Plan Review Details - Permit 20060178
Plan Review Stops For Permit 20060178
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By cthroop Date 2020-10-02 Time 16:22 Rev Time 0.00
Received By cthroop Date 2020-10-02 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By cthroop Date 2020-07-08 Time 16:30 Rev Time 0.00
Received By cthroop Date 2020-07-08 Time 15:28 Sent To  
Notes
2020-07-08 16:30:50PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS FOR THE
 GENERATOR PURSUANT TO FBC-R301.2 AND AS REQUIRED BY THE
 GENERATOR PAD ENGINEERING THAT WAS SUBMITTED.
  
 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-24 Cont ID  
Sent By jleahy Date 2020-09-24 Time 17:06 Rev Time 0.00
Received By jleahy Date 2020-09-24 Time 17:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By cthroop Date 2020-07-08 Time 16:31 Rev Time 0.00
Received By cthroop Date 2020-07-08 Time 15:28 Sent To  
Notes
2020-07-08 16:31:36PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ATS SPECS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-10-01 Cont ID  
Sent By abelisle Date 2020-10-01 Time 05:09 Rev Time 0.00
Received By abelisle Date 2020-10-01 Time 04:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By cthroop Date 2020-07-08 Time 16:32 Rev Time 0.00
Received By cthroop Date 2020-07-08 Time 15:28 Sent To  
Notes
2020-07-08 16:32:24PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DETAIL OF GENERATOR GAS COMPONENTS. RISER,
 SHUTOFF, REGULATOR, DRIP LEG AND FLEX CONNECTOR.
  
 2. PROVIDE APPROPRIATE TABLE FOR 2 PSI P.E. PIPE FROM
 FBC RESIDENTIAL FUEL GAS TABLES.
  
 3. PROVIDE TOTAL SUPPLY BTU FROM UTILITY.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-02 Cont ID  
Sent By cthroop Date 2020-10-02 Time 16:22 Rev Time 0.00
Received By cthroop Date 2020-09-17 Time 07:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-08 Cont ID  
Sent By cthroop Date 2020-07-08 Time 16:33 Rev Time 0.00
Received By cthroop Date 2020-06-22 Time 14:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-01 Cont ID  
Sent By abelisle Date 2020-10-01 Time 04:56 Rev Time 0.00
Received By abelisle Date 2020-10-01 Time 04:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-08 Cont ID  
Sent By cthroop Date 2020-07-08 Time 16:33 Rev Time 0.00
Received By cthroop Date 2020-07-08 Time 15:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By cthroop Date 2020-10-02 Time 16:22 Rev Time 0.00
Received By cthroop Date 2020-10-02 Time 16:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By cthroop Date 2020-07-08 Time 16:32 Rev Time 0.00
Received By cthroop Date 2020-07-08 Time 15:28 Sent To  
Notes
2020-07-08 16:33:06PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  
 . UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By rthermid Date 2020-06-29 Time   Rev Time  
Received By rthermid Date 2020-06-29 Time   Sent To I
Notes
***NONE***