Plan Review Details - Permit 20060393
Plan Review Stops For Permit 20060393
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2020-11-05 Cont ID  
Sent By jwitmer Date 2020-11-05 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2020-11-05 Time 11:31 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-11-02 Cont ID  
Sent By jwitmer Date 2020-11-02 Time 10:52 Rev Time 0.00
Received By jwitmer Date 2020-11-02 Time 10:30 Sent To  
Notes
2020-11-02 10:51:50COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-07-29 Cont ID  
Sent By jwitmer Date 2020-07-29 Time 09:04 Rev Time 0.00
Received By jwitmer Date 2020-07-29 Time 07:33 Sent To  
Notes
2020-07-29 09:04:12PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-06-15 Cont ID  
Sent By jwitmer Date 2020-06-15 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2020-06-15 Time 06:57 Sent To  
Notes
2020-06-15 06:59:13PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date   Cont ID  
Sent By jwitmer Date 2021-01-15 Time 10:45 Rev Time 0.00
Received By   Date 2021-01-15 Time 10:14 Sent To  
Notes
2021-01-15 10:46:14BUILDING PROVISO: THE HIGH LOW WATER FOUNTAIN SHOW
 COMPLIANCE WITH:
 2017 FBC-ACCESSIBILITY CODE SECTION PROTRUDING OBJECTS
 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 08:42 Rev Time 0.00
Received By abelisle Date 2020-11-27 Time 08:16 Sent To  
Notes
2020-11-27 08:34:38WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060393
 ADD: 2405 MERCER AVE.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. NOV. 02/2020
 ACTION: DENIED
  
 1) 1-3 COMPLIED.
  
 4A) COMPLIED.
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 4B) 2ND REQUEST.I'VE RED YOUR RESPONSE IN REGARDS TO
 THE HEALTH DEPARTMENT. MY EXPERIENCE IN ANY ASSEMBLY
 AREA, MERCANTILE AREA AND OR BUSINESS OCCUPANCY WHERE
 THE WATER FOUNTAINS WERE TURNED OFF BY REQUEST OF THE
 HEALTH DEPARTMENT THEY DIDN'T PUT IN A BOTTLED WATER
 DISPENSER. TO MEET THE CODE REQUIREMENTS AS A MINIMUM
 THERE NEEDS TO BE A HIGH-LOW DRINKING FOUNTAIN IF IN
 THE INTEREST OF YOUR CLIENT IF THEY WOULD LIKE TO GO ON
 THE CODE MINIMUM REQUIREMENTS AND INSTALL THE BOTTLED
 WATER DISPENSER THEY DO THAT. TO MEET THE CURRENT
 RQUEST OF THE HEALTH DEPARTMENT ONCE THE INSPECTIONS
 ARE COMPLETE AND C/O ISSUED AND BEFORE OCCUPANCY AND
 MEET THE HEALTH DEPARTMENT CURRENT GUIDELINES YOU COULD
 TURN OFF THE WATER TO THE WATER FOUNTAINS, BUT THE CODE
 MINIMUM REQUIREMENTS NEED TO BE MET.
  
 THE ISSUE IS THE NEWLY PROPOSED WATER BOTTLE DISPENSER.
 THE SECOND REVIEW THERE WAS A SINGLE WATER FOUNTAIN.
 WHEN WE VERSION THE PLANS SHEET A-1 SHOWS A SINGLE
 WATER FOUNTAIN. THE 2017 ACCESSIBILITY CODE REQUIRES AT
 LEAST A HIGH & LOW DRINKING FOUNTAIN INCOMPLIANCE WITH:
 DRINKING FOUNTAINS.
 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. CODE.
 SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 WHEN YOU INSTALL THE HIGH LOW DRINKING FOUNTAIN YOU
 MEET THE CODE REQUIREMENTS OF THE CODE, IF YOU WISH TO
 INSTALL A WATER BOTTLE DISPENSER THAT WOULD BE OVER AND
 ABOVE THE ODE BUT YOU HAVE TO MEET THE CODE
 REQUIREMENTS FOR A HIGH/ LOW DRINKING FOUNTAIN.
  
 5) COMPLIED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-11-02 Cont ID  
Sent By jwitmer Date 2020-11-02 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2020-11-02 Time 10:31 Sent To  
Notes
2020-11-02 11:37:54WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060393
 ADD: 2405 MERCER AVE.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. NOV. 02/2020
 ACTION: DENIED
  
 1) 1-3 COMPLIED.
  
 4A) COMPLIED.
  
 4B) SEMI-COMPLIED. THE ISSUE IS THE NEWLY PROPOSED
 WATER BOTTLE DISPENSER. THE SECOND REVIEW THERE WAS A
 SINGLE WATER FOUNTAIN. WHEN WE VERSION THE PLANS SHEET
 A-1 SHOWS A SINGLE WATER FOUNTAIN. THE 2017
 ACCESSIBILITY CODE REQUIRES AT LEAST A HIGH & LOW
 DRINKING FOUNTAIN INCOMPLIANCE WITH:
 DRINKING FOUNTAINS.
 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. CODE.
 SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 WHEN YOU INSTALL THE HIGH LOW DRINKING FOUNTAIN YOU
 MEET THE CODE REQUIREMENTS OF THE CODE, IF YOU WISH TO
 INSTALL A WATER BOTTLE DISPENSER THAT WOULD BE OVER AND
 ABOVE THE ODE BUT YOU HAVE TO MEET THE CODE
 REQUIREMENTS FOR A HIGH/ LOW DRINKING FOUNTAIN.
  
 5) COMPLIED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-29 Cont ID  
Sent By jwitmer Date 2020-07-29 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2020-07-29 Time 07:33 Sent To  
Notes
2020-07-29 09:03:11WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060393
 ADD: 2405 MERCER AVE.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JULY29TH/ 2020
 ACTION: DENIED
  
 1) 2ND REQUEST. THE PERMIT APPLICATION STATES THE WORK
 TO BE ACCOMPLISHED UNDER THE SCOPE OF THIS PERMIT IS
 FOR THE RENOVATION OF AN EXISTING RESTROOM FOR A VALUE
 OF $5,000.00 DOLLARS.
  
 2A) 2ND REQUEST. SHEET A-2 STILL MAKES REFERENCE TO THE
 2014 FBC.
  
 2B) NEW COMMENT. THIS PLAN STATES THAT THE ALTERATION
 LEVEL IS LEVEL II. THE CITY OF WEST PALM BEACH BUSINESS
 TAX (OLD OCCUPATIONAL LICENSING) SHOWS THIS SPACE BEING
 CARLYLE THERAPY ASSOCIATION WHICH IS A BUSINESS
 OCCUPANCY. A CHANGE OF OCCUPANCY IS OCCURRING.
 THE DESIGNER OF RECORD HAS NOT MET ALL OF THE
 REQUIREMENTS FOUND UNDER COMMENT 468.1 FOR EDUCATIONAL
 OCCUPANCIES. ALL OF THE REQUIREMENTS, THERE IS NO
 EXISTING BUILDING CODE FOR THIS OCCUPANCY GROUP.
  
 3) COMPLIED.
  
 4) SHEET A-2 MAKE REFERENCE TO THIS FACILITY TO BE A
 PUBLIC CHARTER SCHOOL GRADES K-8TH GRADE. PLEASE BE
 AWARE OF THE 2017 FBC-EXISTING CODE SCOPING
 REQUIREMENTS AND EXCEPTION FOUND UNDER SECTION 101.2.
 EXCEPTION: FOR THE PURPOSE OF PUBLIC EDUCATION AND
 STATE LICENSED FACILITIES, SEE CHAPTER 4 SPECIAL
 OCCUPANCIES OF THE FLORIDA BUILDING CODE, BUILDING.
 SECTION 453 DEALS WITH STATE REQUIREMENTS FOR
 EDUCATIONAL FACILITIES. NOT THE LOCAL BUILDING DEPART.
 CONCERN UNLESS THE SCHOOL BOARD SUBMITS PLANS FOR
 PUBLIC SCHOOLS.
 4A)(1) CHAPTER 468 FOR FLORIDA?S PUBLIC & PRIVATE
 SCHOOLS, COLLEGES AND UNIVERSITIES. THERE IS NO
 EXISTING BUILDING CODE TO GO BY UNDER SPECIAL
 OCCUPANCIES FOUND IN CHAPTER 4. CHAPTER 468 IN ITS
 ENTIRITY HAS TO SHOW COMPLIANCE.
  
 4A)(2) SEMI-COMPLIED. THERE IS NOT ENOUGH INFORMATION
 ON THE PLAN TO DETERMINE CODE COMPLIANCE FOR THE
 REQUIRED NUMBER OF FIXTURES REQUIRED UNDER THE 2017
 FBC-B TABLE 2902.1 FOR EDUCATION. THE SUBMITTED TABLE
 GIVES A OVERALL COUNT BUT NOT BY AGE GROUP SEE THE 2017
 ACCESSIBILITY CODE 604.9 AGES 5-8 AGES 9-12 FOR WATER
 CLOSET CENTERLINE, TOILET SEAT HEIGHT, GRAB BAR HEIGHT
 AND DISPENSER HEIGHT.
  
 4B) 2ND REQUEST ACCESS. CODE TABLE 604.9.THE 2017 FBC-B
 468.3.5.1 STANDARDS. EDUCATIONAL AND ANCILLARY
 FACILITIES SHALL BE PROVIDE WITH TOLIETS, HAND WASHING
 AND DRINKING FOUNTAINS FOR ALL OCCUPANTS IN RATIOS AND
 ACCESSIBLE AS REQUIRED BY THE FLORIDA BUILDING CODE,
 FLORIDA LAWS AND FEDERAL REGULATIONS. SHEET A-1 & A2
 SHOWS A SINGLE DRINKING FOUNTAIN, PLEASE SHOW A DOUBLE
 HIGH/ LOW, PLEASE SEE IN THE 2017 FBC-ACCESSIBILITY
 CODE REQUIREMENTS FOR DRINKING FOUNTAINS. SHEET A-3
 SHOWS COMPLIANCE WITH :
  
 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 NOT SHOWN IN COMPLIANCE. PROTRUDING OBJECTS 307.2
 PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING EDGES
 MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE
 THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY IN TO THE CIRCULATION PATH.
  
 60.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5) COMPLIED. SHEET A-3 GRAB BARS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-15 Cont ID  
Sent By jwitmer Date 2020-06-15 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2020-06-15 Time 06:57 Sent To  
Notes
2020-06-15 07:10:042017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060393
 ADD: 2405 MERCER AVE.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 15TH/ 2020
 ACTION: DENIED
  
 1) THE SUBMITTED PERMIT APPLICATION STATES THAT IT IS
 FOR THE RENOVATION OF AN EXISTING RESTROOM FOR A VALUE
 OF $5,000.00 DOLLARS.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
  
  
 2) SHEET A-1 CODE REFERENCES LIST THE 2014 FBC AS THE
 CODE IN AFFECT. PLEASE UPDATE THE CODE REFERENCE TO THE
 2017 FBC. THE 2017 FAMILY OF THE 6TH EDITION FLORIDA
 BUILDING CODE HAS BEEN ADOPTED STATEWIDE SINCE
 12/31/2017.
  
 3) SHEET A.2 SHOWS THE NEW ADA RESTROOM WITH THE BACK
 WALL MEASUREMENT OF 6 FEET 4 INCHES. THE FLOOR PLAN
 DOES NOT SHOW THE CLEARANCES AT WATER CLOSETS. 604.3
 CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS AND IN
 TOILET COMPARTMENTS SHALL COMPLY WITH 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND AND 56 INCHES MINIMUM PERPENDICULAR FROM THE
 REAR WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT
 SHOULD BE 7 FOOT 1 INCH.
  
 4) SHEET A-2 DOES MAKE REFERENCE TO THIS FACILITY IS A
 PUBLIC CHARTER SCHOOL GRADES K-8TH GRADE. PLEASE BE
 AWARE OF THE 2017 FBC-EXISTING BUILDING CODE SCOPING
 REQUIREMENTS AND THE EXCEPTION FOUND UNDER SECTION
 101.2. EXCEPTION: FOR THE PURPOSE OF PUBLIC EDUCATIONAL
 FACILITIES AND STATE LICENSED FACILITIES, SEE CHAPTER
 4, SPECIAL OCCUPANCIES, OF THE FLORIDA BUILDING CODE,
 BUILDING.
 SECTION 453 DEALS WITH STATE REQUIREMENTS FOR
 EDUCATIONAL FACILITIES. NOT THE LOCAL BUILDING
 DEPARTMENT CONCERN UNLESS THE SCHOOL BOARD SUBMITS
 PLANS FOR PUBLIC SCHOOLS.
  
 4A) SECTION 468.1 IS FOR FLORIDA?S PUBLIC AND PRIVATE
 SCHOOLS, COLLEGES AND UNIVERSITIES. THERE IS NO
 EXISTING BUILDING CODE TO GO BY UNDER SPECIAL
 OCCUPANCIES FOUND IN CHAPTER 4. THERE IS NOT ENOUGH
 INFORMATION ON THE PLAN TO DETERMINE CODE COMPLIANCE
 FOR CODE COMPLIANCE FOR THE REQUIRED NUMBER OF FIXTURES
 REQUIRED UNDER THE 2017 FBC-B TABLE 2902.1 FOR
 EDUCATION.
  
 4B) 2017 FBC-B 468.3.5.1 STANDARDS. EDUCATIONAL AND
 ANCILLARY FACILITIES SHALL BE PROVIDED WITH TOILETS,
 HAND WASHING FACILITIES AND DRINKING FOUNTAINS FOR ALL
 OCCUPANTS IN RATIOS AND ACCESSIBLE AS REQUIRED BY THE
 FLORIDA BUILDING CODE, FLORIDA LAW AND FEDERAL
 REGULATIONS. SHEET A-1 SHOWS A SINGLE DRINKING FOUNTAIN
 NOT A HIGH-LOW DRINKING FOUNTAIN AS REQUIRED BY:
 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 DRINKING FOUNTAINS TO SHOW COMPLIANCE WITH 307.2
 PROTRUSION LIMITS. OBJECTS WITH LEADING EDGES MORE THAN
 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FINISH
 FLOOR SHALL PROTRUDE 4 INCHES OR LESS MAXIMUM
 HORIZONTALLY INTO THE CIRCULATION PATH. SKIRTS MAYBE
 REQUIRED TO BE APPLIED TO THE BOTTOM OF THE DRINKING
 FOUNTAIN.
  
 5) SHEET A-3 HAS RESTROOM DETAILS, THE GRAB BARS THAT
 SURROUND THE WATER CLOSET NEED TO BE UPDATED TO THE
 2017 FBC-ACCESSIBILITY CODE. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-01-22 Cont ID  
Sent By jleahy Date 2021-01-22 Time 15:22 Rev Time 0.00
Received By jleahy Date 2021-01-22 Time 15:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-12-17 Cont ID  
Sent By jleahy Date 2020-12-08 Time 10:47 Rev Time 0.00
Received By jleahy Date 2020-12-08 Time 10:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-11-05 Cont ID  
Sent By jleahy Date 2020-11-05 Time 17:28 Rev Time 0.00
Received By jleahy Date 2020-11-05 Time 17:23 Sent To  
Notes
2020-11-05 17:29:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-10 Cont ID  
Sent By jleahy Date 2020-08-10 Time 17:01 Rev Time 0.00
Received By jleahy Date 2020-08-10 Time 16:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By jleahy Date 2020-06-29 Time 11:48 Rev Time 0.00
Received By jleahy Date 2020-06-29 Time 10:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2021-01-15 Cont ID  
Sent By pleduc Date 2021-01-15 Time   Rev Time 0.00
Received By pleduc Date 2021-01-15 Time 12:15 Sent To  
Notes
2021-01-15 12:18:18THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-11-24 Cont ID  
Sent By pleduc Date 2020-11-24 Time   Rev Time 0.00
Received By pleduc Date 2020-11-24 Time 12:31 Sent To  
Notes
2020-11-24 12:33:09THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-11-03 Cont ID  
Sent By pleduc Date 2020-11-03 Time   Rev Time 0.00
Received By pleduc Date 2020-11-03 Time 15:02 Sent To  
Notes
2020-11-03 15:03:42THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-07-28 Cont ID  
Sent By pleduc Date 2020-07-28 Time   Rev Time 0.00
Received By pleduc Date 2020-07-28 Time 09:15 Sent To  
Notes
2020-07-28 09:16:01THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-06-12 Cont ID  
Sent By pleduc Date 2020-06-12 Time   Rev Time 0.00
Received By pleduc Date 2020-06-12 Time 12:31 Sent To  
Notes
2020-06-12 12:32:18THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-01-22 Cont ID  
Sent By jleahy Date 2021-01-22 Time 15:23 Rev Time 0.00
Received By jleahy Date 2021-01-15 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status P Date 2020-12-23 Cont ID  
Sent By jleahy Date 2020-12-23 Time 12:36 Rev Time 0.00
Received By jleahy Date 2020-11-23 Time 14:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-05 Cont ID  
Sent By jleahy Date 2020-11-05 Time 17:29 Rev Time 0.00
Received By jleahy Date 2020-10-30 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-10 Cont ID  
Sent By jleahy Date 2020-08-10 Time 17:02 Rev Time 0.00
Received By jleahy Date 2020-07-24 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-06 Cont ID  
Sent By lmarchan Date 2020-07-06 Time 10:14 Rev Time 0.00
Received By lmarchan Date 2020-06-11 Time 14:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-01-15 Cont ID  
Sent By medwards Date 2021-01-15 Time 13:15 Rev Time 0.00
Received By medwards Date 2021-01-15 Time 13:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-11-25 Cont ID  
Sent By medwards Date 2020-11-25 Time 10:10 Rev Time 0.00
Received By medwards Date 2020-11-25 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-11-02 Cont ID  
Sent By medwards Date 2020-11-02 Time 15:58 Rev Time 0.00
Received By medwards Date 2020-11-02 Time 15:58 Sent To  
Notes
2020-11-02 15:59:153RD REVIEW FBC-2017 MECHANICAL
 PERMIT- 20060393
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AHU-2 APPEARS TO BE CONDITIONING THE CAFETERIA.
 PLEASE SHOW THE OUTSIDE AIR CALCULATIONS FOR THIS UNIT
 BASED ON ITS USE OF SPACE IN TABLE 403.3.1.1. FBC M
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By medwards Date 2020-08-03 Time 13:36 Rev Time 0.00
Received By medwards Date 2020-08-03 Time 13:27 Sent To  
Notes
2020-08-03 13:37:421ST CYCLE MECHANICAL REVIEW COMMENTS WERE NOT
 ADDRESSED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By medwards Date 2020-07-24 Time 13:57 Rev Time 0.00
Received By medwards Date 2020-07-24 Time 13:14 Sent To  
Notes
2020-07-24 13:58:001ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060393
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS APPEARS TO BE A CHANGE OF OCCUPANCY FROM A
 BUSINESS TO EDUCATION.
  
 2) PLEASE PROVIDE MECHANICAL SHEETS, BOTH DEMO AND NEW
 WORK SHEETS. FBC FS 107.2.1
  
 3) PLEASE PROVIDE MECHANICAL VENTILATION CALCULATIONS
 FOR EACH CLASSROOM AND EACH AREA OF THIS SPACE. VERIFY
 THE EXISTING MECHANICAL SYSTEM IS ADEQUATE FOR THIS NEW
 CHANGE OF OCCUPANCY. FBC M TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-01-19 Cont ID  
Sent By abelisle Date 2021-01-19 Time 18:04 Rev Time 0.00
Received By abelisle Date 2021-01-19 Time 17:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-12-18 Cont ID  
Sent By abelisle Date 2020-12-18 Time 07:23 Rev Time 0.00
Received By abelisle Date 2020-12-14 Time 14:03 Sent To I
Notes
2020-12-17 05:16:564TH REVIEW FBC-2017 PLUMBING
 PERMIT-20060393
 12/17/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1). THIRD REQUEST: IT APPEARS THAT SOME CHANGES MAY
 HAVE BEEN MADE TO THE PROJECT THAT WERE NOT PERMITTED.
 PROVIDE AN EXISTING FLOOR PLAN. THE FLOOR LAYOUT OF THE
 EXISTING PLAN IN CITY RECORDS DOES NOT MATCH THE LAYOUT
 OF THE SUBMITTED PLAN. THE RESPONSE IN THE RESPONSE
 NARRATIVE OF " THE OLD PERMIT PLANS MUST BE INACCURATE"
 DOES NOT SOLVE THIS ISSUE. WORK THAT WAS PREVIOUSLY
 DONE WITHOUT PERMITS MUST BE LEGALLY PERMITTED. WPB
 AMEND. TO FBC SEC. 107.3..5, 105.1.
 2. THE CENTERLINE OF THE WATER CLOSET SHALL BE 12
 INCHES MINIMUM TO 15 INCHES MAXIMUM FROM THE SIDE WALL
 OR PARTITION FOR CHILDREN AGES 5-8 YEARS OLD FBC ACC
 604.9
 3) PROVIDE THE REQUIRED CLEAR FLOOR SPACED FOR THE
 TOILET AND SINK IN THE NEW ADA TOILET ROOM. FBC ACC 604
 4) FOURTH REQUEST INDICATE THE ON THE PLAN THAT THE
 TEMPERED WATER TO THE BATHROOM SINKS HAVE A MAX 110
 DEGREES BY AN APPROVED ASSE 1070 DEVICE COMPLYING WITH
 FBC P 607.1.2.
 5) HOT WATER IS REQUIRED FOR THE STAFF LOUNGE SINK AND
 THE SERVICE SINK FOR CLEANING PURPOSES FBC P 607.1
 5) FOURTH REQUEST: A HIGH LOW DRINKING FOUNTAIN IS AN
 ACCESSIBILITY CODE REQUIREMENT FBC ACC 211.2 THE 2017
 ACCESSIBILITY CODE REQUIRES AT LEAST A HIGH & LOW
 DRINKING FOUNTAIN INCOMPLIANCE WITH 2017 FBC ACC 211.2
 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7. THE WATER DISPENSER IS NOT
 ACCEPTABLE AS IT DOES NOT SATISFY THE DRINKING FOUNTAIN
 REQUIREMENTS.
 6) SECOND REQUEST: THERE APPEARS TO HAVE BEEN AN
 EXISTING DRINKING FOUNTAIN (SEE PERMIT # 14050704)
 HOWEVER IT WAS IN A DIFFERENT LOCATION THAN WHERE IT IS
 NOW SHOWN. PER WPB FBC 107.2.1, PROVIDE A SANITARY AND
 WATER RISER DIAGRAM FOR THE DRINKING FOUNTAIN. INCLUDE
 CONNECTION TO EXISTING SERVICES. ALTERNATIVELY THE
 OWNER CAN ADD THE WATER DISPENSER IN ADDITION TO THE
 HIGH LOW DRINKING FOUNTAIN.
 7) SHT. A-2 - ACCESSIBLE TOILETS FOR KIDS DETAILS - THE
 FRONT ELEVATION OF THE WATER CLOSET SHOWS THE
 CENTERLINE AT 12-15 INCHES AND THE WHEELCHAIR
 ACCESSIBLE WATER CLOOSET PLAN SHOWS 12-18 INCHES.
 CORRECT THE DETAIL.
 8) ON A-3 DETAIL #6 PLEASE REMOVE THIS DETAIN AS IT IS
 NOT RELEVANT TO THIS RENOVATION TO THIS EXISTING
 BUILDING.
 9)PROVIDE THE ELECTRIC TANKLESS WATER HEATER
 SPECIFICATIONS
 10) ON SHEET A-1 NEXT TO THE LOCKED STORAGE ROOM THERE
 IS AN ITEM IDENTIFIED AS POS? PLEASE PROVIDE MORE
 DETAIL
 11) ON SHEET MEP AND SHEET A-1 UNDER GENERAL NOTES.
 PLEASE PROVIDE MORE INFORMATION ON THE BATHROOM FLOORS
 AND WALLS TO 48" TO BE "NON-POURS AND SCRABBLE"?
 12)SECOND REQUEST: PER WPB FBC 107.2.1, SUBMIT A SLAB
 REPAIR DETAIL FOR REVIEW AND ONCE APPROVED HAVE TWO
 COPIES AT THE JOB SITE. SHOW THE WIDTH OF THE REPAIR,
 THE MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED,
 AND THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH
 OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, THE ANCHORING MATERIAL FOR THE DOWELS
 AND THE SPACING OF THE DOWELS ON CENTER. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND
 THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. A
 COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A
 FINAL INSPECTION.
 13) SECOND REQUEST: REFER TO PERMIT 14050704. THERE WAS
 A SINK ADJACENT TO THE PLUMBING WET WALL IN THE ROOM
 WHERE THE 7-12 YEAR OLD RESTROOMS ARE LOCATED ON SHEET
 MEP. PLEASE INDICATE IF THIS IS TO BE CAPPED OFF ON THE
 PLANS.
 14) THE ACCESSIBILITY CODE SEC. 604.9 ADDRESSES
 SPECIFICATIONS FOR CHILDREN AGES 3-4, 5-8, AND 9-12
 EACH AGE GROUP SPECIFICALLY HAS SPECIAL REQUIREMENTS
 FOR WATER CLOSETS AND COMPARTMENTS FOR CHILDRES USE.
 15) YOUR PLANS HAVE CONTINUED TO HAVE THE SAME
 DEFICIENCIES. IN ORDER TO HELP ME HELP YOU PLEASE
 CONTACT ME AT 561-805-6695
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-11-04 Cont ID  
Sent By tklarge Date 2020-11-04 Time 10:43 Rev Time 0.00
Received By tklarge Date 2020-11-03 Time 09:48 Sent To  
Notes
2020-11-04 06:18:57 
  
 1. IT APPEARS THAT SOME CHANGES MAY HAVE BEEN MADE TO
 THE PROJECT THAT WERE NOT PERMITTED. PROVIDE AN
 EXISTING FLOOR PLAN. THE FLOOR LAYOUT OF THE EXISTING
 PLAN IN CITY RECORDS DOES NOT MATCH THE LAYOUT OF THE
 SUBMITTED PLAN. THE RESPONSE IN THE RESPONSE NARRATIVE
 OF " THE OLD PERMIT PLANS MUST BE INACCURATE" DOES NOT
 SOLVE THIS ISSUE. WORK THAT WAS PREVIOUSLY DONE WITHOUT
 PERMITS MUST BE LEGALLY PERMITTED. WPB AMEND. TO FBC
 SEC. 107.3..5, 105.1.
 2. THE CENTERLINE OF THE WATER CLOSET SHALL BE 18
 INCHES MAXIMUM, NOT MINIMUM AS NOTED ON PLANS. SEE FBC
 ACC 604.2. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION.
 3)THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. FBC ACC 604.4. PER WPB
 FBC 107.2.1, CORRECT DETAIL ON PLAN A-3.
 4) INDICATE THE ON THE PLAN THAT THE TEMPERED WATER TO
 THE SINK MAX 110 DEGREES BY AN APPROVED ASSE 1070
 DEVICE COMPLYING WITH FBC PL 607.1.2.
 5) THE 2017 ACCESSIBILITY CODE REQUIRES AT LEAST A HIGH
 & LOW DRINKING FOUNTAIN INCOMPLIANCE WITH 2017
 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. THE
 WATER DISPENSER IS NOT ACCEPTABLE AS IT DOES NOT
 SATISFY THE DRINKING FOUNTAIN REQUIREMENTS.
 6) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
 7) SHT. A-1 - NOTE #8 CALLS OUT A UTILITY SINK BUT
 THERE IS NO UTILITY SINK SHOWN ON THE PLANS. CLARIFY.
 8) SHT. A-2 - ACCESSIBLE TOILETS FOR KIDS DETAILS - THE
 FRONT ELEVATION OF THE WATER CLOSET SHOWS THE
 CENTERLINE AT 12-15 INCHES AND THE WHEELCHAIR
 ACCESSIBLE WATER CLOOSET PLAN SHOWS 12-18 INCHES.
 CORRECT THE DETAIL.
 9) SHT. A-2 - THE WATER CLOSET ELEVATION DETAIL SHOWS
 THE GRAB BARS MEASURED TO THE CENTERLINE OF THE BAR.
 GRAB BARS SHALL BE MEASURE TO THE TOP OF THE GRIPPING
 SURFACE. FBC-ACCESS. SEC. 609.4.
 10) SHT. A-3 - PLUMBING FIXTURE MOUNTING HEIGHT DETAILS
 - THE DETAILS REFER TO THE 2007 FBC.THE 2017 FBC IS IN
 EFFECT. REVISE THE NOTE. ALSO, THE FIGURE NUMBERS
 LISTED ON THE DETAILS ARE NO LONGER IN THE CODE.
 11) THE WATER HEATER DETAIL ON THE MEP PLAN SHOWS A TOP
 FEED WATER HEATER BUT THE WATER HEATER SPECIFICATIONS
 SHOW THE WATER HEATER IS BOTTOM FED. A VACUUM RELIEF
 LINE IS REQUIRED ON THE COLD WATER LINE PER
 FBC-PLUMBING SEC.504.2.
 12) THE WATER HEATER PAN SHALL COMPLY WITH FBC-PLUMBING
 SEC.504.7 & 504.7.1.
 13) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER
 HEATER.
 14) SUBMIT DETAILS AS TO HOW THE WATER HEATER IS BEING
 SUPPORTED (TYPE AND SIZE OF HANGING RODS, TYPE AND
 LOCATION OF CONNECTIONS TO BAR JOISTS). WPB AMEND. TO
 FBC SEC. 107.2.1.
 15) ACCESS SHALL BE PROVIDED TO THE WATER HEATER IN THE
 CEILING PER FBC-PLUMBING SEC.502.5. A LEVEL WORKING
 SPACE NOT LESS THAN 30 INCHES IN LENGTH AND 30 INCHES
 IN WIDTH SHALL BE PROVIDED IN FRONT OF THE CONTROL SIDE
 TO SERVICE AN APPLIANCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-08-07 Cont ID  
Sent By jesmith Date 2020-08-07 Time 12:36 Rev Time 0.00
Received By jesmith Date 2020-08-07 Time 11:03 Sent To  
Notes
2020-08-07 12:36:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20060393 2405 MERCER AVE
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. IT APPEARS THAT SOME CHANGES MAY HAVE BEEN MADE TO
 THE PROJECT THAT WERE NOT PERMITTED. SEE COMMENTS 4.B)
 AND 5. REFER TO PERMIT 14050704. PROVIDE EXISTING FLOOR
 PLAN AS PER CITY RECORDS UNDER PERMIT # 14050704
 (UNLESS THERE IS A MORE RECENT RECORD WHICH NEEDS TO BE
 PROVIDED) AND INSPECTORS PHOTOS AS THERE IS NOTICEABLE
 CHANGE TO THE FLOOR PLAN. FBC 107.3.5. EXPOSE ALL WORK
 REQUIRING INSPECTION. IT SHALL BE THE DUTY OF THE
 PERMIT APPLICANT TO CAUSE THE WORK TO REMAIN ACCESSIBLE
 AND EXPOSED FOR INSPECTION PURPOSES. WPB AMEND TO THE
 FBC 110.1
  
 2. PER WPB FBC 107.2.1, SUBMIT A SLAB REPAIR DETAIL FOR
 REVIEW AND ONCE APPROVED HAVE TWO COPIES AT THE JOB
 SITE. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS OF THE CONCRETE TO BE REPLACED, AND THE PSI
 OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF THE
 DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE EXISTING
 SLAB, THE ANCHORING MATERIAL FOR THE DOWELS AND THE
 SPACING OF THE DOWELS ON CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER WELL-COMPACTED SOIL. A COPY OF THE
 TERMITE CERTIFICATE SHALL BE ONSITE FOR A FINAL
 INSPECTION.
  
 3. WATER CLOSET
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 18 INCHES
 MAXIMUM, NOT MINIMUM AS NOTED ON PLANS. SEE FBC ACC
 604.2. ?THE CENTERLINE OF THE WATER CLOSET SHALL BE 16
 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL
 OR PARTITION?
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE
 SPRUNG TO RETURN TO A LIFTED POSITION PER FBC ACC
 604.4. PER WPB FBC 107.2.1, CORRECT DETAIL ON PLAN A-3.
  
 4.A) SECOND REQUEST: PROVIDE A WATER ISOMETRIC FOR THE
 NEW ACCESSIBLE TOILET ROOM PER WPB FBC 107.3.5.
 INDICATE THE ON THE PLAN THE TEMPERED WATER TO THE SINK
 MAX 110 DEGREES BY AN APPROVED ASSE 1070 DEVICE
 COMPLYING WITH FBC PL 607.1.2.
 4.B) ADDITIONALLY, REFER TO PERMIT 14050704. THERE WAS
 A SINK ADJACENT TO THE PLUMBING WET WALL IN THE ROOM
 WHERE THE NEW ACCESSIBLE TOILET ROOM IS BEING ADDED.
 THE WET WALL FOR THE NEW BATHROOM IS OPPOSITE THE
 EXISTING WET WALL, SO THE EXISTING HOT WATER SYSTEM IS
 NOT REMAINING AS IS AS NOTED IN THE COMMENT RESPONSE.
  
 5. THERE APPEARS TO HAVE BEEN AN EXISTING DRINKING
 FOUNTAIN (SEE PERMIT # 14050704) HOWEVER IT WAS IN A
 DIFFERENT LOCATION THAN WHERE IT IS NOW SHOWN. PER WPB
 FBC 107.2.1, PROVIDE A SANITARY AND WATER RISER DIAGRAM
 FOR THE DRINKING FOUNTAIN. INCLUDE CONNECTION TO
 EXISTING SERVICES.
  
 6. SECOND REQUEST: PROVIDE THE REQUIRED CLEAR FLOOR
 SPACED FOR THE TOILET AND SINK IN THE NEW ADA TOILET
 ROOM.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 THE CLEAR FLOOR OR GROUND SPACE FOR LAVATORY SHALL BE
 30 INCHES MINIMUM BY 48 INCHES MINIMUM PER FBC ACC
 305.3
  
 7. SEE BUILDING REVIEW REMARKS BELOW
 4A)THERE IS NOT ENOUGH INFORMATION ON THE PLAN TO
 DETERMINE CODE COMPLIANCE FOR THE REQUIRED NUMBER OF
 FIXTURES REQUIRED UNDER THE 2017 FBC-B TABLE 2902.1 FOR
 EDUCATION. THE SUBMITTED TABLE GIVES A OVERALL COUNT
 BUT NOT BY AGE GROUP SEE THE 2017 ACCESSIBILITY CODE
 604.9 AGES 5-8 AGES 9-12 FOR WATER CLOSET CENTERLINE,
 TOILET SEAT HEIGHT, GRAB BAR HEIGHT AND DISPENSER
 HEIGHT.
 4B) 2ND REQUEST ACCESS. CODE TABLE 604.9.THE 2017 FBC-B
 468.3.5.1 STANDARDS. EDUCATIONAL AND ANCILLARY
 FACILITIES SHALL BE PROVIDE WITH TOLIETS, HAND WASHING
 AND DRINKING FOUNTAINS FOR ALL OCCUPANTS IN RATIOS AND
 ACCESSIBLE AS REQUIRED BY THE FLORIDA BUILDING CODE,
 FLORIDA LAWS AND FEDERAL REGULATIONS. SHEET A-1 & A2
 SHOWS A SINGLE DRINKING FOUNTAIN, PLEASE SHOW A DOUBLE
 HIGH/ LOW, PLEASE SEE IN THE 2017 FBC-ACCESSIBILITY
 CODE REQUIREMENTS FOR DRINKING FOUNTAINS. SHEET A-3
 SHOWS COMPLIANCE WITH :
 NOT SHOWN IN COMPLIANCE. PROTRUDING OBJECTS 307.2
 PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING EDGES
 MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE
 THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY IN TO THE CIRCULATION PATH.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ENGINEER OR ARCHITECT DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY
 HALL DROP BOX) THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS ALONG WITH A "PLAN REVIEW REQUEST
 FORM" EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT
 OR DRAWINGS. PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY E MAILING [email protected] AND ASKING FOR THE FORM
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20060393 2405 MERCER AVE
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-06 Cont ID  
Sent By rmcdouga Date 2020-07-06 Time 08:27 Rev Time 0.00
Received By rmcdouga Date 2020-07-01 Time 16:37 Sent To  
Notes
2020-07-06 08:27:56PLUMBING 1ST REVIEW COMMENTS:
  
 1) PROJECT VALUATION OF $5000 APPEARS LOW. PROVIDE A
 BONA FIDE SIGN CONTRACT. FBC 109.3
  
 2) SHEET A1 LIST 2014 FBC AND SHEET A3 UNDER DETAIL #6
 LIST 2007. AS OF 12/31/2018 WE ARE UNDER THE 2017 FBC
 6TH ED. PLEASE CORRECT.
  
 3) NEW ADA TOILET ROOM IS SHOW @ 76?. MIN PERMITTED
 WITH MIN SIZED SINK OF 19? X 17 WOULD REQUIRE 85? BUT
 AS CALLED OUT ON SHEET A3 THE SINK IS SHOWN AS BEING
 MOUNTED @ 18? OFF SIDE WALL MAKING THE MIN 88? FOR THIS
 PROJECT. THESE ARE FINISHED MEASUREMENTS. FBC-ACC 603,
 604
  
 4) PROVIDE A WATER ISOMETRIC. FBC 107.3.5 SHOWING
 TEMPERED WATER TO THE SINK MAX 110 DEGREES BY AN
 APPROVED ASSE 1070 DEVISE. FBC-PLB 607.1.2
  
 5) PROVIDE THE REQUIRED HI/ LOW DRINKING FOUNTAIN.
 UNABLE TO LOCATE ON PLAN. FBC-PLB 410.3
  
 6) SHEET A3 DETAIL 6 SHOW GRAB BARS AS BEING MOUNTED TO
 THE CENTER. ALL GRAB BAR MEASUREMENTS SHALL BE TO THE
 TOP OF THE GRIPPING SURFACE. FBC 609.4
  
 7) SHEET A3 DETAIL #6 MIRROR IS SHOWN AS MOUNTING TO
 THE BOTTOM. PLEASE SHOWN MAX 40? TO THE BOTTOM OF THE
 REFLECTIVE SURFACE. FBC-ACC 603.3
  
 8) PROVIDE THE REQUIRED CLEAR FLOOR SPACED FOR THE
 TOILET AND SINK IN THE NEW ADA TOILET ROOM. FBC-ACC 604
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 ( CAP GOVERNMENT )
 [email protected]
  
  
2020-07-01 16:37:27TIM HUNT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-01-15 Cont ID  
Sent By jwitmer Date 2021-01-15 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2021-01-15 Time 10:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-11-25 Cont ID  
Sent By medwards Date 2020-11-25 Time 10:11 Rev Time 0.00
Received By medwards Date 2020-11-25 Time 10:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-02 Cont ID  
Sent By medwards Date 2020-11-02 Time 16:01 Rev Time 0.00
Received By medwards Date 2020-11-02 Time 16:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By medwards Date 2020-07-24 Time 14:06 Rev Time 0.00
Received By medwards Date 2020-07-24 Time 14:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-06 Cont ID  
Sent By rmcdouga Date 2020-07-06 Time 08:32 Rev Time 0.00
Received By rmcdouga Date 2020-07-06 Time 08:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-05 Cont ID  
Sent By awooten Date 2020-08-05 Time   Rev Time 0.00
Received By awooten Date 2020-08-05 Time   Sent To  
Notes
***NONE***