Plan Review Details - Permit 20060658
Plan Review Stops For Permit 20060658
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-21 Cont ID  
Sent By jbrooks Date 2020-07-21 Time 10:45 Rev Time 0.00
Received By jbrooks Date 2020-07-21 Time 10:45 Sent To  
Notes
2020-07-21 10:45:23JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC R 310.4. REVISE PLAN TO SHOW REQUIRED MEANS OF
 EGRESS. INCLUDE ROOM DESIGNATION.
 2. SUBMITTED PRODUCT APPROVAL FL16893-R4 HAS BEEN
 REVISED TO FL16893-R5. PLEASE PROVIDE TWO SETS. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-15 Cont ID  
Sent By pvalenti Date 2020-06-15 Time 11:04 Rev Time 0.00
Received By pvalenti Date 2020-06-15 Time 11:04 Sent To  
Notes
2020-06-15 11:06:34PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
 3. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-21 Cont ID  
Sent By jbrooks Date 2020-07-21 Time 10:45 Rev Time 0.00
Received By jbrooks Date 2020-07-21 Time   Sent To  
Notes
2020-07-18 09:31:16ROUTED TO BLDG. MISC 1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-15 Cont ID  
Sent By pvalenti Date 2020-06-15 Time 11:06 Rev Time 0.00
Received By pvalenti Date 2020-06-11 Time 15:00 Sent To  
Notes
2020-06-11 15:01:11ROUTED TO BLDG <$5K