Plan Review Details - Permit 20060201
Plan Review Stops For Permit 20060201
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2020-07-28 Cont ID  
Sent By jleahy Date 2020-07-28 Time 14:07 Rev Time 0.00
Received By jleahy Date 2020-07-28 Time 14:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-07-15 Cont ID  
Sent By jleahy Date 2020-07-15 Time 15:35 Rev Time 0.00
Received By jleahy Date 2020-07-15 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-07-09 Cont ID  
Sent By jleahy Date 2020-07-09 Time 12:25 Rev Time 0.00
Received By jleahy Date 2020-07-09 Time 12:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-25 Cont ID  
Sent By jpearson Date 2020-06-25 Time 08:47 Rev Time 0.00
Received By jpearson Date 2020-06-25 Time 08:47 Sent To  
Notes
2020-06-25 08:47:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. WPB
 FBC 109.3 (NOT ADDRESSED.)
 2. PROVIDE SPEC SHEETS FOR ITEMS TO BE INSTALLED. NEC
 110.3; WPB FBC 107.2.1 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-11 Cont ID  
Sent By jpearson Date 2020-06-11 Time 15:55 Rev Time 0.00
Received By jpearson Date 2020-06-11 Time 15:12 Sent To  
Notes
2020-06-11 15:55:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. WPB
 FBC 109.3
 2. PROVIDE SPEC SHEETS FOR ITEMS TO BE INSTALLED. NEC
 110.3; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2020-07-17 Cont ID  
Sent By pleduc Date 2020-07-17 Time   Rev Time 0.00
Received By pleduc Date 2020-07-17 Time 10:18 Sent To  
Notes
2020-07-17 13:51:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL CARDER READER DOORS SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF NFPA 101, AS PREVIOUSLY
 SUBMITTED.
  
 ADDITIONALLY, STAIRWELL INSTALLS SHALL ALSO RELEASE
 WITH LOSS OF POWER. THE EGRESS DOORS SHALL UNLATCH IF
 APPLICABLE FOR EGRESS PURPOSES ON FIRE ALARM AND LOSS
 OF POWER ENSURING THAT NO PERSON CAN BE TRAPPED INSIDE
 ANY ROOM, ANY AREA, NOR STAIRWELL.
  
 PLEASE ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pleduc Date 2020-07-13 Time 10:45 Sent To  
Notes
2020-07-13 10:48:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE REMIANS NOT INDICATIONS IN WRITING NOR CLOUDS
 ON THE PALN SHEETS SHOWING WHAT AND WHERE CHANGES WERE
 MADE.
  
 PLACING A NOTE IN THE TITLE BLOCK STATING "REVISED PER
 FM COMMENTS" DOES NOT ADDRESS WHAT IS REQUIRED TO
 DOCUMENT THE CHANGES.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
  
 CONTACT ME DIRECTLY SO THAT WE CAN DISCUSS WHAT IS
 NEEDED.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2020-07-01 Cont ID  
Sent By pleduc Date 2020-07-01 Time   Rev Time 0.00
Received By pleduc Date 2020-07-01 Time 12:20 Sent To  
Notes
2020-07-01 15:28:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF THE CHANGES/REVISIONS ON
 THE SUBMITTED PLANS NOR ANY NARRATIVE EXPLAINING THE
 CHANGES.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE PROVIDE CLOUDED CHANGES ON THE PLAN SHEETS OR A
 DETAILED NARRATIVE FOR EACH CHANGE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 THE FOLLOWING COMMENTS WERE FROM THE ORIGINAL REVIEW
 THAT HAVE NOT BEEN ADDRESSED WITH ANY KIND OF CLARITY.
  
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT APPEARS THAT THERE IS NO RE-ENTRY WITHIN THE
 STAIRWELLS.
  
 PER NFPA 101 CH 28 AND CH 7,
  
 28.2.2.2 DOORS.
 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 28.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH
 28.2.2.2.2.1, 28.2.2.2.2.2, 28.2.2.2.2.3, OR
 28.2.2.2.2.4.
 28.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE
 LOCKED
 AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED.
 28.2.2.2.2.2 DELAYED-EGRESS LOCKS COMPLYING WITH
 7.2.1.6.1 SHALL
 BE PERMITTED.
 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING
 WITH
 7.2.1.6.2 SHALL BE PERMITTED.
  
 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE
 THAN FOUR STORIES, UNLESS PERMITTED BY 7.2.1.5.8.2,
 SHALL MEET ONE
 OF THE FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE
 BUILDING SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF
 THE BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO
 UNLOCK ALL
 STAIR ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY.
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH
 7.2.1.5.8.1.
 7.2.1.5.8.1 DOOR ASSEMBLIES ON STAIR ENCLOSURES SHALL
 BE PERMITTED
 TO BE EQUIPPED WITH HARDWARE THAT PREVENTS RE-ENTRY
 INTO THE
 INTERIOR OF THE BUILDING, PROVIDED THAT ALL OF THE
 FOLLOWING CRITERIA
 ARE MET:
 (1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS
 POSSIBLE TO
 LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER EXIT.
 (2) THERE SHALL BE NOT MORE THAN FOUR STORIES
 INTERVENING
 BETWEEN STORIES WHERE IT IS POSSIBLE TO LEAVE THE STAIR
 ENCLOSURE TO ACCESS ANOTHER EXIT.
 (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR
 NEXT-TO-TOP
 STORY SERVED BY THE STAIR ENCLOSURE, AND SUCH STORY
 SHALL ALLOW
 ACCESS TO ANOTHER EXIT.
 (4) DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE
 IDENTIFIED AS SUCH
 ON THE STAIR SIDE OF THE DOOR LEAF.
 (5) DOOR ASSEMBLIES NOT ALLOWING RE-ENTRY SHALL BE
 PROVIDED WITH
 A SIGN ON THE STAIR SIDE INDICATING THE LOCATION OF THE
 NEAREST
 DOOR OPENING, IN EACH DIRECTION OF TRAVEL, THAT ALLOWS
 RE-ENTRY
 OR EXIT.
  
 PLEASE REVIEW, CORRECT AND PROVIDE DETAILS.
  
  
  
 2) STAIRS S 101 - THER APPEAARS TO BE ACCESS CONRTOL
 LIMITING THE EXIT FROM WITHIN THE STAIRWELL WITHOUT A
 CARDER READER.
  
 THOUGH THIS STAIR MAY NOT BE A REQUIRED EGRESS IF A
 PERSON IS ALLOWED TO ENTER IT, FROM ANY FLOOR, HOW
 WOULD THEY BE ABLE TO EXIT IT AT ANY FLOOR?
  
 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING
 WITH
 7.2.1.6.2 SHALL BE PERMITTED.
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN
 THE
 MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH
 ELECTRICAL
 LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL
 OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO
 UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON
 DETECTION
 OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS
 UPON LOSS OF POWER TO THE SENSOR OR TO THE PART OF THE
 ACCESS
 CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF
 EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL
 OF
 THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS
 SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM) VERTICALLY
 ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM) OF THE
 SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE
 AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS:
 PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN
 DIRECT INTERRUPTION OF POWER TO THE LOCK ? INDEPENDENT
 OF THE LOCKING SYSTEM ELECTRONICS ? AND THE LOCK SHALL
 REMAIN UNLOCKED FOR NOT LESS THAN 30 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF
 PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN
 THE
 DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL REMAIN
 UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS
 BEEN
 MANUALLY RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE
 BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN
 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR
 LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE
 DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE
 DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR
 LEAVES
 SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING
 SYSTEM HAS BEEN MANUALLY RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN
 EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE
 PROVIDED
 WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-06-24 Cont ID  
Sent By pleduc Date 2020-06-24 Time   Rev Time 0.00
Received By pleduc Date 2020-06-24 Time 12:23 Sent To  
Notes
2020-06-24 12:38:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF THE CHANGES/REVISIONS ON
 THE SUBMITTED PLANS NOR ANY NARRATIVE EXPLAINING THE
 CHANGES.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE PROVIDE CLOUDED CHANGES ON THE PLAN SHEETS OR A
 DETAILED NARRATIVE FOR EACH CHANGE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By pleduc Date 2020-06-09 Time   Rev Time 0.00
Received By pleduc Date 2020-06-09 Time 15:12 Sent To  
Notes
2020-06-09 15:39:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT APPEARS THAT THERE IS NO RE-ENTRY WITHIN THE
 STAIRWELLS.
  
 PER NFPA 101 CH 28 AND CH 7,
  
 28.2.2.2 DOORS.
 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 28.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH
 28.2.2.2.2.1, 28.2.2.2.2.2, 28.2.2.2.2.3, OR
 28.2.2.2.2.4.
 28.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE
 LOCKED
 AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED.
 28.2.2.2.2.2 DELAYED-EGRESS LOCKS COMPLYING WITH
 7.2.1.6.1 SHALL
 BE PERMITTED.
 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING
 WITH
 7.2.1.6.2 SHALL BE PERMITTED.
  
 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE
 THAN FOUR STORIES, UNLESS PERMITTED BY 7.2.1.5.8.2,
 SHALL MEET ONE
 OF THE FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE
 BUILDING SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF
 THE BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO
 UNLOCK ALL
 STAIR ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY.
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH
 7.2.1.5.8.1.
 7.2.1.5.8.1 DOOR ASSEMBLIES ON STAIR ENCLOSURES SHALL
 BE PERMITTED
 TO BE EQUIPPED WITH HARDWARE THAT PREVENTS RE-ENTRY
 INTO THE
 INTERIOR OF THE BUILDING, PROVIDED THAT ALL OF THE
 FOLLOWING CRITERIA
 ARE MET:
 (1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS
 POSSIBLE TO
 LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER EXIT.
 (2) THERE SHALL BE NOT MORE THAN FOUR STORIES
 INTERVENING
 BETWEEN STORIES WHERE IT IS POSSIBLE TO LEAVE THE STAIR
 ENCLOSURE TO ACCESS ANOTHER EXIT.
 (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR
 NEXT-TO-TOP
 STORY SERVED BY THE STAIR ENCLOSURE, AND SUCH STORY
 SHALL ALLOW
 ACCESS TO ANOTHER EXIT.
 (4) DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE
 IDENTIFIED AS SUCH
 ON THE STAIR SIDE OF THE DOOR LEAF.
 (5) DOOR ASSEMBLIES NOT ALLOWING RE-ENTRY SHALL BE
 PROVIDED WITH
 A SIGN ON THE STAIR SIDE INDICATING THE LOCATION OF THE
 NEAREST
 DOOR OPENING, IN EACH DIRECTION OF TRAVEL, THAT ALLOWS
 RE-ENTRY
 OR EXIT.
  
 PLEASE REVIEW, CORRECT AND PROVIDE DETAILS.
  
  
  
 2) STAIRS S 101 - THER APPEAARS TO BE ACCESS CONRTOL
 LIMITING THE EXIT FROM WITHIN THE STAIRWELL WITHOUT A
 CARDER READER.
  
 THOUGH THIS STAIR MAY NOT BE A REQUIRED EGRESS IF A
 PERSON IS ALLOWED TO ENTER IT, FROM ANY FLOOR, HOW
 WOULD THEY BE ABLE TO EXIT IT AT ANY FLOOR?
  
 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING
 WITH
 7.2.1.6.2 SHALL BE PERMITTED.
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN
 THE
 MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH
 ELECTRICAL
 LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL
 OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO
 UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON
 DETECTION
 OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS
 UPON LOSS OF POWER TO THE SENSOR OR TO THE PART OF THE
 ACCESS
 CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF
 EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL
 OF
 THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS
 SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM) VERTICALLY
 ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM) OF THE
 SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE
 AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS:
 PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN
 DIRECT INTERRUPTION OF POWER TO THE LOCK ? INDEPENDENT
 OF THE LOCKING SYSTEM ELECTRONICS ? AND THE LOCK SHALL
 REMAIN UNLOCKED FOR NOT LESS THAN 30 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF
 PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN
 THE
 DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL REMAIN
 UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS
 BEEN
 MANUALLY RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE
 BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN
 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR
 LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE
 DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE
 DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR
 LEAVES
 SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING
 SYSTEM HAS BEEN MANUALLY RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN
 EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE
 PROVIDED
 WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-07-28 Cont ID  
Sent By jleahy Date 2020-07-28 Time 14:08 Rev Time 0.00
Received By jleahy Date 2020-07-16 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-07-15 Cont ID  
Sent By jleahy Date 2020-07-15 Time 15:36 Rev Time 0.00
Received By jleahy Date 2020-07-10 Time 11:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-09 Cont ID  
Sent By jleahy Date 2020-07-09 Time 12:32 Rev Time 0.00
Received By jleahy Date 2020-06-29 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-06-25 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-23 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-06-11 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-08 Time 14:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2020-07-28 Cont ID  
Sent By jleahy Date 2020-07-28 Time 14:07 Rev Time 0.00
Received By jleahy Date 2020-07-28 Time 14:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-07-15 Cont ID  
Sent By jleahy Date 2020-07-15 Time 15:35 Rev Time 0.00
Received By jleahy Date 2020-07-15 Time 15:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-07-10 Cont ID  
Sent By jleahy Date 2020-07-10 Time 10:52 Rev Time 0.00
Received By jleahy Date 2020-07-10 Time 10:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-07-09 Cont ID  
Sent By jleahy Date 2020-07-09 Time 12:31 Rev Time 0.00
Received By jleahy Date 2020-07-09 Time 12:31 Sent To  
Notes
2020-07-09 12:34:11SEE SIGNATURE NOTES FROM THE LAST TWO REVIEWS JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-06-25 Cont ID  
Sent By jpearson Date 2020-06-25 Time 08:46 Rev Time 0.00
Received By jpearson Date 2020-06-25 Time 08:46 Sent To  
Notes
2020-06-25 08:46:23NO DIGITAL SIGNATURE APPARENT. PERHAPS THESE ARE
 SCANNED SHEETS? PER THE WPB AMENDMENTS TO THE FBC, EACH
 SHEET OF PLAN IS REQUIRED TO BE SIGNED (AND SEALED FOR
 DESIGN PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-11 Cont ID  
Sent By jpearson Date 2020-06-11 Time 15:16 Rev Time 0.00
Received By jpearson Date 2020-06-11 Time 15:16 Sent To  
Notes
2020-06-11 15:16:29ALL SHEETS SHOW AN ERROR DURING SIGNATURE VERIFICATION
 MESSAGE. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET
 OF PLAN IS REQUIRED TO BE SIGNED (AND SEALED FOR DESIGN
 PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481