Plan Review Details - Permit 20060268
Plan Review Stops For Permit 20060268
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-04 Cont ID  
Sent By jleahy Date 2021-03-04 Time 16:49 Rev Time 0.00
Received By jleahy Date 2021-03-03 Time 16:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 13:47 Rev Time 0.00
Received By jleahy Date 2020-07-13 Time 13:47 Sent To  
Notes
2020-07-13 13:47:45FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
  
 2) PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24. ELECTRICAL REVIEW STATUS:
 DENIED, SEE COMMENTS BELOW.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-04 Cont ID  
Sent By jleahy Date 2021-03-04 Time 16:50 Rev Time 0.00
Received By jleahy Date 2021-02-26 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 13:47 Rev Time 0.00
Received By jleahy Date 2020-06-19 Time 11:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-04 Cont ID  
Sent By jleahy Date 2021-03-04 Time 16:49 Rev Time 0.00
Received By jleahy Date 2021-03-04 Time 12:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 13:46 Rev Time 0.00
Received By jleahy Date 2020-07-13 Time 13:46 Sent To  
Notes
2020-07-13 13:46:39FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED FOR DESIGN
 PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  