Plan Review Details - Permit 20060671
Plan Review Stops For Permit 20060671
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-05 Cont ID  
Sent By cthroop Date 2020-10-05 Time 11:35 Rev Time 0.00
Received By cthroop Date 2020-10-05 Time 10:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-03 Cont ID  
Sent By cthroop Date 2020-08-03 Time 11:53 Rev Time 0.00
Received By cthroop Date 2020-08-03 Time 09:13 Sent To  
Notes
2020-08-03 12:10:05PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE HAS BEEN ADJUSTED FROM $78,000 TO $223,099 PER
 ICC BUILDING VALUATION DATA.
  
 2. PROVIDE SITE DRAINAGE PLAN.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 3. PROVIDE A SOILS REPORT.
  
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 4. PROVIDE THE FOLLOWING BUILDING PLANS -
  
 4A) FOUNDATION PLAN.
 4B) EXTERIOR WALL SECTIONS.
 4C) ELEVATIONS PLANS.
 4D) DETAIL PAGE.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 5. DESIGNER SHALL SPECIFY CEILING AND WALL INSULATION
 ON PLANS.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. PROVIDE AN ENERGY SUBMITTAL.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 PROVIDE ENERGY GAUGE FORM R405 PER SECTION R405.2 FBC
 EC.
  
 7. SUBMIT PRODUCT APPROVALS FOR WINDOWS AND DOORS.
 UPLOAD EACH PRODUCT APPROVAL TO PROJECT DOX AS ONE
 SUBMITTAL. PROVIDE APPROPRIATE NAME FOR EACH SUBMITTAL.
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 8. REMOVE DOCUMENTS THAT ARE NOT RELEVANT TO THIS
 SUBMITTAL.
  
 9. PROVIDE APPROPRIATE NAME FOR EACH SUBMITTAL.
  
 10. DIGITAL SIGNATURE OF DESIGN PROFESSIONAL IS
 INVALID. SEE SIGNATURE REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-10-20 Cont ID  
Sent By fgiaquin Date 2020-10-20 Time 19:39 Rev Time 0.00
Received By fgiaquin Date 2020-10-20 Time 19:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-26 Cont ID  
Sent By fgiaquin Date 2020-09-26 Time 12:04 Rev Time 0.00
Received By fgiaquin Date 2020-09-26 Time 10:53 Sent To  
Notes
2020-09-26 12:04:24HOLD ON PRINTING UNTIL CONTRACTOR SIGNS PLAN

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-16 Cont ID  
Sent By fgiaquin Date 2020-09-16 Time 19:08 Rev Time 0.00
Received By fgiaquin Date 2020-09-16 Time 18:17 Sent To  
Notes
2020-09-16 19:07:50HOLD ON PRINTING UNTIL ELECTRICAL CONTRACTOR QUALIFER
 SIGNS PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-29 Cont ID  
Sent By fgiaquin Date 2020-07-29 Time 20:35 Rev Time 0.00
Received By fgiaquin Date 2020-07-29 Time 19:43 Sent To  
Notes
2020-07-29 20:34:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. HOW IS THERE AN EXISTING SERVICE ON A NEW HOUSE? IS
 IT A REMODEL OR NEW HOUSE? FBC 107.2.1
  
 2. NO METER SHOWN ON RISER DIAGRAM FBC 107.2.1 NEC220
  
 3. NO WIRE SIZES SHOWN ON RISER DIAGRAM FBC 107.2.1
  
 4. ELEC NOTE #3 IS INCORRECT. CARBON MONOXIDE ALARMS
 ARE NOT REQURED IN ALL SLEEPING AREAS. SMOKE ALARMS ARE
 REQUIRED IN ALL SLEEPPING AREAS AND COMBO SMOKE/CARBON
 ALARMS ARE REQUIRED WITHIN 10? IMMEDIATELY OUTSIDE OF
 ALL SLEEPING AREAS. PROVIDE CORRECTION. FBC-R 314 &315
  
 5. NOTE 18 IS INCORRECT. SMOKE ALARMS MUST BE 36??
 INCHES AWAY FROM ANY A/C SUPPLYS? BATHROOM DOORS OR
 TIPS OF FAN BLADES. PROVIDE CORRECTION. NFPA 72
  
 6. PPROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 7. SHOW WIRE SIZES FOR GEC SYSTEM FBC 107.2.1
  
 8. 240 GENERATOR NOTE SHOWN ON PLAN. GENERATOR WILL
 REQUIRES SEPARATE PLAN AND PERMIT. PUT NOTE ON PLAN
 SAYING GENERATOR REQUIRES SEPARRATE PERMIT. FBC 107.2.1
 FBC 105.1
  
 9. BEDROOM ADJACENT TO KITCHEN NEEDS RECEPTACLE WITHIN
 6? OF DOOR NEC 210.52
  
 10. GARAGE DOOR RECEPTACLE MUST BE GFCI NEC 210.8
  
 11. $78,000 VALUE IS LOW FOR AMOUNT OF WORK SHOWN
  
 CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 12. PLAN MUST BE SIGNED BY ELECTRICAL CONTRACTOR
 QUALIFIER OR DIGITALLY SIGNED BY DESIGN PROFESSIONAL .
 FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 13. NO DESCRIPTION OF WORK IS LISTED IN PERMIT
 APPLICATION FBC 107.2.1
  
 14. SQUARE FOOTAGE FOR HOUSE IN LOAD CALC IS 1360 BUT
 SQUARE FOOTAGE ON PERMIT APP SAY 1976.. PROVIIDE
 ACCURATE LOAD CALC TO INCLUDE ALL LOADS. NEC 220 FBC
 107.2.1
  
 15. RECEPTACLE REQURIED OUTSIDE ON FRONT OF HOME NEC
 210.52E1
  
 16. 200AMP PANEL NOT SHOWN ON PLAN ONLY METER AND SUB
 PANEL?? FBC 107.2.1
  
 17. PUT NOTE ON PLAN THAT LOW VOLTAGE WILL BE A
 SEPARATE PERMIT. FBC 105.1 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-07-27 Cont ID  
Sent By ccole Date 2020-07-27 Time 15:31 Rev Time 0.00
Received By ccole Date 2020-07-27 Time 15:31 Sent To  
Notes
2020-07-27 15:31:57A SEPARATE PERMIT IS REQUIRED FOR THE GAS PIPING
 INSTALLATION- SECTION 107.2.1 WPB. COMPLETE PLANS AND
 SPECIFICATIONS SHALL BE SUBMITTED FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-10-20 Cont ID  
Sent By fgiaquin Date 2020-10-20 Time 19:39 Rev Time 0.00
Received By fgiaquin Date 2020-10-08 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-08 Cont ID  
Sent By lmarchan Date 2020-10-08 Time 06:57 Rev Time 0.00
Received By lmarchan Date 2020-09-17 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-17 Cont ID  
Sent By lmarchan Date 2020-09-17 Time 15:36 Rev Time 0.00
Received By lmarchan Date 2020-09-03 Time 11:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-03 Cont ID  
Sent By shill Date 2020-08-03 Time 13:01 Rev Time 0.00
Received By shill Date 2020-07-07 Time 07:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-08-03 Cont ID  
Sent By lmarchan Date 2020-08-03 Time 13:06 Rev Time 0.00
Received By lmarchan Date 2020-08-03 Time 09:13 Sent To  
Notes
2020-10-21 08:32:21IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 13:22 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 13:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-09-16 Cont ID  
Sent By medwards Date 2020-09-16 Time 06:57 Rev Time 0.00
Received By medwards Date 2020-09-16 Time 06:56 Sent To  
Notes
2020-09-16 06:59:30SUPPORTING DOCUMENTS FAILED TO UPLOAD CORRECTLY. THEY
 ARE NOT READABLE, PLEASE UPLOAD DOCUMENTS AGAIN. COULD
 NOT DO REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-21 Cont ID  
Sent By medwards Date 2020-07-21 Time 10:05 Rev Time 0.00
Received By medwards Date 2020-07-21 Time 09:26 Sent To  
Notes
2020-07-21 10:05:371ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060671
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE MANUAL J CALCULATIONS FOR THE
 MECHANICAL SYSTEM. FBC EC R403.7
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-10-09 Cont ID  
Sent By ccole Date 2020-10-09 Time 14:26 Rev Time 0.00
Received By ccole Date 2020-10-09 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-09-18 Cont ID  
Sent By ccole Date 2020-09-18 Time 12:37 Rev Time 0.00
Received By ccole Date 2020-09-18 Time 10:16 Sent To  
Notes
2020-09-18 12:39:283RD REVIEW FBC-2017 RES.
 PERMIT- 20060671
 9/16/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE WATER HEATER DETAIL APPEARS TO HAVE BEEN CUT-OFF
 AND IS MISSING THE LOCATION OF THE REQUIRED EXPANSION
 TANK- P2903.4.2 FBC RES. THE DETAIL ALSO SHOWS THE HEAT
 TRAP ON THE HW LINE RUNNING THROUGH THE ADJACENT WALL
 INSTEAD IN A LOCATION AS CLOSE TO THE WATER HEATER AS
 POSSIBLE- SECTION R403.5.5 FBC EC. IT APPEARS A PAN
 WILL NOT BE INSTALLED UNDER THE WATER HEATER SO PLEASE
 INDICATE THE RELIEF VALVE DISCHARGE PIPE WILL DISCHARGE
 A MINIMUM OF 1? FROM THE BUILDING PER SECTION R318.5
 FBC RES.
  
 2) ADVISORY: THE REVISED ENERGY COMPLIANCE FORM
 R405-2017 INDICATES THE EFFICIENCY RATING OF THE GAS
 WATER HEATER AT 0.59 ON PAGE 1 AND PAGE 4. THE OVERALL
 REPORT HAS PASSED CODE WITH THE DATA INSERTED, HOWEVER
 PLEASE NOTE THAT PER TABLE C404.2 FBC EC THE MINIMUM
 EFFICIENCY RATING FOR A 40-GALLON GAS-FIRED STORAGE
 TANK WATER HEATER IS 80% E.
  
 3) SHEET EP1: 3RD REQUEST TO SHOW THE 2? WASHING
 MACHINE DRAIN CONNECTING TO A 3? VERTICAL STACK-
 SECTION 406.2 FBC P.
  
 4) EP1: PLEASE RELOCATE THE LAVATORY FIXTURE DRAIN
 CONNECTION SHOWN AT THE BASE OF THE WASHING MACHINE
 STACK TO THE ADJACENT LAVATORY BRANCH DRAIN. THIS IS A
 DOUBLE BOWL SINK AND THE FIXTURE DRAINS WILL TYPICALLY
 SHARE THE COMMON VENT- SECTION P307.1 FBC P.
  
 5) EP1: IN ACCORDANCE WITH THE RESPONSE NARRATIVE
 PLEASE PLACE A LIST OF DEFERRED SUBMITTALS ON THE PLAN
 TO INCLUDE THE WATER HEATER, SHOWER, BATHTUB VALVE,
 SHOWER VALVE, AND THE IN-WALL TANK WATER CLOSET.
 ADVISORY: PLEASE NOTE THE WATER HEATER GALLON SIZE IS
 DETERMINED BY PEAK DEMAND CALCULATIONS PROVIDED BY THE
 MANUFACTURER (NOT PROVIDED) AND IN ACCORDANCE WITH
 TABLE P2903.1 FBC RES.
  
 6) EP1: 2ND REQUEST TO PLACE BOLD NOTES ON THE PLAN
 INDICATING SEPARATE PERMITS ARE REQUIRED FOR THE GAS
 PIPING AND BACKFLOW PREVENTER. PLEASE NOTE COMPLETE
 PLANS, AND EQUIPMENT AND APPLIANCE SPECIFICATIONS ARE
 REQUIRED FOR INSTALLATION OF THE GAS PIPING SYSTEM
 INCLUDING A GAS RISER DRAWING, COMBUSTION AND MAKEUP
 AIR CALCULATIONS, AND VENTING PLANS- SECTION 105.1 AND
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-09-16 Cont ID  
Sent By ccole Date 2020-09-16 Time 09:25 Rev Time 0.00
Received By ccole Date 2020-09-16 Time 07:06 Sent To  
Notes
2020-09-16 09:27:312ND REVIEW FBC-2017 RES.
 PERMIT- 20060671
 9/16/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 PLEASE NOTE THAT FIVE OF THE SUPPORTING DOCUMENTS DID
 NOT UPLOAD PROPERLY AND CANNOT BE OPENED AND REVIEWED
 IN THE PROGRAM. EACH DOC HAS AN ERROR MESSAGE INCLUDING
 THE ENERGY COMPLIANCE SUBMITTAL AND THE COMMENT
 RESPONSE NARRATIVE. THOSE DOCS ARE ESSENTIAL TO
 REVIEWING AND APPROVING THE PLUMBING PLANS.
  
 1) SHEET EP1: 2ND REQUEST TO SHOW THE 2 IN. WASHING
 MACHINE DRAIN CONNECTING TO A 3 IN. VERTICAL STACK-
 SECTION 406.2 FBC P.
  
 2) EP1: INDICATE THE REQUIRED MINIMUM 1/4 IN. AND
 MAXIMUM 1/2 IN. PER FT. SLOPE TO DRAIN IN THE SHOWER
 PAN DETAIL- SECTION P2709.1 FBC RES.
  
 3) EP1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE ON
 THE PLAN AND SUBMIT THE MANUFACTURER'S SPECIFICATIONS
 FOR THE UNIT AS PREVIOUSLY REQUESTED. PLEASE NOTE THAT
 A STORAGE TYPE WATER HEATER WILL REQUIRE INSTALLATION
 OF A DEVICE TO CONTROL THERMAL EXPANSION WHICH MOST
 TYPICALLY IS A THERMAL EXPANSION TANK- SECTION P2903.4
 FBC RES. PLEASE NOTE THE EFFICIENCY RATING OF THE WATER
 HEATER SHALL BE INCLUDED IN THE ENERGY COMPLIANCE
 SUBMITTAL WHICH CANNOT BE REVIEWED AT THE PRESENT TIME-
 TABLE C404.2 FBC EC.
  
 4) EP1: PLEASE PROVIDE A NOTE OR DETAIL SHOWING THE
 DISCHARGE PIPING SERVING THE WATER HEATER
 PRESSURE-RELIEF VALVE, TEMPERATURE RELIEF VALVE, OR
 COMBINATION VALVE IS IN COMPLIANCE WITH SECTION
 P2904.6.1 ITEMS 1-14. IF DISCHARGING INTO A PAN, A
 DRAIN LINE FROM THE PAN SHALL TERMINATE A MINIMUM A
 MINIMUM OF 1FT. FROM THE BUILDING- SECTION R318.5 FBC
 RES.
  
 5) EP1, WATER RISER: WATER HAMMER ARRESTOR MISSING AT
 DISHWASHER SUPPLY LINE- SECTION P2717.1 FBC RES. PLEASE
 NOTE TYPICALLY A DISHWASHER GETS ONLY A COLD WATER
 SUPPLY FEED - HOT AND COLD SUPPLY LINES ARE SHOWN. A)
 2ND REQUEST TO SHOW THE SUPPLY LINE TO THE REFRIGERATOR
 ICE MAKER (IF TO BE INSTALLED) AND THE REQUIRED WATER
 HAMMER ARRESTOR AND BACKFLOW DEVICE- SECTIONS P2717.1,
 P2902.1 P2903.5 FBC RES.
  
 6) 2ND REQUEST TO SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR:
 A) WATER HEATER- SECTION P2801.3 FBC RES.
 B) SHOWER AND BATHTUB VALVES- SECTIONS P2708.4 &
 P2713.3.
 C) IN-WALL TANK TOILET- SECTION P2712.1.
 PLEASE NOTE THE SHOWER VALVE, BATHTUB VALVE, AND
 IN-WALL TANK TOILET SUBMITTALS MAY BE DEFERRED. PLEASE
 PLACE A NOTE ON THE PLAN IF APPLICABLE.
  
 6) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED
 FOR THE GAS PIPING INSTALLATIONS TO THE WATER HEATER,
 DRYER, AND RANGE- SECTION 107.2.1 WPB. PLACE A NOTE ON
 THE PLAN ACCORDINGLY.
  
 7) EP1: THE SIGNATURE OF THE LICENSED CONTRACTOR OR
 QUALIFIER WHO PREPARED THE PLUMBING DRAWINGS SHALL BE
 ON THE PLAN PER SECTION 107.1 WPB AND AND FLORIDA
 STATUTES 471.003(2)(H) & 471.025. IF THE DESIGNER IS A
 FL. LICENSED ENGINEER OR ARCHITECT, THE PLAN SHALL BEAR
 HIS/HER ELECTRONIC SEAL AND SIGNATURE- FL. STATUTES
 471.025, 481.221 AND SECTIONS 61G1-16.005, 61G15-23.005
 FLORIDA ADMINISTRATIVE CODE.
  
 8) ADVISORY: PLEASE NOTE THAT A FL. LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By ccole Date 2020-07-27 Time 15:25 Rev Time 0.00
Received By ccole Date 2020-07-27 Time 12:41 Sent To  
Notes
2020-07-27 15:26:211ST REVIEW FBC-2017 RES.
 PERMIT- 20060671
 7/27/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3: SHOW THE DIMENSIONS OF THE SHOWER AND THE
 BATHTUB IN THE MASTER BATHROOM, AND THE DIMENSIONS OF
 THE SHOWER IN BATH 2- SECTION P2708.1 FBC RES.
  
 2) SHEET EP-1: THE PLUMBING RISER IS NOT CODE
 COMPLIANT.
 A) NO VENTS ARE SHOWN FOR THE MASTER BATH SHOWER AND
 TUB- SECTION P3101.2.1 FBC RES.
 B) THE MASTER BATH FIXTURES AND POWDER ROOM FIXTURES
 ARE NOT BEING PROPERLY VENTED- SEE SECTIONS P3108.1 &
 P3108.2.1 FBC RES. IN ORDER FOR THE TOILET TANK VENT TO
 SERVE AS THE DRY VENT FOR THE HORIZONTAL WET VENT
 SERVING THE TWO BATH GROUPS, IT MUST CONNECT
 HORIZONTALLY TO THE HORIZONTAL WET VENT- THE DRAWING
 SHOWS A VERTICAL CONNECTION. ADDITIONALLY, NOT MORE
 THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION-
 THE DRAWING SHOWS THREE BATH FIXTURES.
 C) ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. THE
 CLOTHES WASHING MACHINE FIXTURE DRAIN- P3108.1 SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. PLEASE
 NOTE THAT THE 2? WASHING MACHINE DRAIN SHALL CONNECT TO
 A 3? FIXTURE BRANCH OR VERTICAL STACK- SECTION 406.2
 D) THE ISOMETRIC FOR BATH-2 SHOWS TWO FIXTURES
 DISCHARGING UPSTREAM OF THE DRY VENT AT THE LAVATORY-
 ONLY ONE FIXTURE IS ALLOWED TO DISCHARGE UPSTREAM-
 SECTION P3108.1.
  
 3) PROVIDE A WATER RISER DRAWING SHOWING THE WATER
 DISTRIBUTION PIPING RUNS INCLUDING THE TYPES AND SIZES
 OF PIPING, AND SHUT OFF VALVE LOCATIONS- SECTION
 107.3.5.3 WPB. PLEASE INCLUDE THE SUPPLY LINES TO THE
 DISHWASHER AND REFRIGERATOR ICE MAKER SHOWING THE
 REQUIRED BACKFLOW PREVENTERS AND WATER HAMMER
 ARRESTORS- SECTIONS P2717.1, P2902.1 P2903.5 FBC RES.
  
 4) PROVIDE A SHOWER PAN DETAIL- SECTIONS P2709.1 &
 P2709.2 FBC RES.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR:
 A) WATER HEATER- SECTION P2801.3 FBC RES.
 B) SHOWER AND BATHTUB VALVES- SECTIONS P2708.4 &
 P2713.3.
 C) IN-WALL TANK TOILET- SECTION P2712.1.
  
 6) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED
 FOR THE GAS PIPING INSTALLATIONS TO THE WATER HEATER,
 DRYER, AND RANGE- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2020-10-05 Cont ID  
Sent By cthroop Date 2020-10-05 Time 11:35 Rev Time 0.00
Received By cthroop Date 2020-10-05 Time 10:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-08-03 Cont ID  
Sent By cthroop Date 2020-08-03 Time 11:49 Rev Time 0.00
Received By cthroop Date 2020-08-03 Time 09:13 Sent To  
Notes
2020-08-03 11:53:15PLAN REVIEW - ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED PER FBC 105.1.
  
 2. SUBMIT PRODUCT APPROVALS FOR ROOFING SYSTEM
 COMPONENTS. EACH PRODUCT APPROVAL SHALL BE UPLOADED TO
 PROJEC DOX AS ONE PDF. PROPER NAMING OF SUBMITTAL
 DOCUMENTRS IS REQUIRED.
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-10-20 Cont ID  
Sent By fgiaquin Date 2020-10-20 Time 19:39 Rev Time 0.00
Received By fgiaquin Date 2020-10-20 Time 19:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-10-05 Cont ID  
Sent By cthroop Date 2020-10-05 Time 11:36 Rev Time 0.00
Received By cthroop Date 2020-10-05 Time 10:42 Sent To  
Notes
2020-10-05 11:37:53PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET / DIGITAL SIGNATURE IS
 NOT CONSIDERED A DIGITAL SIGNATURE.
  
 EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF
 (OR MAIL) ONE PAPER ORIGINAL WITH A WET SEAL AND
 SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 NOTE: APPLICANT INTENDS TO SUBMIT PAPER COPY WITH SET
 SEAL AND SIGNATURE.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By cthroop Date 2020-08-03 Time 11:46 Rev Time 0.00
Received By cthroop Date 2020-08-03 Time 11:07 Sent To  
Notes
2020-08-03 11:49:16PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DESIGN PROFESSIONALS
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
 NOTE: YOU MAY SUBMIT A PAPER PLAN WITH WET SIGNATURE
 AND SEAL AFTER ALL REVIEWS ARE COMPLETE.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-21 Cont ID  
Sent By medwards Date 2020-07-21 Time 10:09 Rev Time 0.00
Received By medwards Date 2020-07-21 Time 10:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By kalexand Date 2020-10-06 Time 13:24 Rev Time 0.00
Received By kalexand Date 2020-10-06 Time 13:22 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By kalexand Date 2020-07-24 Time 16:28 Rev Time 0.00
Received By kalexand Date 2020-07-24 Time 16:28 Sent To I
Notes
2020-07-24 17:06:59ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 7/24/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED HOME ON AN
 ELEVATION PLAN. PURSUANT TO THE ZLDR, SECTION 94-611,
 FOR BUILDINGS, THE HEIGHT SHALL BE MEASURED AS THE
 VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE
 FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF
 THE TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK
 LINE OF A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL
 BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL
 ROOFS. (HEIGHT OF STRUCTURE) THE HEIGHT SHALL BE
 MEASURED AS THE VERTICAL DISTANCE FROM THE AVERAGE
 ELEVATION OF THE FINISHED GRADE OF THE BUILDING TO THE
 MEAN HEIGHT LEVEL BETWEEN EAVES AND RIDGE FOR GABLE,
 HIP, AND GAMBREL ROOFS.
  
 2. PROVIDE A LANDSCAPE PERMIT. IF YOU DO NOT HAVE A
 LANDSCAPE PERMIT, PLEASE SUBMIT AN AFFIDAVIT.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  