Plan Review Details - Permit 20060478
Plan Review Stops For Permit 20060478
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-18 Cont ID  
Sent By jgomez Date 2020-08-18 Time 13:23 Rev Time 0.00
Received By jgomez Date 2020-08-18 Time 13:13 Sent To  
Notes
2020-08-19 10:01:22CONCRETE PAD DRAWING WITH ENGINEER'S ORIGINAL
 SEAL/SIGNATURE WAS UPLOADED TO PROJECTDOX. HARD COPY
 SENT TO STORAGE. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By rmcdouga Date 2020-08-03 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2020-08-03 Time 13:53 Sent To  
Notes
2020-08-03 13:54:19THE GENERATOR PAD DRAWING NEEDS DIGITAL SIGNATURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-01 Cont ID  
Sent By rmcdouga Date 2020-07-01 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2020-07-01 Time 10:11 Sent To  
Notes
2020-07-01 10:23:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PREFAB GENERATOR PAD DRAWING IS REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE. FS 71 AND FAC 61G15
  
 2) THE PREFAB GENERATOR PAD DRAWING SPECIFIES THE WIND
 LOAD PRESSURE CAPACITY OF A SPECIFIC GENERATOR AND THE
 PAD. THE REQUIRED WIND LOAD PRESSURES FOR THE LOCATION
 IS NOT PROVIDED. THE ENGINEERING THAT WAS SUBMITTED
 REQUIRES SITE SPECIFIC ENGINEERING TO DETERMINE THE
 WIND LOAD PRESSURES REQUIRED AT THE LOCATION OF THE
 PROJECT. FBC 107

Review Stop E ELECTRICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2020-07-01 Time   Rev Time 0.00
Received By cthroop Date 2020-07-01 Time 11:38 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-07-01 Cont ID  
Sent By cthroop Date 2020-07-01 Time 12:02 Rev Time 0.00
Received By cthroop Date 2020-07-01 Time 11:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-05 Cont ID  
Sent By lmarchan Date 2020-09-05 Time 08:37 Rev Time 0.00
Received By lmarchan Date 2020-08-26 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-25 Cont ID  
Sent By lmarchan Date 2020-08-25 Time 07:00 Rev Time 0.00
Received By lmarchan Date 2020-07-23 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-06 Cont ID  
Sent By lmarchan Date 2020-07-06 Time 08:37 Rev Time 0.00
Received By lmarchan Date 2020-06-16 Time 14:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-01 Cont ID  
Sent By cthroop Date 2020-07-01 Time 12:00 Rev Time 0.00
Received By cthroop Date 2020-07-01 Time 11:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-08-18 Cont ID  
Sent By jgomez Date 2020-08-18 Time 13:21 Rev Time 0.00
Received By jgomez Date 2020-08-18 Time 13:20 Sent To  
Notes
2020-08-04 13:36:41ORIGINAL SIGNATURE:
 CONCRETE PAD ENGINEERING DRAWING 17-3961.1 SIGNED BY
 RICHARD NEET P.E. ON 04/15/2019. SENT TO STORAGE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-08-04 Cont ID  
Sent By jgomez Date 2020-08-03 Time 17:41 Rev Time 0.00
Received By jgomez Date 2020-08-03 Time 17:37 Sent To  
Notes
2020-08-04 09:21:541-ENGINEER WHO SIGNED AND SEALED THE CONCRETE PAD
 ENGINEERING IS NOT THE SAME ENGINEER WHO SIGNED/SEALED
 THE ORIGINAL ENGINEERING SUBMITTED. SEC. 107.3 CITY
 AMENDMENTS.
 THERE ARE THERE TWO OPTIONS TO ADDRESS THIS ISSUE:
 1)SUBMIT ENGINEERING WITH ORIGINAL SEAL/SIGNATURE OF
 THE ENGINEER WHO SIGNED THE ORIGINAL SUBMITTAL. OR
 2) UPLOAD TO PROJECTDOX NEW DOCUMENT SIGNED/SEALED BY
 THE NEW ENGINEER FOR BUILDING REVIEW.
 NOTE: IN ORDER TO EXPEDITE THE REVIEW PROCESS, IT IS
 PREFERABLE TO DOWNLOAD THE NEW ENGINEERING WITH A
 DIGITAL SIGNATURE. OTHERWISE, HARD COPY WITH ORIGINAL
 SEAL/SIGNATURE IS REQUIRED. WE CAN USE THE ONE
 SUBMITTED NOW IF IT MATCHES THE ONE THAT WAS DOWNLOADED
 TO PROJECTDOX.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By rmcdouga Date 2020-08-03 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2020-08-03 Time 13:56 Sent To  
Notes
2020-08-03 13:58:38ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE PAPER DRAWINGS. NO PHOTOCOPY OR
 OTHER FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS
 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-01 Cont ID  
Sent By cthroop Date 2020-07-01 Time 12:00 Rev Time 0.00
Received By cthroop Date 2020-07-01 Time 11:38 Sent To  
Notes
2020-07-01 12:02:11PLAN REVIEW - SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DESIGN PROFESSIONALS
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-09-03 Cont ID  
Sent By kalexand Date 2020-09-03 Time 11:30 Rev Time 0.00
Received By kalexand Date 2020-09-03 Time 11:30 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-08-24 Cont ID  
Sent By kalexand Date 2020-08-24 Time 16:52 Rev Time 0.00
Received By kalexand Date 2020-08-24 Time 16:52 Sent To I
Notes
2020-08-24 16:56:29ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 8/24/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By kalexand Date 2020-07-02 Time   Rev Time  
Received By   Date 2020-07-02 Time   Sent To I
Notes
2020-07-02 17:02:22ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 7/2/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE GENERATOR PROJECTS TO FAR INTO THE 25FT FRONT
 SETBACK. PER SEC. 94-305(B)(4) MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4FT INTO A SETBACK.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved