Plan Review Details - Permit 20060300
Plan Review Stops For Permit 20060300
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-18 Cont ID  
Sent By rmcphers Date 2020-09-18 Time 15:49 Rev Time 0.00
Received By rmcphers Date 2020-09-18 Time 15:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-21 Cont ID  
Sent By shill Date 2020-08-21 Time 10:58 Rev Time 0.00
Received By shill Date 2020-08-21 Time 10:52 Sent To  
Notes
2020-08-21 11:00:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, THE ENGINEERING FOR THE DIVERSITECH PAD
 REQUIRES THAT WIND LOADS BE DETERMINED BY OTHERS; THIS
 WAS NOT PROVIDED. PROVIDE WIND LOADS AS PER NOTE ON THE
 ENGINEERING.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By rmcphers Date 2020-07-09 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 13:26 Sent To  
Notes
2020-07-09 13:27:36GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SLAB ENGINEERING = SIGNED AND SEALED DRAWINGS NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR
 - IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH
 A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
 2) SLAB ENGINEERING PROVIDED REQUIRES A SEPARATE SIGNED
 AND SEALED ENGINEERING SHOWING THE SITE SPECIFIC WIND
 DESIGN PRESSURES - SEE NOTE NUMBER 2 ON THE PROVIDED
 ENGINEERING.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-15 Cont ID  
Sent By jleahy Date 2020-07-15 Time 10:06 Rev Time 0.00
Received By jleahy Date 2020-07-15 Time 10:04 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By ccole Date 2020-08-20 Time 10:06 Rev Time 0.00
Received By ccole Date 2020-08-17 Time 09:44 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By ccole Date 2020-07-09 Time 16:25 Rev Time 0.00
Received By ccole Date 2020-07-09 Time 16:25 Sent To  
Notes
2020-07-09 16:28:241ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20060300
 7/9/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. PLEASE PROVIDE CORRECTED
 PLANS ADDRESSING THE FOLLWING COMMENTS.
  
 1) GAS ISOMETRIC DRAWING:
 A) IN ORDER TO ENSURE A SAFE OPERATING SYSTEM THE
 DRAWING MUST BE MODIFIED TO SHOW THE ENTIRE SYSTEM
 INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST
 REMOTE OUTLET.THE BTUH LOAD OF EACH EXISTING APPLIANCE
 AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON
 THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES.
 B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND ALL
 BRANCH LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3.
 B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 C) CORRECT THE 396,000 BTUH LOAD LISTED FOR THE
 GENERATOR. THE SUBMITTED SPECS ON PAGE 4 INDICATE
 327,000 BTUH FULL LOAD FOR MODEL RG032- 32KW - G2413.2
 FBC RES.
  
 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH
 MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET
 AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION
 G2421.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-06 Cont ID  
Sent By jleahy Date 2020-10-06 Time 09:47 Rev Time 0.00
Received By jleahy Date 2020-09-17 Time 07:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-05 Cont ID  
Sent By lmarchan Date 2020-09-05 Time 08:35 Rev Time 0.00
Received By lmarchan Date 2020-08-13 Time 15:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-21 Cont ID  
Sent By cpuell Date 2020-07-21 Time 09:34 Rev Time 0.00
Received By cpuell Date 2020-06-22 Time 15:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-20 Cont ID  
Sent By ccole Date 2020-08-20 Time 11:09 Rev Time 0.00
Received By ccole Date 2020-08-17 Time 09:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-09 Cont ID  
Sent By ccole Date 2020-07-09 Time 16:28 Rev Time 0.00
Received By ccole Date 2020-07-09 Time 16:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-18 Cont ID  
Sent By rmcphers Date 2020-09-18 Time 15:50 Rev Time 0.00
Received By rmcphers Date 2020-09-18 Time 15:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-21 Cont ID  
Sent By shill Date 2020-08-21 Time 11:02 Rev Time 0.00
Received By shill Date 2020-08-21 Time 11:02 Sent To  
Notes
2020-08-21 11:03:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A WET SIGNATURE IS NOT CONSIDERED
 A DIGITAL SIGNATURE.
  
 EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF
 (OR MAIL) ONE PAPER ORIGINAL:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By rmcphers Date 2020-07-09 Time 13:27 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 13:27 Sent To  
Notes
2020-07-09 13:28:07SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 3 Status P Date 2020-10-06 Cont ID  
Sent By kalexand Date 2020-10-06 Time 09:34 Rev Time 0.00
Received By kalexand Date 2020-10-06 Time 09:34 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-09-04 Cont ID  
Sent By kalexand Date 2020-09-04 Time 19:20 Rev Time 0.00
Received By kalexand Date 2020-09-04 Time 19:19 Sent To I
Notes
2020-09-04 19:22:38ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 9/4/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT ZLDR SEC.94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK. SHOULD BE 3.8 FT.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By kalexand Date 2020-07-20 Time   Rev Time  
Received By   Date 2020-07-20 Time   Sent To I
Notes
2020-07-20 16:52:04ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 7/20/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PER SEC 94-305(B)(4) MECHANICAL EQUIPMENT MAY ONLY
 PROJECT 4FT INTO A SETBACK. THE SETBACK IS 7.8'; THE
 GENERATOR EXTENDS TOO FAR INTO THE SETBACK.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved