Plan Review Details - Permit 20060162
Plan Review Stops For Permit 20060162
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By cthroop Date 2020-10-13 Time 14:19 Rev Time 0.00
Received By cthroop Date 2020-10-13 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 14:36 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 14:09 Sent To  
Notes
2020-07-07 14:36:33PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS FOR THE
 GENERATOR PURSUANT TO FBC-R301.2 AND AS REQUIRED BY THE
 GENERATOR PAD ENGINEERING THAT WAS SUBMITTED.
  
 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By cthroop Date 2020-10-13 Time 08:35 Rev Time 0.00
Received By cthroop Date 2020-10-13 Time 08:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 14:35 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 14:09 Sent To  
Notes
2020-07-07 15:39:32PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ATS SPECS.
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-09-23 Cont ID  
Sent By shill Date 2020-09-23 Time 14:54 Rev Time 0.00
Received By shill Date 2020-09-23 Time 14:54 Sent To  
Notes
2020-09-23 14:55:38PROVISO: SEPARATE PERMIT AND PLANS REQUIRED PRIOR TO
 COMMENCEMENT OF GAS WORK
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 14:37 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 14:09 Sent To  
Notes
2020-07-07 14:42:39PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 OUR RECORDS INDICATE AN EXISTING NG SERVICE AT THE
 PROPERTY. PROVIDE A CODE COMPLIANT GAS RISER DIAGRAHM.
  
 1. PROVIDE DETAIL OF GENERATOR GAS COMPONENTS. RISER,
 SHUTOFF, REGULATOR, DRIP LEG AND FLEX CONNECTOR.
  
 2. PROVIDE APPROPRIATE TABLE FOR 2 PSI P.E. PIPE FROM
 FBC RESIDENTIAL FUEL GAS TABLES.
  
 3. PROVIDE TOTAL SUPPLY BTU FROM UTILITY.
  
 4. PROVIDE TOTAL GAS LOADS. INCLUDE EXISTING GAS
 APPLIANCES.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-13 Cont ID  
Sent By cthroop Date 2020-10-13 Time 14:19 Rev Time 0.00
Received By cthroop Date 2020-09-29 Time 14:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 14:42 Rev Time 0.00
Received By cthroop Date 2020-06-22 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 14:34 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 14:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By cthroop Date 2020-10-13 Time 08:36 Rev Time 0.00
Received By cthroop Date 2020-10-13 Time 08:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By cthroop Date 2020-07-07 Time 14:37 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 14:10 Sent To  
Notes
2020-07-07 14:37:32PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  
 . UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  