Plan Review Details - Permit 20060703
Plan Review Stops For Permit 20060703
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 08:45 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 08:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-07-14 Cont ID  
Sent By rmcphers Date 2020-07-14 Time 11:06 Rev Time 0.00
Received By rmcphers Date 2020-07-14 Time 11:06 Sent To  
Notes
2020-07-14 11:10:44WINDOWS/DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SLIDING GLASS DOOR = ITEM CIRCLED ON THE SLIDING
 GLASS DOOR PRODUCT APPROVAL DOES NOT MEET THE REQUIRED
 WIND LOADS (CHART ON THE PRODUCT APPROVAL SHOWS MAX
 -60).
 2) PLEASE PROVIDE A STATEMENT SHOWING THE BUILDING
 HEIGHT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-02 Cont ID  
Sent By jwitmer Date 2020-07-02 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2020-07-02 Time 07:31 Sent To  
Notes
2020-07-02 08:15:43WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060703
 ADD: 1701 S. FLAGLER DR. # 506
 CONT: AOA CONSTRUCTION
 TEL: 561-660-3504
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 2ND REVIEW
 ACTION: DENIED
  
 1A-1B) COMPLIED.
  
 1C) THE CONTRACTOR DID NOT IDENTIFY THE SIZE OF THE
 OPENINGS, NOR IF THE UNIT # 506 IS AN INTERIOR UNIT
 WALL ZONE 4 OR AN END UNIT IN ZONE 5 NEITHER NOR DID
 THE CONTRACTOR PROVIDE A FLOOR PLAN OF THE BUILDING AND
 THE RELATIONSHIP OF UNIT 506 WITHIN THE BUILDING TO BE
 ABLE TO DETERMINE WHICH WALL ZONE THIS UNIT IS LOCATED.
  
 2) THE SUBMITTED PRODUCT APPROVALS DID NOT HAVE THE
 FOLLOWING INFORMATION IDENTIFIED. PLEASE
 IDENTIFY(CIRCLE) ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY (CIRCLE) RTHE OPENING WIDTH &
 HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 3) COMPLIED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2020-07-01 17:39:33IN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By rmcphers Date 2020-06-29 Time 09:49 Rev Time 0.00
Received By rmcphers Date 2020-06-29 Time 09:49 Sent To  
Notes
2020-06-29 11:16:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060703
 ADD: 1701 S. FLAGLER DR. # 506
 CONT: AOA CONSTRUCTION
 TEL: 561-660-3504
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 29TH/ 2020
 ACTION: DENIED
  
 1) WIND CHART FROM ENGINEERING EXPRESS:
 1A) THE WIND CHART FORM ENGINEERING EXPRESS COULD NOT
 VERIFY THE DIGITAL SIGNATURE.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 1B) THE SUBMITTED WIND CHART FROM ENGINEERING EXPRESS
 IS ONLY GOOD FOR BUILDINGS < (LESS THAN 60 FEET). THIS
 HIGHRISE IS APPROXIMATELY 230 FEET ABOVE GRADE. NOTE TO
 CONTRACTOR NEGATIVE PRESSURES FOR COMPONENTS AND
 CLADDING ARE ALWAYS TAKEN FROM THE MRH (MEAN ROOF
 HEIGHT). 2017 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS
 FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR
 THE BUILDING.
 1C) ) THE SUBMITTED WIND CHART FROM ENGINEERING EXPRESS
 NEITHER ARE THE WALL ZONES IDENTIFIED ON THE SIDE
 ELEVATIONS AND ON THE PRESSURE CHARTS OPENING SIZES AND
 PRESSURES ARE NOT IDENTIFIED.
 2) THE SUBMITTED PRODUCT APPROVALS DIDN?T HAVE THE
 FOLLOWING INFORMATION IDENTIFIED. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
 3) PLEASE NOTE THE FOLLOWING 3 FILES WERE LOADED WRONG,
 FAILED TO OPEN:
 3.1) 1XFRVUM1.RJI
 3.2) JOOOE3PQP.WZH
 3.3) RBV4W5R5.PZN
 YOU MAY HAVE TO CONTACT THE PERMIT LIBRARIANS:
 LAURA MARCHANT 561-805-6658
 OR CAROLINA CARVAJAL 561-805-6690
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
2020-06-29 09:54:55WINDOWS/DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) WIND PRESSURES PROVIDED NEED TO BE BASED ON BUILDING
 HEIGHT NOT HEIGHT OF THE UNIT.
 2) WIND DESIGN PRESSURES NEED TO BE
 ELECTRONICALLY/DIGITALLY SIGNED BY THE ENGINEER TO BE
 USED IN ELECTRONIC PLAN REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 08:45 Rev Time 0.00
Received By rmcphers Date 2020-07-15 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-14 Cont ID  
Sent By rmcphers Date 2020-07-14 Time 11:10 Rev Time 0.00
Received By rmcphers Date 2020-07-06 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-07-02 Time 08:15 Rev Time 0.00
Received By lmarchan Date 2020-07-01 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-29 Cont ID  
Sent By rmcphers Date 2020-06-29 Time 10:02 Rev Time 0.00
Received By rmcphers Date 2020-06-24 Time 11:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 08:45 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 08:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-02 Cont ID  
Sent By jwitmer Date 2020-07-02 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2020-07-02 Time 07:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By rmcphers Date 2020-06-29 Time 10:01 Rev Time 0.00
Received By rmcphers Date 2020-06-29 Time 10:01 Sent To  
Notes
2020-06-29 11:15:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060703
 ADD: 1701 S. FLAGLER DR. # 506
 CONT: AOA CONSTRUCTION
 TEL: 561-660-3504
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 29TH/ 2020
 ACTION: DENIED
  
 1) WIND CHART FROM ENGINEERING EXPRESS:
 1A) THE WIND CHART FORM ENGINEERING EXPRESS COULD NOT
 VERIFY THE DIGITAL SIGNATURE.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 1B) THE SUBMITTED WIND CHART FROM ENGINEERING EXPRESS
 IS ONLY GOOD FOR BUILDINGS < (LESS THAN 60 FEET). THIS
 HIGHRISE IS APPROXIMATELY 230 FEET ABOVE GRADE. NOTE TO
 CONTRACTOR NEGATIVE PRESSURES FOR COMPONENTS AND
 CLADDING ARE ALWAYS TAKEN FROM THE MRH (MEAN ROOF
 HEIGHT). 2017 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS
 FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR
 THE BUILDING.
 1C) ) THE SUBMITTED WIND CHART FROM ENGINEERING EXPRESS
 NEITHER ARE THE WALL ZONES IDENTIFIED ON THE SIDE
 ELEVATIONS AND ON THE PRESSURE CHARTS OPENING SIZES AND
 PRESSURES ARE NOT IDENTIFIED.
 2) THE SUBMITTED PRODUCT APPROVALS DIDN?T HAVE THE
 FOLLOWING INFORMATION IDENTIFIED. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
 3) PLEASE NOTE THE FOLLOWING 3 FILES WERE LOADED WRONG,
 FAILED TO OPEN:
 3.1) 1XFRVUM1.RJI
 3.2) JOOOE3PQP.WZH
 3.3) RBV4W5R5.PZN
 YOU MAY HAVE TO CONTACT THE PERMIT LIBRARIANS:
 LAURA MARCHANT 561-805-6658
 OR CAROLINA CARVAJAL 561-805-6690
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
2020-06-29 10:02:16SEE BUILDING PLAN REVIEW