Plan Review Details - Permit 20060697
Plan Review Stops For Permit 20060697
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By cthroop Date 2020-08-19 Time 15:23 Rev Time 0.00
Received By cthroop Date 2020-08-19 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By cthroop Date 2020-06-29 Time 15:00 Rev Time 0.00
Received By cthroop Date 2020-06-29 Time 10:49 Sent To  
Notes
2020-06-29 15:42:31PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN WITH LOCATION OF GENERATOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE DESIGN WIND LOADS PER ASCE 7-10.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 3. VALUE APPEARS LOW FOR SCOPE OF WORK.
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
  
 1. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 2. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
 3. FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By cthroop Date 2020-08-19 Time 15:23 Rev Time 0.00
Received By cthroop Date 2020-08-19 Time 15:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By cthroop Date 2020-06-29 Time 15:50 Rev Time 0.00
Received By cthroop Date 2020-06-29 Time 10:49 Sent To  
Notes
2020-06-29 16:04:57PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AN UPDATED LOAD CALCULATION.
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 2. PROVIDE AN ELECTRICAL RISER DIAGRAHM.
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S)
 AND TRANSFER SWITCH. SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-08-18 Cont ID  
Sent By medwards Date 2020-08-18 Time 09:56 Rev Time 0.00
Received By medwards Date 2020-08-18 Time 09:56 Sent To  
Notes
2020-08-18 10:30:27MR. SNED CONTACTED ME AND EXPLAINED THAT PERMIT
 #19110160 WAS THE ORIGINAL GAS PERMIT FOR THIS NEW
 RESIDENTIAL HOME. THIS PERMIT WAS APPROVED AND FINALED
 IN THE FIELD. THE DRAWING SHOWS THE GAS LINE TO THE
 GENERATOR. NO NEW PIPING WAS DONE.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-08-13 Cont ID  
Sent By medwards Date 2020-08-13 Time 07:44 Rev Time 0.00
Received By medwards Date 2020-08-13 Time 06:42 Sent To  
Notes
2020-08-13 07:44:552ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20060697
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT THE GAS PERMIT WITH THIS PROJECT.
 FBCFS 107.2.1
  
 2) PLEASE SEE 1ST REVIEWER?S COMMENTS. WE CAN NOT DO A
 GAS REVIEW UNTIL THE GASLINE RISER DIAGRAM AND ALL
 ASSOCIATED DOCUMENTS HAVE BEEN SUBMITTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By cthroop Date 2020-06-29 Time 15:45 Rev Time 0.00
Received By cthroop Date 2020-06-29 Time 10:49 Sent To  
Notes
2020-06-29 15:50:53PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RESIDENTIAL GENERATOR ? CHPT. 1 GAS
  
  
 1. A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 2. PROVIDE THE TOTAL BTU LOAD OF EXISTING GAS
 APPLIANCES - IF ANY. THE BTU LOAD OF THE PROPOSED GAS
 EQUIPMENT MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. NOTE: IF THE EXISTING
 SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE SYSTEM
 PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 3. SUBMIT MANUFACTURERS SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR ANY NEW PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE FOR THE NEW
 INSTALLATION PER 2017 FBC FUEL GAS RES SECS. G2413.4.1,
 G2413.4.2.
  
 5. SUBMIT A COPY OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM.
  
 REFER TO THE 2017 FBC FUEL GAS RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 6. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. PROVIDE A SITE PLAN - GENERATOR SHALL BE LOCATED
 THREE FEET FROM STRUCTURE.
 NFPA 37 ? 4.1.4
 EXHAUST GASES SHALL NOT BE LOCATED WITHIN 5 FEET OF ANY
 BUILDING OPENING OR COMBUSTIBLE CONSTRUCTION.
  
 8. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-31 Cont ID  
Sent By ccarvaja Date 2020-08-28 Time 08:30 Rev Time 0.00
Received By ccarvaja Date 2020-08-12 Time 06:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-02 Cont ID  
Sent By lmarchan Date 2020-07-02 Time 14:24 Rev Time 0.00
Received By lmarchan Date 2020-06-12 Time 15:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-14 Cont ID  
Sent By lcrespo Date 2020-08-14 Time 15:21 Rev Time 0.00
Received By lcrespo Date 2020-08-14 Time 15:20 Sent To  
Notes
2020-08-14 15:21:30NOT REQUIRED FOR GENERATOR

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-29 Cont ID  
Sent By cthroop Date 2020-06-29 Time 14:31 Rev Time 0.00
Received By cthroop Date 2020-06-29 Time 10:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By cthroop Date 2020-08-19 Time 15:23 Rev Time 0.00
Received By cthroop Date 2020-08-19 Time 15:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By cthroop Date 2020-06-29 Time 15:42 Rev Time 0.00
Received By cthroop Date 2020-06-29 Time 10:48 Sent To  
Notes
2020-06-29 15:44:57PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DESIGN PROFESSIONALS
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
 NON-DESIGN PROFESSIONALS
  
 1. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON PLAN SHEETS UNDER THEIR
 AUTHORITY ?
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-08-28 Cont ID  
Sent By kalexand Date 2020-08-28 Time 16:46 Rev Time 0.00
Received By kalexand Date 2020-08-28 Time 16:45 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By kalexand Date 2020-07-02 Time   Rev Time  
Received By   Date 2020-07-02 Time   Sent To I
Notes
2020-07-02 10:26:38ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 7/2/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE CLEARLY INDICATE THE LOCATION OF THE
 GENERATOR WITH THE PROPER SETBACKS FROM THE PROPERTY
 LINE. NOTE THAT PER SEC 94-305(B)(4) MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4FT INTO A
 SETBACK.
 _____________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved