Plan Review Stops For Permit 20060300 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-09-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-09-18 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-09-18 |
Time |
15:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-08-21 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-08-21 |
Time |
10:52 |
Sent To |
|
|
Notes |
2020-08-21 11:00:09 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC R 301, THE ENGINEERING FOR THE DIVERSITECH PAD | | REQUIRES THAT WIND LOADS BE DETERMINED BY OTHERS; THIS | | WAS NOT PROVIDED. PROVIDE WIND LOADS AS PER NOTE ON THE | | ENGINEERING. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-07-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-09 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-09 |
Time |
13:26 |
Sent To |
|
|
Notes |
2020-07-09 13:27:36 | GENERATOR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) SLAB ENGINEERING = SIGNED AND SEALED DRAWINGS NEED | | TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER | | OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR | | - IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR | | DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP | | BOX) THE ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH | | A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON FOR | | SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW | | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] | | AND ASKING FOR THE FORM. | | 2) SLAB ENGINEERING PROVIDED REQUIRES A SEPARATE SIGNED | | AND SEALED ENGINEERING SHOWING THE SITE SPECIFIC WIND | | DESIGN PRESSURES - SEE NOTE NUMBER 2 ON THE PROVIDED | | ENGINEERING. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-07-15 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-07-15 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-07-15 |
Time |
10:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2020-08-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-08-20 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-08-17 |
Time |
09:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-07-09 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-07-09 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-07-09 |
Time |
16:25 |
Sent To |
|
|
Notes |
2020-07-09 16:28:24 | 1ST REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 20060300 | | 7/9/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. PLEASE PROVIDE CORRECTED | | PLANS ADDRESSING THE FOLLWING COMMENTS. | | | | 1) GAS ISOMETRIC DRAWING: | | A) IN ORDER TO ENSURE A SAFE OPERATING SYSTEM THE | | DRAWING MUST BE MODIFIED TO SHOW THE ENTIRE SYSTEM | | INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST | | REMOTE OUTLET.THE BTUH LOAD OF EACH EXISTING APPLIANCE | | AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON | | THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. | | B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM | | FROM THE METER TO THE MOST REMOTE OUTLET, AND ALL | | BRANCH LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & | | G2413.4.3. | | B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE | | OUTLET OF THE REGULATOR- SECTION G2421.1 | | C) CORRECT THE 396,000 BTUH LOAD LISTED FOR THE | | GENERATOR. THE SUBMITTED SPECS ON PAGE 4 INDICATE | | 327,000 BTUH FULL LOAD FOR MODEL RG032- 32KW - G2413.2 | | FBC RES. | | | | 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH | | MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET | | AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION | | G2421.1. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-10-06 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-10-06 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-09-17 |
Time |
07:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-09-05 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-09-05 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-08-13 |
Time |
15:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-07-21 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2020-07-21 |
Time |
09:34 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2020-06-22 |
Time |
15:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2020-08-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-08-20 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-08-17 |
Time |
09:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-07-09 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-07-09 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-07-09 |
Time |
16:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-09-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-09-18 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-09-18 |
Time |
15:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-08-21 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-08-21 |
Time |
11:02 |
Sent To |
|
|
Notes |
2020-08-21 11:03:19 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS. A SCAN OF A WET SIGNATURE IS NOT CONSIDERED | | A DIGITAL SIGNATURE. | | | | EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF | | (OR MAIL) ONE PAPER ORIGINAL: | | | | BUILDING DIVISION, FIRST FLOOR | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST | | WEST PALM BEACH, FL 33401 | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-07-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-09 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-09 |
Time |
13:27 |
Sent To |
|
|
Notes |
2020-07-09 13:28:07 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2020-10-06 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2020-10-06 |
Time |
09:34 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2020-10-06 |
Time |
09:34 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2020-09-04 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2020-09-04 |
Time |
19:20 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2020-09-04 |
Time |
19:19 |
Sent To |
I |
|
Notes |
2020-09-04 19:22:38 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 9/4/20 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED | | SETBACK. PURSUANT ZLDR SEC.94-305(B)(4): MECHANICAL | | EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A | | REQUIRED SETBACK. SHOULD BE 3.8 FT. | | | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALLY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG | | IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | KIZZI ALEXANDRE, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1442 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2020-07-20 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2020-07-20 |
Time |
|
Sent To |
I |
|
Notes |
2020-07-20 16:52:04 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 7/20/20 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PER SEC 94-305(B)(4) MECHANICAL EQUIPMENT MAY ONLY | | PROJECT 4FT INTO A SETBACK. THE SETBACK IS 7.8'; THE | | GENERATOR EXTENDS TOO FAR INTO THE SETBACK. | | | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST | | THAT IT BE SENT TO YOU BY EMAILING [email protected] | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | KIZZI ALEXANDRE, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1442 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|