Plan Review Details - Permit 20060280
Plan Review Stops For Permit 20060280
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 11:23 Rev Time 0.00
Received By jleahy Date 2021-03-03 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By fgiaquin Date 2020-07-09 Time 19:59 Rev Time 0.00
Received By fgiaquin Date 2020-07-09 Time 19:37 Sent To  
Notes
2020-07-09 19:59:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS SUBMITTED DIGITALLY AND THAT HAVE BEEN
 PREPARED BY A DESIGN PROFESSIONAL MUST BE DIGITALLY
 SIGNED.
  
 2. PROVIDE NOTE ON PLAN THAT EQUIPMENT GROUNDING
 CONDUCTORS AND GROUNDED CONDUCTOR (NEUTRAL) WILL BE
 SEPARATED IN OLD SERVICE DISCONNECTING MEANS (ATS). NEC
 250.24A5
  
 3. FAULT CURRENT CALCULATION AND LABELING REQUIRED. NEC
 110.9,110.10, 110.24A&B,
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 11:24 Rev Time 0.00
Received By jleahy Date 2021-02-26 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-09 Cont ID  
Sent By fgiaquin Date 2020-07-09 Time 19:59 Rev Time 0.00
Received By fgiaquin Date 2020-06-19 Time 11:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 11:24 Rev Time 0.00
Received By jleahy Date 2021-03-05 Time 11:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By fgiaquin Date 2020-07-09 Time 19:59 Rev Time 0.00
Received By fgiaquin Date 2020-07-09 Time 19:59 Sent To  
Notes
2020-07-09 19:59:46MUST BE DIGITALLY SIGNED BY PE

Review Stop Z ZONING
Rev No 1 Status N Date 2021-03-04 Cont ID  
Sent By eschneid Date 2021-03-04 Time 15:52 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***