Plan Review Details - Permit 20060176
Plan Review Stops For Permit 20060176
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-29 Cont ID  
Sent By cthroop Date 2020-08-29 Time 08:22 Rev Time 0.00
Received By cthroop Date 2020-08-29 Time 07:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 13:40 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 13:06 Sent To  
Notes
2020-07-07 13:44:03PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS FOR THE
 GENERATOR PURSUANT TO FBC-R301.2 AND AS REQUIRED BY THE
 GENERATOR PAD ENGINEERING THAT WAS SUBMITTED.
  
 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-29 Cont ID  
Sent By cthroop Date 2020-08-29 Time 08:25 Rev Time 0.00
Received By cthroop Date 2020-08-29 Time 07:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 13:47 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 13:06 Sent To  
Notes
2020-07-07 15:38:39PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ATS SPECS.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-08-29 Cont ID  
Sent By cthroop Date 2020-08-29 Time 08:31 Rev Time 0.00
Received By cthroop Date 2020-08-29 Time 07:58 Sent To  
Notes
2020-08-29 08:32:05PROVISO: SYSTEM PRESSURE CHANGED FROM 12" WC TO 2 PSI.
 LOW PRESSURE REGULATORS REQUIRED AT EXISITNG
 APPLIANCES. CT

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 13:47 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 13:06 Sent To  
Notes
2020-07-07 13:55:28PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DETAIL OF GENERATOR GAS COMPONENTS. RISER,
 SHUTOFF, REGULATOR, DRIP LEG AND FLEX CONNECTOR.
  
 2. PROVIDE APPROPRIATE TABLE FOR 2 PSI P.E. PIPE FROM
 FBC RESIDENTIAL FUEL GAS TABLES.
  
 3. PROVIDE TOTAL SUPPLY BTU FROM UTILITY.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-09-08 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-03 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-02 Cont ID  
Sent By lmarchan Date 2020-09-02 Time 16:38 Rev Time 0.00
Received By lmarchan Date 2020-08-24 Time 15:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 13:55 Rev Time 0.00
Received By cthroop Date 2020-06-22 Time 14:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-29 Cont ID  
Sent By cthroop Date 2020-08-29 Time 08:15 Rev Time 0.00
Received By cthroop Date 2020-08-29 Time 07:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 13:47 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 13:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-29 Cont ID  
Sent By cthroop Date 2020-08-29 Time 08:25 Rev Time 0.00
Received By cthroop Date 2020-08-29 Time 07:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 13:44 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 13:06 Sent To  
Notes
2020-07-07 13:45:44PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  
 . UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-09-08 Cont ID  
Sent By rthermid Date 2020-09-08 Time   Rev Time 0.00
Received By rthermid Date 2020-09-08 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-09-01 Cont ID  
Sent By rthermid Date 2020-09-01 Time   Rev Time 0.00
Received By rthermid Date 2020-09-01 Time   Sent To I
Notes
2020-09-01 08:06:00ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 9/1/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE PROPOSED GENERATOR LOCATION DOES NOT MEET THE
 SETBACK REQUIREMENT. PURSUANT TO THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR),
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. THE
 REQUIRED SETBACK FOR THIS PROPERTY IS 8 FEET, THE
 GENERATOR MUST BE A MINIMUM OF 4 FEET FROM THE SIDE
 PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By rthermid Date 2020-06-29 Time   Rev Time  
Received By rthermid Date 2020-06-29 Time   Sent To I
Notes
2020-06-29 13:27:33ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 6/29/020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1443
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  