Plan Review Details - Permit 20060159
Plan Review Stops For Permit 20060159
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-01 Cont ID  
Sent By cthroop Date 2020-08-01 Time 08:35 Rev Time 0.00
Received By cthroop Date 2020-08-01 Time 08:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By rmcphers Date 2020-07-09 Time 13:42 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 13:41 Sent To  
Notes
2020-07-09 13:42:46GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SLAB ENGINEERING = SIGNED AND SEALED DRAWINGS NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR
 - IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH
 A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
 2) SLAB ENGINEERING PROVIDED REQUIRES A SEPARATE SIGNED
 AND SEALED ENGINEERING SHOWING THE SITE SPECIFIC WIND
 DESIGN PRESSURES - SEE NOTE NUMBER 2 ON THE PROVIDED
 ENGINEERING.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-01 Cont ID  
Sent By cthroop Date 2020-08-01 Time 08:35 Rev Time 0.00
Received By cthroop Date 2020-08-01 Time 08:04 Sent To  
Notes
2020-08-01 08:35:59PROVISO: PROVIDE ATS SPEC'S TO CITY INSPECTOR. CT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By cthroop Date 2020-07-10 Time 12:55 Rev Time 0.00
Received By cthroop Date 2020-07-10 Time 12:49 Sent To  
Notes
2020-07-10 12:55:58PLAN REVIEW - ELECTRIC
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ATS SPECIFICATIONS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-09-10 Cont ID  
Sent By lcrespo Date 2020-09-10 Time 14:06 Rev Time 0.00
Received By lcrespo Date 2020-09-10 Time 14:06 Sent To  
Notes
2020-09-10 14:07:0609/10/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-07-31 Cont ID  
Sent By lcrespo Date 2020-07-31 Time 10:57 Rev Time 0.00
Received By lcrespo Date 2020-07-31 Time 10:57 Sent To  
Notes
2020-07-31 10:58:2307/31/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS DRAWING IS A DUPLICATE OF ANOTHER DRAWING FOR A
 DIFFERENT REVIEW AND IT IS INCOMPLETE, IT MUST BE
 MODIFIED TO SHOW THE ENTIRE SYSTEM INCLUDING ALL BRANCH
 PIPES FROM THE METER TO THE MOST REMOTE OUTLET, YOU MAY
 WANT TO REDRAW IT. THE SIZE OF THE RECORDED SYSTEM IS 1
 1/2" AND YOU HAVE 1" BRANCHING OUT SO PLEASE CORRECT ON
 NEW DRAWING. SHOW THE BTU'S LOAD OF EACH APPLIANCE AND
 THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON THE
 DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. LIST THE
 BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2017 FBC RES. SEC. G2413.
  
 2. PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3.
  
 3. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By cthroop Date 2020-07-10 Time 12:53 Rev Time 0.00
Received By cthroop Date 2020-07-10 Time 12:49 Sent To  
Notes
2020-07-10 12:55:07PLAN REVIEW - FUEL GAS GENERATOR
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) GAS ISOMETRIC DRAWING:
 A) THE DRAWING IS INCOMPLETE AND MUST BE MODIFIED TO
 SHOW THE ENTIRE SYSTEM INCLUDING ALL BRANCH PIPES FROM
 THE METER TO THE MOST REMOTE OUTLET. THE BTUH LOAD OF
 EACH APPLIANCE AND THE LOCATIONS OF REGULATORS SHALL BE
 INDICATED ON THE DRAWING- SECTIONS G2412.3 & G2412.4
 FBC RES.
 B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3.
 B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 C) GENERATOR SPES NOT PROVIDED. CANNOT VERIFY BTU LOAD.
 G2413.2 FBC RES.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-10 Cont ID  
Sent By lcrespo Date 2020-09-10 Time 14:06 Rev Time 0.00
Received By lcrespo Date 2020-09-02 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-13 Cont ID  
Sent By lmarchan Date 2020-08-13 Time 09:27 Rev Time 0.00
Received By lmarchan Date 2020-07-22 Time 15:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2020-07-20 Cont ID  
Sent By shill Date 2020-07-20 Time 08:58 Rev Time 0.00
Received By shill Date 2020-06-22 Time 14:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-09-10 Cont ID  
Sent By lcrespo Date 2020-09-10 Time 14:06 Rev Time 0.00
Received By lcrespo Date 2020-09-10 Time 14:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-31 Cont ID  
Sent By lcrespo Date 2020-07-31 Time 10:59 Rev Time 0.00
Received By lcrespo Date 2020-07-31 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-10 Cont ID  
Sent By cthroop Date 2020-07-10 Time 12:56 Rev Time 0.00
Received By cthroop Date 2020-07-10 Time 12:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-01 Cont ID  
Sent By cthroop Date 2020-08-01 Time 08:35 Rev Time 0.00
Received By cthroop Date 2020-08-01 Time 08:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By rmcphers Date 2020-07-09 Time 13:42 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 13:42 Sent To  
Notes
2020-07-09 13:43:16SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2020-08-13 Cont ID  
Sent By kalexand Date 2020-08-13 Time 08:09 Rev Time 0.00
Received By kalexand Date 2020-08-13 Time 08:08 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-07-17 Time   Rev Time  
Received By   Date 2020-07-17 Time   Sent To I
Notes
***NONE***