DURING THE BREWING
 PROCESS.
  
 PLEASE CONFIRM THAT CO2 STORAGE TANKS WILL NOT BE USED.
  
  
  
  
 3) ELECTRICAL DEVICES/EQUIPMENT - IN BREWERIES THERE
 CAN BE COMBUSTIBLE DUST CREATED DUE TO SEVRAL PROCESSED
 THAT MAY ACCULMULATE ON SURFACES AND IN THE AIR.
  
 IT IS IMPORTANT TO HAVE INTRINSICALY SAFE ELCTRICAL
 DEVICES/EQUIPMENT IN THESE AREAS.
  
 PLEASE REVIEW AND PROVIDE PROPER ELECTRICAL EQUIPMENT.
  
 PER NFPA 654
 6.5 ELECTRICAL EQUIPMENT.
 6.5.1 ALL ELECTRICAL EQUIPMENT AND INSTALLATIONS SHALL
 COMPLY
 WITH THE REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL
 CODE, OR
 NFPA 496, STANDARD FOR PURGED AND PRESSURIZED
 ENCLOSURES FOR ELECTRICAL
 EQUIPMENT.
 6.5.2* IN LOCAL AREAS OF A PLANT WHERE A HAZARDOUS
 QUANTITY OF
 DUST ACCUMULATES OR IS SUSPENDED IN AIR, THE AREA SHALL
 BE CLASSIFIED
 AND ALL ELECTRICAL EQUIPMENT AND INSTALLATIONS IN THOSE
 LOCAL AREAS SHALL COMPLY WITH ARTICLE 502 OR ARTICLE
 503 OF
 NFPA 70, NATIONAL ELECTRICAL CODE, AS APPLICABLE.
  
 I. GENERAL
 502.1 SCOPE. ARTICLE 502 COVERS THE REQUIREMENTS FOR
 ELECTRICAL
 AND ELECTRONIC EQUIPMENT AND WIRING FOR ALL VOLTAGES
 IN CLASS II, DIVISION 1 AND 2 LOCATIONS WHERE FIRE OR
 EXPLOSION
 HAZARDS MAY EXIST DUE TO COMBUSTIBLE DUST.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-27 Cont ID  
Sent By rmcdouga Date 2021-08-27 Time 15:14 Rev Time 0.00
Received By rmcdouga Date 2021-07-29 Time 09:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-22 Cont ID  
Sent By rmcdouga Date 2020-07-22 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2020-06-19 Time 09:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By rmcdouga Date 2020-07-17 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2020-07-17 Time 14:23 Sent To  
Notes
2020-07-17 14:25:01THIS IS A CHANGE OF OCCUPANCY WHICH IS REQUIRED TO BE
 REVIEWED FOR IMPACT FEES. PLANS WILL BE REVIEWED BY THE
 PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-18 Cont ID  
Sent By medwards Date 2021-08-17 Time 15:59 Rev Time 0.00
Received By medwards Date 2021-08-06 Time 09:28 Sent To  
Notes
2021-08-17 15:59:472ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20060761
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW HOW THE VENTILATION FOR ALL SPACES OF
 THIS TENANT SPACE WILL MEET FBC M 401.3 (VENTILATION
 SHALL BE PROVIDED DURING THE PERIODS THAT THE ROOM OR
 SPACE IS OCCUPIED.)
  
 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS BASED ON THE NATURAL VENTILATION OF THE
 CHANGE OF USE OF THE SPACES. FBC EC C403.2.1
  
 3) PLEASE ADDRESS ALL OF THE COMMENTS FROM THE 1ST
 CYCLE MECHANICAL REVIEW LISTED BELOW.
  
  
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060761
  
  
  
 2) PLEASE PROVIDE COMPLETE DRAWINGS OF THE EXISTING
 MECHANICAL SYSTEM AND INCLUDE ANY NEW CHANGES. THIS
 DRAWING MUST SHOW THE RATED WALLS USED AS SEPARATION
 BETWEEN THE NEW OCCUPANCIES WITH DAMPERS IF ANY DUCT
 WORK IS PENETRATING THESE RATED WALLS. FBC FS 107.2.1
  
 3) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS NEW
 PROJECT, FOR ALL AREAS. THE NATURAL VENTILATION
 CALCULATIONS IN THIS PACKAGE WOULD NOT WORK AS THERE
 SHOULD BE A RATED WALL BETWEEN THE F-2 AND B
 OCCUPANCIES. FBC M 403
  
 4) PLEASE PROVIDE QUANTITIES OF INGREDIENTS STORED AT
 THIS FACILITY. FBC FS 107.2.1
  
 5) PLEASE SHOW THE EXHAUST FOR THE MASH AREA. FBC FS
 107.2.1
  
 6) PLEASE PROVIDE A VENTING DETAIL FOR THE CO2 TO AN
 APPROVED TERMINATION LOCATION. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By medwards Date 2020-07-10 Time 09:44 Rev Time 0.00
Received By medwards Date 2020-07-09 Time 15:36 Sent To  
Notes
2020-07-10 09:45:331ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060761
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OCCUPANCY CLASSIFICATION OF EXISTING
 COMMERCIAL SUITE. FBC FS 107.2.1
  
 2) PLEASE PROVIDE COMPLETE DRAWINGS OF THE EXISTING
 MECHANICAL SYSTEM AND INCLUDE ANY NEW CHANGES. THIS
 DRAWING MUST SHOW THE RATED WALLS USED AS SEPARATION
 BETWEEN THE NEW OCCUPANCIES WITH DAMPERS IF ANY DUCT
 WORK IS PENETRATING THESE RATED WALLS. FBC FS 107.2.1
  
 3) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS NEW
 PROJECT, FOR ALL AREAS. THE NATURAL VENTILATION
 CALCULATIONS IN THIS PACKAGE WOULD NOT WORK AS THERE
 SHOULD BE A RATED WALL BETWEEN THE F-2 AND B
 OCCUPANCIES. FBC M 403
  
 4) PLEASE PROVIDE QUANTITIES OF INGREDIENTS STORED AT
 THIS FACILITY. FBC FS 107.2.1
  
 5) PLEASE SHOW THE EXHAUST FOR THE MASH AREA. FBC FS
 107.2.1
  
 6) PLEASE PROVIDE A VENTING DETAIL FOR THE CO2 TO AN
 APPROVED TERMINATION LOCATION. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-06 Cont ID  
Sent By ccole Date 2021-08-06 Time 15:55 Rev Time 0.00
Received By ccole Date 2021-08-06 Time 10:33 Sent To  
Notes
2021-08-06 15:55:442ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20060761
 8/6/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. A NARRATIVE RESPONSE HAS
 BEEN PROVIDED TO THE IST REVIEW PLUMBING COMMENTS,
 HOWEVER THE DOCUMENT WAS NOT SIGNED AND HAD NO REPLY
 INFORMATION PROVIDED. THE NARRATIVE STATES THAT
 PLUMBING PLANS WILL BE UPLOADED SEPARATELY. AS I COULD
 NOT LOCATE THE (P) PLUMBING PLANS, PLEASE CLARIFY IF
 THE PLANS ARE TO BE UPLOADED "SEPARATELY" UNDER A
 SEPARATE PERMIT OR UNDER THIS PERMIT. SHEET A100
 INDICATES BATH AND BAR FIXTURES AND UNDERSLAB DRAIN
 PIPING AS EXISTING. PLEASE NOTE I HAVE RESEARCHED
 BUILDING DEPARTMENT RECORDS AND WAS UNABLE TO LOCATE A
 PERMIT FOR THE SECOND BATHROOM AND BAR IN THE SPACE. IT
 APPEARS THAT ONE BATHROOM WAS CONSTRUCTED UNDER THE
 MAIN BUILDING PERMIT FOR BUILDING-4 BUT THE RECORD
 PLANS THAT WERE UPLOADED SHOW A SINGLE BATHROOM AND THE
 MAIN DRAIN TO THE NORTH OF THE BATHROOM. SHEET A100
 SHOWS A SECOND BATHROOM AND THE DRAIN RUNNING SW OF THE
 BATHROOMS. FAILED COMMENTS FROM THE 1ST REVIEW ARE
 LISTED BELOW WITH ADDITONAL NOTES FOR FURTHER
 CLARIFICATION.
  
 1) FAILED. PROVIDE PLUMBING FIXTURE CALCULATIONS.
 PROVIDE A SCHEDULE ON THE PLAN SHOWING THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES PER TABLE 403.3 FBC P.
 PLEASE NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS
 ARE REQUIRED FOR F AND A OCCUPANCIES. AN EMERGENCY
 SHOWER AND EYE WASH STATION MAY BE REQUIRED FOR THE F
 OCCUPANCY DEPENDING UPON DEPARTMENT OF HEALTH,
 DEPARTMENT OF AGRICULTURE, OSHA, OR OTHER GOVERNING
 AGENCY REQUIREMENTS. PLEASE CONTACT THOSE AGENCIES FOR
 FURTHER INFORMATION. NOT PROVIDED. PLEASE NOTE THAT THE
 BUILDING PLANS EXAMINER HAS DETERMINED THE BREWERY IS A
 MIXED OCCUPANCY. REFER TO SECTION 403.1.1 FBC P-
 FRACTIONAL NUMBERS RESULTING FROM APPLYING THE FIXTURE
 RATIOS OF TABLE 403.1 SHALL BE ROUNDED UP TO THE NEXT
 WHOLE NUMBER. FOR CALCULATIONS INVOLVING MULTIPLE
 OCCUPANCIES, SUCH FRACTIONAL NUMBERS FOR EACH OCCUPANCY
 SHALL FIRST BE SUMMED AND THEN ROUNDED UP TO THE NEXT
 WHOLE NUMBER.
  
 3) FAILED. A.100: THE PLAN INDICATES ACCESS TO ONE OF
 THE TWO TOILET ROOMS IS THROUGH A STORAGE AND BREWERY
 AREA WHICH IS NOT ALLOWED PER SECTION 403.3.1 FBC P. NO
 CHANGES MADE TO THE PLAN.
  
 4) FAILED. A.100: THE PLAN SHOWS NEW SINKS IN WHAT
 APPEARS TO BE A BAR AREA, HOWEVER PLUMBING PLANS WERE
 NOT PROVIDED FOR THE PROPOSED PROJECT. PLEASE SUBMIT
 PLUMBING PLANS SHOWING THE LOCATIONS OF ALL NEW OR
 RELOCATED FIXTURES, FLOOR DRAINS, TRENCH DRAINS,
 INDIRECT WASTE RECEPTORS, ETC. PROVIDE SANITARY AND
 WATER RISER ISOMETRIC DRAWINGS, AND FLAT LINE PIPING
 PLANS SHOWING THE POINTS OF CONNECTIONS TO THE EXISTING
 DWV AND WATER DISTRIBUTION SYSTEMS- SECTIONS 107.2.1
 AND 107.3.5.1.1 WPB. THE WATER RISER SHALL PROVIDE
 SYMBOLS TO INDICATE THE LOCATIONS OF REQUIRED BACKFLOW
 PREVENTERS, WATER HAMMER ARRESTORS, TRAP PRIMERS, SHUT
 OFF VALVES, AND ALL PIPING CONNECTIONS TO PROCESS OR
 BREWERY EQUIPMENT AND TANKS (IF APPLICABLE). NOT
 PROVIDED. IN ACCORDANCE WITH SECTION 107.3.5.1.3 WPB
 PLEASE PROVIDE PLUMBING PLANS INCLUDING ITEMS LISTED
 ABOVE AND:
 A) SANITARY DRAINAGE AND WATER PIPING LAYOUT PLANS AND
 ISOMETRIC DRAWINGS.
 B) A HOT WATER PLAN- LOCATIONS AND EQUIPMENT SCHEDULES
 FOR NEW WATER HEATERS- SECTION 502.1 FBC P & TABLE
 C404.1 FBC EC; THE MEANS OF PROVIDING TEMPERED WATER TO
 THE PUBLIC LAVATORES- SECTIONS 416.5 & 607.1.2 FBC P;
 HOT WATER PIPE INSULATION TABLE C403.2.10 FBC EC;
 LENGTH OF PIPING FROM THE HOT WATER SOURCE TO THE
 PUBLIC LAVATORIES- TABLE C404.5.1 FBC EC . PLEASE THE
 MAXIMUM DISTANCE IS 2 FT FOR ?-INCH PIPE.
  
 5) FAILED. PROVIDE PLUMBING FIXTURE AND DEVICE
 SCHEDULES INDICATING MAKES AND MODELS AND LISTING AND
 LABELING INFORMATION- SECTION 303 FBC P. A SCHEDULE HAS
 BEEN PROVIDED ON A SEPARATE DOCUMENT FROM THE PLANS,
 HOWEVER A CORRELATING PLUMBING LAYOUT PLAN (SEE COMMENT
 4) SHALL BE SUBMITTED IDENTIFYING THE LOCATIONS OF THE
 FIXTURES- SECTION 107.2.1 WPB.
  
 6) FAILED. REFER TO SECTION 1003.3.1 FBC P: A GREASE
 INTERCEPTOR WILL BE REQUIRED TO RECEIVE THE DRAINAGE
 FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN WASTE
 LOCATED IN THE BREWERY AND PROCESSING AREAS. SHOW ON
 THE PLANS THE DRAINAGE SYSTEM FOR THE TANKS AND KETTLES
 AND OTHER PROCESS EQUIPMENT. THE CITY OF WEST PALM
 BEACH HAS NOT REQUIRED GREASE INTERCEPTORS FOR
 BREWERIES UNLESS COOKING OPERATIONS ARE CONDUCTED AS
 PART OF THE BUSINESS. GREASE INTERECEPTORS ARE ALSO
 REQUIRED FOR OIL OR FAT LADEN DRAINAGE FROM FIXTURES.
 PLEASE SUBMIT A BREWERY MENU AS EVIDENCE TO VERIFY THE
 GREASE INBTERCEPTOR WILL NOT BE REQUIRED.
  
 7) FAILED. SHEET 8: REFER TO TABLE 608.1 AND SUBMIT
 SPECS FOR THE WATER SUPPLY HOSE BIB AND BACKFLOW
 PREVENTER, AND THE FDA HOSE AND CARBON FILTER- SECTION
 107.2.1 WPB. THE NARRATIVE STATES THE FILTER IS REMOVED
 HOWEVER IT IS STILL SHOWING ON SHEET A100.
  
 8) FAILED. SHEET 6: SHOW THE WATER FEED CONNECTION TO
 THE COLD WATER TANK. CLARIFY IF THE TANK WILL BE
 MANUALLY FILLED USING THE HOSE OR IF IT WILL BE
 HARD-PIPED- SEE SECTION 608.1 FBC P. A NEW FEED DIAGRAM
 HAS BEEN PROVIDED FOR THE TANKS BUT THE DIAGRAM DOES
 NOT SHOW THE LOCATION OF THE HOSE BIB AND POTABLE WATER
 SUPPLY LINE CONNECTION AS NO PLUMBING PLANS HAVE BEEN
 PROVIDED.
  
 9) FAILED. ACCESSIBILITY: PLEASE BE ADVISED THAT ALL
 NEW PLUMBING FIXTURES FOR PUBLIC USE SHALL BE
 ACCESSIBLE- SECTION 201.1 FBC ACC. THE SUBMITTED PLANS
 ARE NOT SHOWING ANY NEW PUBLIC USE FIXTURES, HOWEVER
 ALL REVISED PLANS INDICATING NEW FIXTURE INSTALLATIONS,
 INCLUDING THE REQUIRED DRINKING FOUNTAINS, SHALL
 INCLUDE INSTALLATION DRAWINGS AND DETAILS IN COMPLIANCE
 WITH SECTION 601.1 FBC ACC. THE LOCATION OF THE
 REQUIRED DRINKING FOUNTAINS IS NOT SHOWN AND THE
 REQUESTED ACCESSIBILITY COMPLAINCE DRAWINGS HAVE NOT
 BEEN PROVIDED. PLEASE REVIEW THE LIST OF COMPLIANCE
 BELOW PER THE FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
 L) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48
 IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH
 TO THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW
 THE LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS.
  
 NEW COMMENT
 1) SHEETS 1, 2, 5, & 8 OF 8 SHEETS FROM INNOVATIVE
 ENGINEERING HAVE BEEN SUBMITTED., HOWEVER I DO NOT SEE
 THAT SHEETS 3, 4, 6, & 7 HAVE BEEN SUBMITTED. PLEASE
 PROVIDE THE SHEETS- SECTION 107.2.1 WPB. EQUIPMENT
 SPECS MISSING INCLUDE THE SPECS FOR THE BOIL KETTLE AND
 THE CHILLER- SECTION 107.2.1 WPB.
 2) IT APPEARS THAT ALL THE TANK SUBMITTALS DO NOT
 PROVIDE LISTING OR LABELING INFORMATION. HAVE THE TANKS
 BEEN TESTED IN ACCORDANCE WITH ANY ACCEPTED STANDARDS
 SUCH AS NSF OR IAMPO?- SECTION 102.4 AND 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By ccole Date 2020-07-07 Time 14:41 Rev Time 0.00
Received By ccole Date 2020-07-07 Time 12:03 Sent To  
Notes
2020-07-07 14:44:301ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20060761
 7/7/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE PLUMBING FIXTURE CALCULATIONS. PROVIDE A
 SCHEDULE ON THE PLAN SHOWING THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES PER TABLE 403.3 FBC P. PLEASE NOTE
 THAT DRINKING FOUNTAINS AND SERVICE SINKS ARE REQUIRED
 FOR F AND A OCCUPANCIES. AN EMERGENCY SHOWER AND EYE
 WASH STATION MAY BE REQUIRED FOR THE F OCCUPANCY
 DEPENDING UPON DEPARTMENT OF HEALTH, DEPARTMENT OF
 AGRICULTURE, OSHA, OR OTHER GOVERNING AGENCY
 REQUIREMENTS. PLEASE CONTACT THOSE AGENCIES FOR FURTHER
 INFORMATION.
  
 2) SHEET A.100: PLEASE LABEL THE TOILET ROOMS AS EITHER
 MALE OR FEMALE- SEE SECTIONS 403.2 AND 403.2.1 FBC P.
 THE PLAN INDICATES THE TOILET ROOMS ARE EXISTING.
 PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS TO VERIFY
 COMPLIANCE WITH SECTION 1006.1 FBC EX, AND SECTION
 601.1 FBC ACC.
  
 3) A.100: THE PLAN INDICATES ACCESS TO ONE OF THE TWO
 TOILET ROOMS IS THROUGH A STORAGE AND BREWERY AREA
 WHICH IS NOT ALLOWED PER SECTION 403.3.1 FBC P.
  
 4) A.100: THE PLAN SHOWS NEW SINKS IN WHAT APPEARS TO
 BE A BAR AREA, HOWEVER PLUMBING PLANS WERE NOT PROVIDED
 FOR THE PROPOSED PROJECT. PLEASE SUBMIT PLUMBING PLANS
 SHOWING THE LOCATIONS OF ALL NEW OR RELOCATED FIXTURES,
 FLOOR DRAINS, TRENCH DRAINS, INDIRECT WASTE RECEPTORS,
 ETC. PROVIDE SANITARY AND WATER RISER ISOMETRIC
 DRAWINGS, AND FLAT LINE PIPING PLANS SHOWING THE POINTS
 OF CONNECTIONS TO THE EXISTING DWV AND WATER
 DISTRIBUTION SYSTEMS- SECTIONS 107.2.1 AND 107.3.5.1.1
 WPB. THE WATER RISER SHALL PROVIDE SYMBOLS TO INDICATE
 THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS, WATER
 HAMMER ARRESTORS, TRAP PRIMERS, SHUT OFF VALVES, AND
 ALL PIPING CONNECTIONS TO PROCESS OR BREWERY EQUIPMENT
 AND TANKS (IF APPLICABLE).
  
 5) PROVIDE PLUMBING FIXTURE AND DEVICE SCHEDULES
 INDICATING MAKES AND MODELS AND LISTING AND LABELING
 INFORMATION- SECTION 303 FBC P.
  
 6) REFER TO SECTION 1003.3.1 FBC P: A GREASE
 INTERCEPTOR WILL BE REQUIRED TO RECEIVE THE DRAINAGE
 FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN WASTE
 LOCATED IN THE BREWERY AND PROCESSING AREAS. SHOW ON
 THE PLANS THE DRAINAGE SYSTEM FOR THE TANKS AND KETTLES
 AND OTHER PROCESS EQUIPMENT.
  
 7) SHEET 8: REFER TO TABLE 608.1 AND SUBMIT SPECS FOR
 THE WATER SUPPLY HOSE BIB AND BACKFLOW PREVENTER, AND
 THE FDA HOSE AND CARBON FILTER- SECTION 107.2.1 WPB.
  
 8) SHEET 6: SHOW THE WATER FEED CONNECTION TO THE COLD
 WATER TANK. CLARIFY IF THE TANK WILL BE MANUALLY FILLED
 USING THE HOSE OR IF IT WILL BE HARD-PIPED- SEE SECTION
 608.1 FBC P.
  
 9) ACCESSIBILITY: PLEASE BE ADVISED THAT ALL NEW
 PLUMBING FIXTURES FOR PUBLIC USE SHALL BE ACCESSIBLE-
 SECTION 201.1 FBC ACC. THE SUBMITTED PLANS ARE NOT
 SHOWING ANY NEW PUBLIC USE FIXTURES, HOWEVER ALL
 REVISED PLANS INDICATING NEW FIXTURE INSTALLATIONS,
 INCLUDING THE REQUIRED DRINKING FOUNTAINS, SHALL
 INCLUDE INSTALLATION DRAWINGS AND DETAILS IN COMPLIANCE
 WITH SECTION 601.1 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-17 Cont ID  
Sent By medwards Date 2021-08-17 Time 16:02 Rev Time 0.00
Received By medwards Date 2021-08-17 Time 16:02 Sent To  
Notes
2021-08-17 16:02:19DESIGNER MUST DIGITALLY SIGN AND SEAL ALL PAGES OF HIS
 DESIGN. FS471.025
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By medwards Date 2020-07-10 Time 10:13 Rev Time 0.00
Received By medwards Date 2020-07-10 Time 09:45 Sent To  
Notes
2020-07-10 10:15:16DESIGNER MUST DIGITALLY SIGN AND SEAL ALL PAGES OF HIS
 DESIGN. FS471.025
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-08-13 Cont ID  
Sent By awooten Date 2021-08-13 Time   Rev Time 0.00
Received By awooten Date 2021-08-13 Time   Sent To  
Notes
2021-08-13 14:21:04*********ZONING REVIEW FAILED*********
  
 ****DUE TO THIS LOCATION BEING ZONED INDUSTRIAL, IT IS
 EXEMPT FROM ADDITIONAL STANDARDS 1 AND 2 LOCATED IN
 SECTION 6.1. PLEASE SHOW THAT YOU MEET THE OTHER
 REQUIREMENTS ON FLOOR PLAN.
  
 6.1. BREWPUB/MICROBREWERY/MICRO-DISTILLERY/MICRO-WINERY
 (PXR: SEE ITEM 12.1, TABLE IX-I).
  
 A. ADDITIONAL APPLICATION REQUIREMENTS
  
 1. A WRITTEN STATEMENT THAT THE PROPOSED FACILITY WILL
 COMPLY WITH ALL APPLICABLE STATE LAWS AND REGULATIONS.
 (SUBMITTED)
 2. THE ADDITIONAL STANDARDS FOR THIS USE SHALL NOT
 APPLY TO BONA FIDE RESTAURANTS DERIVING MORE THAN 51
 PERCENT OF SALES FROM FOOD AND SERVING MANUFACTURES
 ALCOHOLIC BEVERAGES FOR ON-SITE CONSUMPTION ONLY AND
 WITH NO DISTRIBUTION. (NOT A RESTAURANT, N/A.)
 3. A FLOOR PLAN DEPICTING COMPLIANCE WITH ADDITIONAL
 STANDARD 2 SHALL BE SUBMITTED AS PART OF THE
 CERTIFICATE OF USE APPLICATION. NOT A RESTAURANT, N/A.)
  
 B. ADDITIONAL STANDARDS .
  
 1. THE MAXIMUM SIZE OF A BUILDING CONTAINING A BREWPUB,
 MICROBREWERY, MICRO-DISTILLERY, OR MICRO-WINERY USE
 SHALL NOT EXCEED 3,000 SQUARE FEET IN THE NORTHWOOD
 MIXED-USE DISTRICT (NMUD) OR 5,000 SQUARE FEET IN THE
 GENERAL COMMERCIAL (GC) ZONING DISTRICT. THERE SHALL BE
 NO LIMIT FOR A FACILITY LOCATED WITHIN THE INDUSTRIAL
 (IND) ZONING DISTRICT. (ZONED INDUSTRIAL, N/A.)
  
 2. THIS USE SHALL BE PERMITTED ONLY IN CONJUNCTION WITH
 A RESTAURANT, BAR, TASTING ROOM OR RETAIL SERVICE. A
 MAXIMUM OF 75 PERCENT OF THE SQUARE FOOTAGE OF THE
 FACILITY (INCLUSIVE OF OUTDOOR SEATING FACILITIES)
 SHALL BE DEDICATED TO THE BREWERY FUNCTION INCLUDING,
 BUT NOT LIMITED TO, BREW HOUSE, BOILING AND WATER
 TREATMENT AREAS, BOTTLING AND KEGGING LINES, MALT
 MILLING AND STORAGE, FERMENTATION TANKS, CONDITION
 TANKS AND SERVING TANKS. THIS STANDARD SHALL NOT APPLY
 TO PROPERTIES LOCATED WITHIN THE INDUSTRIAL (I) ZONING
 DISTRICT). N/A
  
 3. EXCEPT FOR LOADING AND UNLOADING, ALL ACTIVITIES
 SHALL OCCUR WITHIN A BUILDING. DELIVERY ACCESS AND
 LOADING BAYS SHALL NOT FACE TOWARD ANY STREET,
 EXCLUDING ALLEYS. DELIVERY ACCESS AND LOADING BAYS
 FACING AN ADJACENT RESIDENTIAL USE, OR RESIDENTIAL
 ZONING DISTRICT, SHALL HAVE THE DOORS CLOSED AT ALL
 TIMES, EXCEPT DURING THE MOVEMENT OF RAW MATERIALS,
 OTHER SUPPLIES AND FINISHED PRODUCTS INTO AND OUT OF
 THE BUILDING. ( PROPERTY HAS A SERVICE ALLEY IN THE
 REAR WHERE THEY WILL DO LOADING AND UNLOADING. LOADING
 BAYS DO NOT FACE AN ADJACENT RESIDENTIAL DISTRICT/USE.)
  
 4. ALL NEW FACILITIES, WHETHER IN AN EXISTING BUILDING
 OR NEW BUILDING SHALL PROVIDE ON-SITE LOADING IN
 ACCORDANCE WITH ZLDR SECTION 94-485(P), TABLE XV-4. FOR
 NEW FACILITIES LOCATING WITHIN AN EXISTING BUILDING,
 WITH NO CHANGE IN BUILDING FOOTPRINT, IF A FUNCTIONAL
 ALLEY EXISTS ADJACENT TO THE FACILITY, FACILITIES MAY
 USE THE ALLEY TO ACCOUNT FOR ONE OF THE REQUIRED
 ON-SITE LOADING SPACES. ( PROPERTY HAS AN SERVICE ALLEY
 IN THE REAR.)
  
 5. ALL MECHANICAL EQUIPMENT VISIBLE FROM THE STREET
 (EXCLUDING ALLEYS), WITH AN ADJACENT RESIDENTIAL USE OR
 WITHIN A RESIDENTIAL ZONING DISTRICT, SHALL BE SCREENED
 USING ARCHITECTURAL FEATURES CONSISTENT WITH THE
 PRINCIPAL STRUCTURE. (THE PROPERTY IS NOT WITHIN A
 RESIDENTIAL ZONING DISTRICT/USE.)
  
 6. NO OUTDOOR STORAGE SHALL BE ALLOWED. THIS
 PROHIBITION INCLUDES USE OF PORTABLE STORAGE UNITS,
 CARGO CONTAINERS, AND TRACTOR TRAILERS. (NO OUTDOOR
 STORAGE IS BEING PROPOSED.)
  
 7. OUTDOOR SEATING AREAS OR AREAS OF PATRON
 CONGREGATION SHALL BE PROHIBITED WHEN THE PROPERTY
 DIRECTLY ABUTS A RESIDENTIAL ZONING DISTRICT. (SUBJECT
 PROPERTY DOES NOT ABUT A RESIDENTIAL ZONING DISTRICT
 AND OUTDOOR SEATING IS NOT PROPOSEDL)
  
 8. DRIVE-THROUGH FACILITIES ARE PROHIBITED. (THE
 BREWERY IS NOT PROPOSING A DRIVE-THROUGH.)
  
 ****PLEASE SHOW THAT YOU HAVE MET CRITERIA A ON YOUR
 SITE PLAN AS WELL AS PROVIDE PROOF OF LICENSE INDICATED
 IN B FROM CHAPTER 6 - ALCOHOLIC BEVERAGES.
  
 CHAPTER 6 ALCOHOLIC BEVERAGES
  
 (E) OTHER EXCEPTIONS. THE PROVISIONS OF SUBSECTIONS (B)
 OF THIS SECTION SHALL NOT APPLY TO:
  
 (1) BREWPUB/MICROBREWERY/MICRO-DISTILLERY/MICRO-WINERY
 AS DEFINED IN THIS CHAPTER, WHERE THE SALE OF ALCOHOLIC
 BEVERAGES FOR ON-SITE CONSUMPTION IS INCIDENTAL TO THE
 PRODUCTION, DISTRIBUTION, AND SALE OF PACKAGED
 ALCOHOLIC BEVERAGES FOR OFF-SITE CONSUMPTION AND MEETS
 THE FOLLOWING CRITERIA:
  
 A. AT LEAST 65 PERCENT OF THE SQUARE FOOTAGE OF THE
 FACILITY (INCLUSIVE OF OUTDOOR SEATING FACILITIES)
 SHALL BE DEDICATED TO THE BREWERY FUNCTION INCLUDING,
 BUT NOT LIMITED TO, BREW HOUSE, BOILING AND WATER
 TREATMENT AREAS, BOTTLING AND KEGGING LINES, MALT
 MILLING AND STORAGE, FERMENTATION TANKS, CONDITION
 TANKS AND SERVING TANKS.
  
 **PLEASE INDICATE SQUARE FOOTAGE CALCULATIONS ON FLOOR
 PLAN SHOWING THAT THE 65% REQUIREMENT HAS BEEN MET.**
  
 B. BUSINESS MUST HOLD ONE OF THE FOLLOWING LICENSES
 ISSUED BY THE FLORIDA DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATIONS, DIVISION OF ALCOHOLIC
 BEVERAGES AND TOBACCO: CMB, AMW, BMWC, DD.
  
 **PLEASE SUBMIT A COPY OF CMB LICENSE.**
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By awooten Date 2020-07-09 Time   Rev Time  
Received By awooten Date 2020-07-09 Time   Sent To  
Notes
2020-07-09 10:43:51*********ZONING REVIEW FAILED*********
  
 ****DUE TO THIS LOCATION BEING ZONED INDUSTRIAL, IT IS
 EXEMPT FROM ADDITIONAL STANDARDS 1 AND 2 LOCATED IN
 SECTION 6.1. PLEASE SHOW THAT YOU MEET THE OTHER
 ADDITIONAL STANDARDS 3-8 ON YOUR FLOOR PLAN AND SITE
 PLAN.
  
 6.1. BREWPUB/MICROBREWERY/MICRO-DISTILLERY/MICRO-WINERY
 (PXR: SEE ITEM 12.1, TABLE IX-I).
  
 A. ADDITIONAL APPLICATION REQUIREMENTS .
  
 1. A WRITTEN STATEMENT THAT THE PROPOSED FACILITY WILL
 COMPLY WITH ALL APPLICABLE STATE LAWS AND REGULATIONS.
 2. THE ADDITIONAL STANDARDS FOR THIS USE SHALL NOT
 APPLY TO BONA FIDE RESTAURANTS DERIVING MORE THAN 51
 PERCENT OF SALES FROM FOOD AND SERVING MANUFACTURES
 ALCOHOLIC BEVERAGES FOR ON-SITE CONSUMPTION ONLY AND
 WITH NO DISTRIBUTION.
 3. A FLOOR PLAN DEPICTING COMPLIANCE WITH ADDITIONAL
 STANDARD 2 SHALL BE SUBMITTED AS PART OF THE
 CERTIFICATE OF USE APPLICATION.
  
 B. ADDITIONAL STANDARDS .
  
 1. THE MAXIMUM SIZE OF A BUILDING CONTAINING A BREWPUB,
 MICROBREWERY, MICRO-DISTILLERY, OR MICRO-WINERY USE
 SHALL NOT EXCEED 3,000 SQUARE FEET IN THE NORTHWOOD
 MIXED-USE DISTRICT (NMUD) OR 5,000 SQUARE FEET IN THE
 GENERAL COMMERCIAL (GC) ZONING DISTRICT. THERE SHALL BE
 NO LIMIT FOR A FACILITY LOCATED WITHIN THE INDUSTRIAL
 (IND) ZONING DISTRICT. N/A
  
 2. THIS USE SHALL BE PERMITTED ONLY IN CONJUNCTION WITH
 A RESTAURANT, BAR, TASTING ROOM OR RETAIL SERVICE. A
 MAXIMUM OF 75 PERCENT OF THE SQUARE FOOTAGE OF THE
 FACILITY (INCLUSIVE OF OUTDOOR SEATING FACILITIES)
 SHALL BE DEDICATED TO THE BREWERY FUNCTION INCLUDING,
 BUT NOT LIMITED TO, BREW HOUSE, BOILING AND WATER
 TREATMENT AREAS, BOTTLING AND KEGGING LINES, MALT
 MILLING AND STORAGE, FERMENTATION TANKS, CONDITION
 TANKS AND SERVING TANKS. THIS STANDARD SHALL NOT APPLY
 TO PROPERTIES LOCATED WITHIN THE INDUSTRIAL (I) ZONING
 DISTRICT). N/A
  
 3. EXCEPT FOR LOADING AND UNLOADING, ALL ACTIVITIES
 SHALL OCCUR WITHIN A BUILDING. DELIVERY ACCESS AND
 LOADING BAYS SHALL NOT FACE TOWARD ANY STREET,
 EXCLUDING ALLEYS. DELIVERY ACCESS AND LOADING BAYS
 FACING AN ADJACENT RESIDENTIAL USE, OR RESIDENTIAL
 ZONING DISTRICT, SHALL HAVE THE DOORS CLOSED AT ALL
 TIMES, EXCEPT DURING THE MOVEMENT OF RAW MATERIALS,
 OTHER SUPPLIES AND FINISHED PRODUCTS INTO AND OUT OF
 THE BUILDING.
  
 4. ALL NEW FACILITIES, WHETHER IN AN EXISTING BUILDING
 OR NEW BUILDING SHALL PROVIDE ON-SITE LOADING IN
 ACCORDANCE WITH ZLDR SECTION 94-485(P), TABLE XV-4. FOR
 NEW FACILITIES LOCATING WITHIN AN EXISTING BUILDING,
 WITH NO CHANGE IN BUILDING FOOTPRINT, IF A FUNCTIONAL
 ALLEY EXISTS ADJACENT TO THE FACILITY, FACILITIES MAY
 USE THE ALLEY TO ACCOUNT FOR ONE OF THE REQUIRED
 ON-SITE LOADING SPACES.
  
 5. ALL MECHANICAL EQUIPMENT VISIBLE FROM THE STREET
 (EXCLUDING ALLEYS), WITH AN ADJACENT RESIDENTIAL USE OR
 WITHIN A RESIDENTIAL ZONING DISTRICT, SHALL BE SCREENED
 USING ARCHITECTURAL FEATURES CONSISTENT WITH THE
 PRINCIPAL STRUCTURE.
  
 6. NO OUTDOOR STORAGE SHALL BE ALLOWED. THIS
 PROHIBITION INCLUDES USE OF PORTABLE STORAGE UNITS,
 CARGO CONTAINERS, AND TRACTOR TRAILERS.
  
 7. OUTDOOR SEATING AREAS OR AREAS OF PATRON
 CONGREGATION SHALL BE PROHIBITED WHEN THE PROPERTY
 DIRECTLY ABUTS A RESIDENTIAL ZONING DISTRICT.
  
 8. DRIVE-THROUGH FACILITIES ARE PROHIBITED.
  
 ****PLEASE SHOW THAT YOU HAVE MET CRITERIA A ON YOUR
 SITE PLAN AS WELL AS PROVIDE PROOF OF LICENSE INDICATED
 IN B FROM CHAPTER 6 - ALCOHOLIC BEVERAGES.
  
 CHAPTER 6 ALCOHOLIC BEVERAGES
  
 (E) OTHER EXCEPTIONS. THE PROVISIONS OF SUBSECTIONS (B)
 OF THIS SECTION SHALL NOT APPLY TO:
  
 (1) BREWPUB/MICROBREWERY/MICRO-DISTILLERY/MICRO-WINERY
 AS DEFINED IN THIS CHAPTER, WHERE THE SALE OF ALCOHOLIC
 BEVERAGES FOR ON-SITE CONSUMPTION IS INCIDENTAL TO THE
 PRODUCTION, DISTRIBUTION, AND SALE OF PACKAGED
 ALCOHOLIC BEVERAGES FOR OFF-SITE CONSUMPTION AND MEETS
 THE FOLLOWING CRITERIA:
  
 A. AT LEAST 65 PERCENT OF THE SQUARE FOOTAGE OF THE
 FACILITY (INCLUSIVE OF OUTDOOR SEATING FACILITIES)
 SHALL BE DEDICATED TO THE BREWERY FUNCTION INCLUDING,
 BUT NOT LIMITED TO, BREW HOUSE, BOILING AND WATER
 TREATMENT AREAS, BOTTLING AND KEGGING LINES, MALT
 MILLING AND STORAGE, FERMENTATION TANKS, CONDITION
 TANKS AND SERVING TANKS.
  
 B. BUSINESS MUST HOLD ONE OF THE FOLLOWING LICENSES
 ISSUED BY THE FLORIDA DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATIONS, DIVISION OF ALCOHOLIC
 BEVERAGES AND TOBACCO: CMB, AMW, BMWC, DD.
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449