Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-07-09 Cont ID  
Sent By rmcphers Date 2020-07-09 Time 13:22 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-24 Cont ID  
Sent By cthroop Date 2020-08-24 Time 16:06 Rev Time 0.00
Received By cthroop Date 2020-08-24 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By cthroop Date 2020-07-09 Time 16:09 Rev Time 0.00
Received By cthroop Date 2020-07-09 Time 16:07 Sent To  
Notes
2020-07-09 16:09:19PLAN REVIEW - ELECTRIC
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ATS SPECIFICATIONS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By ccole Date 2020-08-20 Time 09:30 Rev Time 0.00
Received By ccole Date 2020-08-14 Time 14:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By ccole Date 2020-07-09 Time 16:06 Rev Time 0.00
Received By ccole Date 2020-07-09 Time 15:53 Sent To  
Notes
2020-07-09 16:13:261ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20060502
 7/9/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. PLEASE PROVIDE CORRECTED
 PLANS ADDRESSING THE FOLLWING COMMENTS.
  
 1) GAS ISOMETRIC DRAWING:
 A) IN ORDER TO ENSURE A SAFE OPERATING SYSTEM THE
 DRAWING MUST BE MODIFIED TO SHOW THE ENTIRE SYSTEM
 INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST
 REMOTE OUTLET.THE BTUH LOAD OF EACH EXISTING APPLIANCE
 AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON
 THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES.
 B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND ALL
 BRANCH LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3.
 B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 C) CORRECT THE 576,000 BTUH LOAD LISTED FOR THE
 GENERATOR. THE SUBMITTED SPECS ON PAGE 3 INDICATE
 375.000 BTUH FULL LOAD FOR MODEL RG032- 32KW - G2413.2
 FBC RES.
  
 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH
 MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET
 AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION
 G2421.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-24 Cont ID  
Sent By cthroop Date 2020-08-24 Time 16:06 Rev Time 0.00
Received By cthroop Date 2020-08-13 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-09 Cont ID  
Sent By ccole Date 2020-07-09 Time   Rev Time 0.00
Received By ccole Date 2020-06-22 Time 14:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-14 Cont ID  
Sent By ccole Date 2020-08-14 Time 16:07 Rev Time 0.00
Received By ccole Date 2020-08-14 Time 14:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-09 Cont ID  
Sent By ccole Date 2020-07-09 Time 16:13 Rev Time 0.00
Received By ccole Date 2020-07-09 Time 15:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-08-14 Cont ID  
Sent By ccole Date 2020-08-14 Time 16:08 Rev Time 0.00
Received By ccole Date 2020-08-14 Time 16:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By rmcphers Date 2020-07-09 Time 13:22 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 13:22 Sent To  
Notes
2020-07-09 13:23:41SLAB ENGINEERING = SIGNED AND SEALED DRAWINGS NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By rthermid Date 2020-06-29 Time   Rev Time  
Received By rthermid Date 2020-06-29 Time   Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved