Plan Review Details - Permit 20060456
Plan Review Stops For Permit 20060456
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-10-25 Cont ID  
Sent By jwitmer Date 2020-10-25 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2020-10-25 Time 16:03 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-08-25 Cont ID  
Sent By jwitmer Date 2020-08-25 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2020-08-24 Time 15:16 Sent To  
Notes
2020-08-25 09:39:36ASBESTOS COMMERCIAL.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-06-15 Cont ID  
Sent By jwitmer Date 2020-06-15 Time 10:13 Rev Time 0.00
Received By jwitmer Date 2020-06-15 Time 07:46 Sent To  
Notes
2020-06-15 10:13:20ASBESTOS COMMERCIAL.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-11-17 Cont ID  
Sent By jwitmer Date 2020-11-17 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2020-11-17 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-10-27 Cont ID  
Sent By jwitmer Date 2020-10-27 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2020-10-25 Time 16:03 Sent To  
Notes
2020-10-27 11:57:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060456
 ADD: 1101 N. OLIVE AVE.
 CONT: S. D. CHURCH & SONS
 TEL:1- 386-314-3001
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. AUGUST 25TH / 2020
 ACTION: DENIED
  
 1) COMPLIED. ACCESSIBLE PARKING AND ACCESS AISLE.
  
 2) COMPLIED. LIFE SAFETY PLAN 1ST FLOOR & 2ND FLOOR.
  
 3) COMPLIED/ VERTICAL ACCESSIBILITY/ DISPROPORTIONATE
 COST.
  
 4)SEMI- COMPLIED, ADDITIONAL COMMENTS. SPOKE WITH THE
 CONTRACTOR ABOUT THE REQUIRED 20% DISPROPORTIONATE COST
 LETTER ON THE COMPANY LETTER HEAD AND WHAT ITEMS CAN BE
 INCLUDED UNDER THE 20% DISPROPORTIONATE COST. THE FIRST
 FLOOR SHOWS VARIOUS AREAS WHERE ACCESSIBLE UPGRADES ARE
 GOING TO BE MADE BUT THE 2ND FLOOR DOES SHOW
 ALTERATIONS TO THE 2ND FLOOR. THE RESTROOM 2 AND THE
 PRIVATE BATHROOM AS WELL AS DOORS TO THE RESTROO#2 AND
 PRIVATE BATHROOM.
  
 WHEN YOU REMODEL A ELEMENT AS DOORS AND OR RESTROOMS
 AND OR BATHROOMS THEN THEY HAVE TO BE BROUGHT UP TO THE
 CURRENT CODE STANDARDS. 2017 EXISTING BUILDING CODE.
 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 UNDER THE EXISTING BUILDING CODE EACH PORTION OF THIS
 CODE LEVEL I, LEVEL 2 OR LEVEL 3 ALL REFER BACK TO THE
 ACCESSIBILITY CODE. IF ELEMENTS ARE NOT TOUCHED THEN
 THEY CAN STAY AS THEY ARE. THE DISPROPORTIONATE COST
 KICKS IN TRYING TO MAKE THE BUILDING OVER A SERIES OF
 SMALLER RENOVATIONS. YOU SHOW HOW YOU HAVE MET THE
 DISPROPORTIONATE COST FOR THE VERTICAL ACCESSIBILITY,
 BUT THAT DOES NOT RELIEVE YOU FROM UPGRADING THE 2ND
 FLOOR WHERE WORK IS SHOWN TO BE PREFORMED.
  
  
 DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO
 MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR
 THE DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW
 HOW THEY ARE GOING TO SPEND THE 20% DISPROPORTIONATE
 FUNDS LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING
 SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 5A-C) COMPLIED.
  
 5D)SEMI-COMPLIED. SHEET A-3 DOES NOT SHOW A HIGH- LOW
 DRINKING FOUNTAIN. THE 1ST AND 2ND FLOOR COMBINED
 OCCUPANT LOAD IS 27 OCCUPANTS REQUIRING DRINKING
 FOUNTAINS. THE FLOOR PLAN DOES SHOW A HIGH/ LOW
 DRINKING FOUNTAIN AND 30X 48 CLEAR FLOOR SPACE. SHEET
 A4 SHOWS ELEVATIONS FOR ELEMENTS WITHIN THE RESTROOMS
 BUT MISSING ELEVATIONS FOR THE DRINKING FOUNTAIN AND
 COMPLIANCE WITH:
  
 DRINKING FOUNTAINS.
 5D)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7. SHOW ELEVATION VIEW WITH SPOUT HEIGHTS.
  
 5D)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH. SHOW WITH ELEVATION VIEW, DOES THIS
 TYPE OF DRINKING FOUNTAIN THE BOTTOM OF THE SHROUD LESS
 THAN 27 INCHES OFF THE FLOOR FOR BOTH HIGH & LOW
 DRINKING FOUNTAINS?
  
 5D)(3) COMPLIED. 30X48 CLEAR FLOOR SPACE.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-25 Cont ID  
Sent By jwitmer Date 2020-08-25 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2020-08-24 Time 15:15 Sent To  
Notes
2020-08-25 09:36:132017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060456
 ADD: 1101 N. OLIVE AVE.
 CONT: S. D. CHURCH & SONS
 TEL:1- 386-314-3001
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. AUGUST 25TH / 2020
 ACTION: DENIED
  
 1) COMPLIED. ACCESSIBLE PARKING AND ACCESS AISLE.
  
 2) COMPLIED. LIFE SAFETY PLAN 1ST FLOOR & 2ND FLOOR.
  
 3) 2ND REQUEST. SPOKE WITH THE CONTRACTOR ABOUT THIS
 ISSUE, DISPROPORTIONATE COST MAY PROHIBIT VERTICAL
 ACCESSIBILITY WILL SUPPLY LETTER ON CONTRACTORS LETTER
 HEAD WHERE THE DISPROPORTIONATE FUNDS WILL BE SPENT UP
 TO 0.20 % OF THE CONTRACT VALUE OR $21,000.00 DOLLARS.
 SHEET A-3 THE 2ND FLOOR DOES NOT SHOW A ACCESSIBLE
 MEANS OF EGRESS. 2017 FBC-ACCESSIBILITY CODE SECTION
 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 THE 2017 FBC-ACCESSIBILITY CODE REQUIRES VERTICAL
 ACCESSIBILITY UNDER 201.1.1. PLEASE ALSO SEE ADVISORY
 SCOPING 201.1 SCOPE (GREY BOX) FLORIDA REQUIREMENTS
 MAYBE WAIVED DOWN TO THE REQUIREMENTS OF THE ADA
 STANDARDS. SEE THE ACCESSIBILITY CODE FOR LIMITED-
 USE-APPLICATION ELEVATORS (LULA).
  
 4) SPOKE WITH THE CONTRACTOR ABOUT THE REQUIRED 20%
 DISPROPORTIONATE COST LETTER ON THE COMPANY LETTER HEAD
 AND WHAT ITEMS CAN BE INCLUED UNDER THE 20%
 DISPROPORTIONATE COST. THE FIRST FLOOR SHOWS VARIOUS
 AREAS WHERE ACCESSIBLE UPGRADES ARE GOING TO BE MADE
 BUT THE 2ND FLOOR DOES NOT SHOW ANY NEW ACCESSIBLE
 UPGRADES.
 DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO
 MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR
 THE DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW
 HOW THEY ARE GOING TO SPEND THE 20% DISPROPORTIONATE
 FUNDS LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING
 SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 5A-C) COMPLIED.
  
 5D) NEW COMMENT. SHEET A-3 DOES NOT SHOW A HIGH- LOW
 DRINKING FOUNTAIN. THE 1ST AND 2ND FLOOR COMBINED
 OCCUPANT LOAD IS 27 OCCUPANTS REQUIRING DRINKING
 FOUNTAINS.
  
 DRINKING FOUNTAINS.
 5D)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 5D)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY IN TO THE
 CIRCULATION PATH.
  
 5D)(3) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-15 Cont ID  
Sent By jwitmer Date 2020-06-15 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2020-06-15 Time 07:46 Sent To  
Notes
2020-06-15 10:11:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060456
 ADD: 1101 N. OLIVE AVE.
 CONT: S. D. CHURCH & SONS
 TEL:1- 386-314-3001
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 15TH/ 2020
 ACTION: DENIED
  
 1) SHEET A-1 SHOWS THE ACCESSIBLE PARKING AND ACCESS
 AISLE TO BE RESTRIPED. THE PLAN SHOWS SINGLE STRIPPING.
 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL
 BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN
 ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING. 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE
 SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 FEET
 WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND SHALL
 HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
  
 2) SHEET A-3 SHOWS THE NEW PROPOSED 1ST FLOOR AND 2ND
 FLOOR PLAN. THERE IS NO LIFE SAFETY PLAN FOR THE 1ST
 FLOOR NOR 2ND FLOOR. PEASE SHOW THE COMMON PATH OF
 TRAVEL FOR THE 1ST FLOOR IN COMPLIANCE WITH 2017 FBC-B
 TABLE 1006.2.1 & FOR THE 2ND FLOOR IN ACCORDANCE WITH:
 2017 FBC-B 1006.3.2(2).
  
 3) SHEET A-3 THE 2ND FLOOR DOES NOT SHOW A ACCESSIBLE
 MEANS OF EGRESS. 2017 FBC-ACCESSIBILITY CODE SECTION
 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 THE 2017 FBC-ACCESSIBILITY CODE REQUIRES VERTICAL
 ACCESSIBILITY UNDER 201.1.1. PLEASE ALSO SEE ADVISORY
 SCOPING 201.1 SCOPE (GREY BOX) FLORIDA REQUIREMENTS
 MAYBE WAIVED DOWN TO THE REQUIREMENTS OF THE ADA
 STANDARDS. SEE THE ACCESSIBILITY CODE FOR LIMITED-
 USE-APPLICATION ELEVATORS (LULA).
  
 4) THE FIRST FLOOR SHOWS VARIOUS AREAS WHERE ACCESSIBLE
 UPGRADES ARE GOING TO BE MADE BUT THE 2ND FLOOR DOES
 NOT SHOW ANY NEW ACCESSIBLE UPGRADES.
 DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO
 MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR
 THE DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW
 HOW THEY ARE GOING TO SPEND THE 20% DISPROPORTIONATE
 FUNDS LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING
 SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 5) SHEET A-4 SHOWS VARIOUS ACCESSIBILITY DETAILS:
 5A) THE MIRROR OVER THE SINK SHOWS THE BOTTOM OF THE
 MIRROR FRAME AT 40 INCHES ABOVE THE FINISH FLOOR, NOT
 THE REFLECTIVE SURFACE.
 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 5B) TOILET PAPER DISPENSERS. 2017 ACCESSIBILITY CODE
 SECTION 604.7. TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7-9 INCHES MAXIMUM IN FRONT OF
 THE WATER CLOSET MEASURED TO THE CENTER LINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND THE GRAB BARS.
  
 5C) THERE ARE NO DETAILS FOR AN ACCESSIBLE BREAK ROOM
 SINK, NOR DOES SHEET A-3 DOES NOT SHOW THE CLEAR FLOOR
 SPACE FOR THE BREAK ROOM SINK.
 SINKS. 2017 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED,
 SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED CLEAR FLOOR
 SPACE ON THE FLOOR PLAN.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2020-11-19 Cont ID  
Sent By jleahy Date 2020-11-19 Time 07:55 Rev Time 0.00
Received By jleahy Date 2020-11-19 Time 07:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-11-17 Cont ID  
Sent By jleahy Date 2020-11-17 Time 17:17 Rev Time 0.00
Received By jleahy Date 2020-11-17 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-10-27 Cont ID  
Sent By jleahy Date 2020-10-27 Time 11:48 Rev Time 0.00
Received By jleahy Date 2020-10-27 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-08-26 Cont ID  
Sent By fgiaquin Date 2020-08-26 Time 22:24 Rev Time 0.00
Received By fgiaquin Date 2020-08-26 Time 21:22 Sent To  
Notes
2020-08-26 22:24:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MUST COMPLY WITH CURRENT ENERGY CODES PER FBC ENERGY
 CONSERVATION BOOK. NEED RECEPTACLE CONTROL, OCC
 SENSORS, ETC.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By jleahy Date 2020-06-29 Time 15:02 Rev Time 0.00
Received By jleahy Date 2020-06-29 Time 11:49 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-10-27 Cont ID  
Sent By jleahy Date 2020-10-27 Time 11:49 Rev Time 0.00
Received By jleahy Date 2020-10-27 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-11-16 Cont ID  
Sent By pleduc Date 2020-11-16 Time   Rev Time 0.00
Received By pleduc Date 2020-11-16 Time 15:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-10-23 Cont ID  
Sent By pleduc Date 2020-10-23 Time   Rev Time 0.00
Received By pleduc Date 2020-10-23 Time 10:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-08-13 Cont ID  
Sent By pleduc Date 2020-08-13 Time   Rev Time 0.00
Received By pleduc Date 2020-08-13 Time 13:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-06-12 Cont ID  
Sent By pleduc Date 2020-06-12 Time   Rev Time 0.00
Received By pleduc Date 2020-06-12 Time 12:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-11-19 Cont ID  
Sent By jleahy Date 2020-11-19 Time 07:55 Rev Time 0.00
Received By jleahy Date 2020-11-18 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-11-17 Cont ID  
Sent By jleahy Date 2020-11-17 Time 17:17 Rev Time 0.00
Received By jleahy Date 2020-11-13 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-10-27 Time 11:59 Rev Time 0.00
Received By lmarchan Date 2020-10-22 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-26 Cont ID  
Sent By fgiaquin Date 2020-08-26 Time 22:24 Rev Time 0.00
Received By fgiaquin Date 2020-08-12 Time 07:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-07-02 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-11 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-11-19 Cont ID  
Sent By medwards Date 2020-11-19 Time 07:45 Rev Time 0.00
Received By medwards Date 2020-11-19 Time 07:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By medwards Date 2020-11-16 Time 16:10 Rev Time 0.00
Received By medwards Date 2020-11-16 Time 15:49 Sent To  
Notes
2020-11-16 16:10:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060456
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE SPECIFICATIONS FOR THE BATH
 EXHAUST FANS. FBC 107.2
  
 2) PLEASE PROVIDE CFM OF BATH EXHAUST FANS: FBC M TABLE
 403.3.1.1 NOTE E-RATES ARE PER WATER CLOSET OR URINAL.
 THE HIGHER RATE SHALL BE PROVIDED WHERE THE EXHAUST
 SYSTEM IS DESIGNED TO OPERATE INTERMITTENTLY. THE LOWER
 RATE SHALL BE PERMITTED ONLY WHERE THE EXHAUST SYSTEM
 IS DESIGNED TO OPERATE CONTINUOUSLY WHILE OCCUPIED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-11-16 Cont ID  
Sent By ccole Date 2020-11-16 Time 08:21 Rev Time 0.00
Received By ccole Date 2020-11-16 Time 07:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-10-23 Cont ID  
Sent By ccole Date 2020-10-23 Time 13:31 Rev Time 0.00
Received By ccole Date 2020-10-23 Time 09:33 Sent To  
Notes
2020-10-23 13:32:113RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20060456
 10/23/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW WILL BE MARKED AS PASSED
 OR FAILED. I HAVE ADDED NOTES TO FAILED COMMENTS FOR
 FUTHER CLARIFICATION.
  
 1) PASSED. SHEET P1: THE SINK FIXTURE DRAIN MUST
 CONNECT TO THE 3" BUILDING DRAIN DOWNSTREAM OF THE WC
 AND LAVATORY PER SECTIONS 912.1 AND 912.2.1 FBC P.
  
 2) FAILED P1: PROVIDE A WATER RISER DRAWING SHOWING
 PIPE SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER
 ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC.
 A) FULL OPEN SHUT OFF VALVES ARE REQUIRED AT THE BASES
 OF THE WATER RISERS UP TO THE SECOND FLOOR- SECTION
 606.1(4) FBC P.
 B) IT APPEARS THAT THE DISTANCE FROM THE WATER HEATER
 TO THE MOST REMOTE FIXTURE BEING SUPPLIED WITH HOT
 WATER EXCEEDS THE MAXIMUM 50 FT DISTANCE. PLEASE VERIFY
 COMPLIANCE WITH SECTION 607.2
  
 3) FAILED. P1: PROVIDE A PLUMBING FIXTURE AND DEVICE
 SCHEDULE- SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
 SCHEDULES NOT PROVIDED. PLEASE NOTE THAT THE SPEC
 SHEETS SUBMITTED ARE FOR NON- ADA COMPLIANT FIXTURES
 EXCEPT FOR THE LAVATORY FAUCET WHICH MEETS THE
 STANDARDS. THE SUBMITTALS FOR FIXTURES AND DEVICES MAY
 BE DEFERRED AND BE ONSITE IF PREFERRED, HOWEVER IT
 WOULD BE HELPFUL TO PROVIDE A LIST OF DEFERRED
 SUBMITTALS ON THE PLANS.
  
 4) FAILED P1: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR
 THE PROPOSED ALTERATIONS PER TABLE 403.3 FBC P. PROVIDE
 A SCHEDULE INDICATING THE REQUIRED AND PROVIDED
 PLUMBING FIXTURES. PLEASE NOTE THAT THE PLAN DOES NOT
 INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE
 EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1-
 211.3 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN
 REQUIREMENTS. REVISE THE PLANS TO SHOW COMPLIANCE.
 A) BUSINESS OCCUPANCIES ARE CALCULATED AT 100 GROSS PER
 SQ. FT. NOT 150- TABLE 1004.1.2 FBC B. THE CALCULATION
 RESULTS IN 27 OCCUPANTS.
 B) EXCEPTION #4 UNDER SECTION 403.2 DOES NOT EXIST.
 ACCORDING TO SECTION 403.2 EXCEPTION #2- SEPARATE
 FACILITIES ARE NOT REQUIRED IN STRUCTURES AND TENANT
 SPACES WITH A TOTAL OCCUPANT LOAD OF 15 OR FEWER,
 THEREFORE SEPARATE FACILITIES ARE REQUIRED FOR MALE AND
 FEMALE USE. THE CODE DOES ALLOW THE ROOMS TO BE
 DESIGNATED AS UNISEX- SECTION 403.2.1. CORRECT THE
 SCHEDULE TO SHOW 2 WATER CLOSET AND 2 LAVATORIES ARE
 REQUIRED. PLEASE NOTE THAT EACH OF THESE TOILET ROOMS
 THAT ARE BEING CONSTRUCTED OR ALTERED SHALL BE DESIGNED
 AS ACCESSIBLE- SECTION 213.1 FBC ACC.
  
 5) PASSED P1: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORY- SECTION 416.5 FBC P. REFER TO
 COMMENT #3 DEFERRED SUBMITTAL. IT WILL BE HELPFUL TO
 NOTE ON THE PLAN THE REQUIRED ASSE 1070 LISTING
 STANDARD FOR THE DEVICES-SSECTION 607.1.2.
  
 6) FAILED. A4: ACCESSIBILITY CORRECTIONS- FBC ACC:
 PLEASE NOTE THAT BOTH RESTROOMS 1 & 2 NEED TO MEET
 COMPLIANCE HOWEVER THE PLANS INDICATE ONLY RESTROOM 1
 IS BEING MADE ACCESSIBLE- SECTION 213.1 FBC ACC. ITEMS
 A- J BELOW PASSED FOR RESTROOM 1 ONLY.
  
 A) LENGTH OF THE LAVATORY CLEAR FLOOR SPACE NOT SHOWN-
 SECTION 606.2 AND 305.
 B) HEIGHT TO THE TOP OF THE WATER CLOSET SEAT FROM THE
 FINISHED FLOOR INDICATED AT 20"- SECTION 604.4
 C) THE SIDE GRAB BAR AT THE WATER CLOSET SHALL EXTEND
 MINIMUM 54" FROM THE REAR WALL- FIGURE 604.5.1.
 D) REAR GRAB BEHIND WATER CLOSET NOT CENTERED
 CORRECTLY- FIGURE 604.5.2.
 E) HEIGHTS OF GRABS SHOWN AT BOTH 33" AND 36" FROM
 FLOOR. GRAB BARS SHALL BE INSTALLED AT 33" MINIMUM AND
 36"MAXIMUM MEASURED FROM THE FINISHED FLOOR TO THE TOP
 OF THE GRIPPING SURFACE- SECTION 609.4.
 F) FLUSH CONTROL SHOWN ON THE WRONG SIDE OF THE WATER
 CLOSET- SECTION 604.6
 G) TOILET PAPER DISPENSER NOT LOCATED IN COMPLIANCE
 WITH- SECTION 604.7.
 H) HEIGHT OF THE MIRROR SHALL BE 40" FROM THE FINISHED
 FLOOR TO THE BOTTOM OF THE REFLECTIVE SURFACE SECTION
 603.3.
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 305 & 306.
  
 7) FAILED. A2, A3, & A4: NO ACCESSIBILITY DETAILS HAVE
 BEEN PROVIDED FOR THE ALTERED SECOND FLOOR BATHROOM.
 THE CONFIGURATION OF THE ROOM INDICATES NON-COMPLIANCE.
 PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS TO SHOW
 COMPLIANCE WITH THE FBC ACC. THE ACCESSIBILITY ALLOWS
 SOME EXCEPTIONS FOR PRIVATE BATHROOMS INCLUDING TOILET
 SEATS (SECTION 604.4), GRAB BARS FOR TOILETS AND
 SHOWERS (604.5 & 608.3), LAVATORY KNEE AND TOE
 CLEARANCES (606.2) & LAVATORY HEIGHT (606.3). IN LIEU
 OF THE GRAB BARS REINFORCEMENTS FOR FUTURE GRABS ARE
 REQUIRED TO BE INSTALLED. ALL OTHER COMPLIANCES LISTED
 BELOW SHALL BE MET AND SHOWN ON THE PLANS UNLESS MARKED
 AS NOT REQUIRED.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) DIAGRAMS AND DIMENSIONS FOR THE NEW SHOWER PER
 SECTION 608.2.1 AND FIGURE 608.2.1. THE SHOWER
 COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES CLEAR
 INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS OF
 OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
 D) BATHROOM ENTRY DOOR WIDTH, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
 PLEASE SEE SECTION 403.5- 36 IN. WALKING CLEAR WIDTH,
 AND 404.2.3- 32 IN. DOOR CLEAR WIDTH REQUIRED.
 E) TURNING SPACE DIAMETERS SECTION 304.3.
 F) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 G) NOT REQUIRED. HEIGHT OF THE WATER CLOSET SEAT FROM
 THE FINISHED FLOOR- SECTION 604.4.
 H) NOT REQUIRED. HEIGHT OF THE FRONT RIM OF THE
 LAVATORY FROM THE FINISHED FLOOR- SECTION 606.3
 I) NOT REQUIRED. KNEE AND TOE CLEARANCES FOR THE
 LAVATORY- SECTION 306.
 J) REINFORCEMENTS REQUIRED. LOCATIONS, LENGTHS, AND
 MOUNTING HEIGHTS OF GRAB BARS- SECTION 604.5
 K) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 L) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 M) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 N) REINFORCEMENTS REQUIRED. NEW SHOWER GRAB BAR AND
 SHOWER CONTROL LOCATIONS AND CLEARANCES PER SECTIONS
 AND FIGURES 608.3.1 & 608.5.1.
 O) REINFORCEMENTS REQUIRED. LOCATION AND DETAILS FOR
 INSTALLATION OF THE REQUIRED SEAT IN THE SHOWER-
 SECTION 608.4 & 610.3.
  
 NEW COMMENT BASED ON RESUBMITTED PLANS AND DOCUMENTS.
  
 1) CONCERNING THE DISPROPORTIONATE ITEMIZED COSTS
 SHEET, PLEASE REFER TO SECTION 202.4.2 FBC ACC:
 PRIORITY SHALL BE GIVEN TO THOSE ELEMENTS THAT WILL
 PROVIDE THE GREATEST ACCESS BEGINNING WITH THE
 ACCESSIBLE ENTRANCE AND FOLLOWED BY ACCESSIBLE ROUTE TO
 THE ALTERED AREA. YOU ARE SHOWING THE COSTS ASSOCIATED
 WITH THE ENTRANCE, BUT THE COSTS ASSOCIATED WITH THE
 ACCESSIBLE ROUTE DO NOT INCLUDE THE ESTIMATED COSTS TO
 PROVIDE VERTICAL ACCESSIBILITY TO THE 2ND FLOOR. THOSE
 COSTS TAKE PRIORITY OVER RESTROOMS, KITCHENS AND
 DRINKING FOUNTAIN COSTS. GIVEN THE NUMBERS SHOWN IT
 APPEARS COSTS ASSOCIATED WITH THE ENTRANCE AND
 ACCESSIBLE ROUTE ARE AT 18 % OF THE TOTAL COSTS.
  
 2) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 LOCATIONS AND HEIGHTS. THE FOUNTAINS SHALL BE INSTALLED
 TO MEET COMPLIANCE WITH SECTION 307.2 PROTRUDING
 OBJECTS. PLEASE SHOW HOW COMPLIANCE IS BEING MET.
  
 3) PROVIDE A SLAB REPAIR DETAIL FOR THE SLAB CUTS MADE
 TO INSTALL PLUMBING PIPES- SECTION 107.2.1 WPB.
  
 4) SHEET P-2: PROVIDE HOT WATER PIPE INSUILATION
 SPECIFICATIONS TO THE NOTES- TABLE C403.2.10 FBC EC.
  
 5) P-2: SHOW THE REQUIRED 1/4 IN. PER FT. SHOWER PAN
 SLOPE- SECTION 417.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-08-13 Cont ID  
Sent By ccole Date 2020-08-13 Time 12:19 Rev Time 0.00
Received By ccole Date 2020-08-13 Time 10:58 Sent To  
Notes
2020-08-13 12:19:422ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20060456
 8/13/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIE
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW WERE NOT
 ADDRESSED AND STILL EXIST WITH THE EXCEPTIONS OF
 COMMENTS # 6,A,E,G & H. NEW COMMENTS #8, 9 & 10 WERE
 ADDED. PLEASE NOTE THAT THE REQUESTED RESPONSE
 NARRATIVE TO THESE COMMENTS WAS NOT PROVIDED
  
 1) SHEET P1: THE SINK FIXTURE DRAIN MUST CONNECT TO THE
 3" BUILDING DRAIN DOWNSTREAM OF THE WC AND LAVATORY PER
 SECTIONS 912.1 AND 912.2.1 FBC P.
  
 2) P1: PROVIDE A WATER RISER DRAWING SHOWING PIPE
 SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER
 ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC.
  
 3) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE-
 SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
  
 4) P1: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR THE
 PROPOSED ALTERATIONS PER TABLE 403.3 FBC P. PROVIDE A
 SCHEDULE INDICATING THE REQUIRED AND PROVIDED PLUMBING
 FIXTURES. PLEASE NOTE THAT THE PLAN DOES NOT INDICATE
 DRINKING FOUNTAINS, OR A SERVICE SINK ARE EITHER
 EXISTING OR PROPOSED. REFER TO SECTION 211.1- 211.3 FBC
 ACC FOR ACCESSIBLE DRINKING FOUNTAIN REQUIREMENTS.
 REVISE THE PLANS TO SHOW COMPLIANCE.
  
 5) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORY- SECTION 416.5 FBC P.
  
 6) A4: ACCESSIBILITY CORRECTIONS FOR THE 1ST FLOOR
 RESTROOM - FBC ACC:
 B) HEIGHT TO THE TOP OF THE WATER CLOSET SEAT FROM THE
 FINISHED FLOOR INCORRECTLY INDICATED AT 20"- SECTION
 604.4
 C) THE SIDE GRAB BAR AT THE WATER CLOSET SHALL EXTEND
 MINIMUM 54" FROM THE REAR WALL- FIGURE 604.5.1.
 D) REAR GRAB BEHIND WATER CLOSET NOT CENTERED
 CORRECTLY- FIGURE 604.5.2.
 F) FLUSH CONTROL SHOWN ON THE WRONG SIDE OF THE WATER
 CLOSET- SECTION 604.6
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 305 & 306.
  
 7) A2, A3, & A4: NO ACCESSIBILITY DETAILS HAVE BEEN
 PROVIDED FOR THE ALTERED SECOND FLOOR BATHROOM. THE
 CONFIGURATION OF THE ROOM INDICATES NON-COMPLIANCE.
 PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS TO SHOW
 COMPLIANCE WITH THE FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) DIAGRAMS AND DIMENSIONS FOR THE NEW SHOWER PER
 SECTION 608.2.1 AND FIGURE 608.2.1. THE SHOWER
 COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES CLEAR
 INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS OF
 OPPOSING SIDES AND SHALL HAVE A 36-INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
 D) BATHROOM ENTRY DOOR WIDTH, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
 E) TURNING SPACE DIAMETERS SECTION 304.3.
 F) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 G) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 H) HEIGHT OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 J) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5 & 609.4.
 K) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 L) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 M) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 N) NEW SHOWER GRAB BAR AND SHOWER CONTROL LOCATIONS AND
 CLEARANCES PER SECTIONS AND FIGURES 608.3.1 & 608.5.1.
 O) LOCATION AND DETAILS FOR INSTALLATION OF THE
 REQUIRED SEAT IN THE SHOWER- SECTION 608.4 & 610.3.
  
 8) NEW COMMENT. SHEET A3, A4., P1: PROVIDE DIMENSIONED
 FRONT AND SIDE ELEVATION DRAWINGS OF THE NEW BREAK ROOM
 SINK. THE SINK SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES FROM THE
 FINISHED FLOOR- SECTION 606.3 FBC ACC. THE DEPTH OF THE
 COUNTERTOP SHALL BE INCOMPLIANCE WITH SECTION 308.3.2
 FOR ALLOWABLE REACH RANGES TO THE FAUCET CONTROLS.
  
 9) NEW COMMENT, SHEET P1: PLEASE LABEL THE WATER HEATER
 IN THE MECH RM AS EITHER NEW OR EXISTING, IF THE UNIT
 IS BEING REPLACED, PLEASE PROVIDE A PLUMBING PIPING
 DETAIL AND AN EQUIPMENT SCHEDULE ON THE PLAN, AND
 SUBMIT A PRODUCT SPEC SHEET- SECTIONS 502.1 AND 607.1.
  
 10) NEW COMMENT: PROVIDE WALL AND FLOOR FINISH MATERIAL
 SCHEDULES FOR THE BATHROOMS- SEE SECTION 310.3 FBC P
 AND SECTION 1210.2.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-02 Cont ID  
Sent By ccole Date 2020-07-02 Time 08:51 Rev Time 0.00
Received By ccole Date 2020-07-01 Time 16:40 Sent To  
Notes
2020-07-02 08:51:461ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20060456
 7/2/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE SINK FIXTURE DRAIN MUST CONNECT TO THE
 3" BUILDING DRAIN DOWNSTREAM OF THE WC AND LAVATORY PER
 SECTIONS 912.1 AND 912.2.1 FBC P.
  
 2) P1: PROVIDE A WATER RISER DRAWING SHOWING PIPE
 SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER
 ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC.
  
 3) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE-
 SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
  
 4) P1: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR THE
 PROPOSED ALTERATIONS PER TABLE 403.3 FBC P. PROVIDE A
 SCHEDULE INDICATING THE REQUIRED AND PROVIDED PLUMBING
 FIXTURES. PLEASE NOTE THAT THE PLAN DOES NOT INDICATE
 DRINKING FOUNTAINS, OR A SERVICE SINK ARE EITHER
 EXISTING OR PROPOSED. REFER TO SECTION 211.1- 211.3 FBC
 ACC FOR ACCESSIBLE DRINKING FOUNTAIN REQUIREMENTS.
 REVISE THE PLANS TO SHOW COMPLIANCE.
  
 5) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORY- SECTION 416.5 FBC P.
  
 6) A4: ACCESSIBILITY CORRECTIONS- FBC ACC:
 A) LENGTH OF THE LAVATORY CLEAR FLOOR SPACE NOT SHOWN-
 SECTION 606.2 AND 305.
 B) HEIGHT TO THE TOP OF THE WATER CLOSET SEAT FROM THE
 FINISHED FLOOR INDICATED AT 20"- SECTION 604.4
 C) THE SIDE GRAB BAR AT THE WATER CLOSET SHALL EXTEND
 MINIMUM 54" FROM THE REAR WALL- FIGURE 604.5.1.
 D) REAR GRAB BEHIND WATER CLOSET NOT CENTERED
 CORRECTLY- FIGURE 604.5.2.
 E) HEIGHTS OF GRABS SHOWN AT BOTH 33" AND 36" FROM
 FLOOR. GRAB BARS SHALL BE INSTALLED AT 33" MINIMUM AND
 36"MAXIMUM MEASURED FROM THE FINISHED FLOOR TO THE TOP
 OF THE GRIPPING SURFACE- SECTION 609.4.
 F) FLUSH CONTROL SHOWN ON THE WRONG SIDE OF THE WATER
 CLOSET- SECTION 604.6
 G) TOILET PAPER DISPENSER NOT LOCATED IN COMPLIANCE
 WITH- SECTION 604.7.
 H) HEIGHT OF THE MIRROR SHALL BE 40" FROM THE FINISHED
 FLOOR TO THE BOTTOM OF THE REFLECTIVE SURFACE SECTION
 603.3.
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 305 & 306.
  
 7) A2, A3, & A4: NO ACCESSIBILITY DETAILS HAVE BEEN
 PROVIDED FOR THE ALTERED SECOND FLOOR BATHROOM. THE
 CONFIGURATION OF THE ROOM INDICATES NON-COMPLIANCE.
 PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS TO SHOW
 COMPLIANCE WITH THE FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) DIAGRAMS AND DIMENSIONS FOR THE NEW SHOWER PER
 SECTION 608.2.1 AND FIGURE 608.2.1. THE SHOWER
 COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES CLEAR
 INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS OF
 OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
 D) BATHROOM ENTRY DOOR WIDTH, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
 E) TURNING SPACE DIAMETERS SECTION 304.3.
 F) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 G) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 H) HEIGHT OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 J) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 K) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 L) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 M) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 N) NEW SHOWER GRAB BAR AND SHOWER CONTROL LOCATIONS AND
 CLEARANCES PER SECTIONS AND FIGURES 608.3.1 & 608.5.1.
 O) LOCATION AND DETAILS FOR INSTALLATION OF THE
 REQUIRED SEAT IN THE SHOWER- SECTION 608.4 & 610.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-11-19 Cont ID  
Sent By medwards Date 2020-11-19 Time 07:53 Rev Time 0.00
Received By medwards Date 2020-11-19 Time 07:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-11-17 Cont ID  
Sent By jwitmer Date 2020-11-17 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2020-11-17 Time 13:12 Sent To  
Notes
2020-11-13 10:50:05DIGITALLY SIGNED FILES UPLOADED UNDER 'SIGNATURES'
 FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-27 Cont ID  
Sent By jwitmer Date 2020-10-27 Time 11:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-25 Cont ID  
Sent By jwitmer Date 2020-08-25 Time 09:38 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-08-12 07:04:48DIGITALLY SIGNED FILES UNDER 'SIGNATURES' FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-02 Cont ID  
Sent By ccole Date 2020-07-02 Time 07:28 Rev Time 0.00
Received By ccole Date 2020-07-02 Time 07:25 Sent To  
Notes
2020-06-11 09:55:32DIGITALLY SIGNED DRAWINGS UNDER "SIGNATURES" FOLDER