Plan Review Details - Permit 20060166
Plan Review Stops For Permit 20060166
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-18 Cont ID  
Sent By rmcdouga Date 2020-08-18 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2020-08-18 Time 10:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-22 Cont ID  
Sent By rmcdouga Date 2020-07-22 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2020-07-22 Time 11:26 Sent To  
Notes
2020-07-22 13:20:07PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING IS NOT THE CORRECT ONE
 FOR THE GENERAC MODEL G0007042-2, 22 KW GENERATOR THE
 SPECIFICATIONS WERE SUBMITTED FOR. FBC 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By rmcdouga Date 2020-06-25 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2020-06-25 Time 07:31 Sent To  
Notes
2020-06-25 07:36:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS FOR THE
 GENERATOR PURSUANT TO FBC-R301.2 AND AS REQUIRED BY THE
 GENERATOR PAD ENGINEERING THAT WAS SUBMITTED.
  
 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-25 Cont ID  
Sent By cthroop Date 2020-06-25 Time 11:59 Rev Time 0.00
Received By cthroop Date 2020-06-25 Time 11:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-06-25 Cont ID  
Sent By cthroop Date 2020-06-25 Time 12:02 Rev Time 0.00
Received By cthroop Date 2020-06-25 Time 11:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-18 Cont ID  
Sent By rmcdouga Date 2020-08-18 Time 10:46 Rev Time 0.00
Received By rmcdouga Date 2020-07-31 Time 07:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-22 Cont ID  
Sent By rmcdouga Date 2020-07-22 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2020-07-06 Time 12:40 Sent To  
Notes
2020-07-16 12:40:2807/16/2020 RESUBMITTAL UPLOADED TO PROJECT DOX. DRAWING
 WITH ENGINEER'S ORIGINAL SIGNATURE SENT TO "STORAGE".
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-25 Cont ID  
Sent By cthroop Date 2020-06-25 Time 12:02 Rev Time 0.00
Received By cthroop Date 2020-06-11 Time 16:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-25 Cont ID  
Sent By cthroop Date 2020-06-25 Time 11:59 Rev Time 0.00
Received By cthroop Date 2020-06-25 Time 11:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-08-19 Cont ID  
Sent By jgomez Date 2020-08-19 Time 16:37 Rev Time 0.00
Received By jgomez Date 2020-08-19 Time 16:37 Sent To  
Notes
2020-08-19 16:37:3708/19/2020 ENGINEER DRAWING MATCHES ONE UPLOADED TO
 PROJECTDOX. DRAWING WITH EMBOSSED SEAL AND ORIGINAL
 SIGNATURE SENT TO STORAGE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-04 Cont ID  
Sent By jgomez Date 2020-08-04 Time 10:47 Rev Time 0.00
Received By jgomez Date 2020-08-04 Time 10:36 Sent To  
Notes
2020-08-04 10:47:35DRAWING WITH ENGINEER'S ORIGINAL SIGNATURE SENT TO
 "STORAGE". JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-16 Cont ID  
Sent By jgomez Date 2020-07-16 Time 12:39 Rev Time 0.00
Received By jgomez Date 2020-07-16 Time 12:39 Sent To  
Notes
2020-07-16 12:39:5907/16/2020 RESUBMITTAL UPLOADED TO PROJECT DOX. DRAWING
 WITH ENGINEER'S ORIGINAL SIGNATURE SENT TO "STORAGE".
 JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By rmcdouga Date 2020-06-25 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2020-06-25 Time 07:31 Sent To  
Notes
2020-06-25 07:36:50THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2020-06-19 Cont ID  
Sent By rthermid Date 2020-06-19 Time   Rev Time  
Received By rthermid Date 2020-06-19 Time   Sent To I
Notes
***NONE***