Plan Review Details - Permit 20060156
Plan Review Stops For Permit 20060156
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-14 Cont ID  
Sent By dbattles Date 2020-07-14 Time 14:36 Rev Time 0.00
Received By dbattles Date 2020-07-14 Time 14:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-24 Cont ID  
Sent By rmcdouga Date 2020-06-24 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2020-06-24 Time 15:04 Sent To  
Notes
2020-06-24 15:17:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS FOR THE
 GENERATOR PURSUANT TO FBC-R301.2 AND AS REQUIRED BY THE
 GENERATOR PAD ENGINEERING THAT WAS SUBMITTED.
  
 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 16:40 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 15:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 16:40 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-14 Cont ID  
Sent By dbattles Date 2020-07-14 Time 14:36 Rev Time 0.00
Received By dbattles Date 2020-07-14 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-01 Cont ID  
Sent By shill Date 2020-07-01 Time 16:51 Rev Time 0.00
Received By shill Date 2020-06-11 Time 16:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 15:57 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 15:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-14 Cont ID  
Sent By dbattles Date 2020-07-14 Time 14:36 Rev Time 0.00
Received By dbattles Date 2020-07-14 Time 14:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-24 Cont ID  
Sent By rmcdouga Date 2020-06-24 Time 15:54 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 15:48 Sent To  
Notes
2020-06-24 15:57:19PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DESIGN PROFESSIONALS
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  
  
2020-06-24 15:53:45THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-07-01 Time   Rev Time  
Received By   Date 2020-07-01 Time   Sent To I
Notes
***NONE***