Plan Review Details - Permit 20060023
Plan Review Stops For Permit 20060023
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2020-07-23 Time 11:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2020-06-22 Cont ID  
Sent By rmcdouga Date 2020-06-22 Time 12:04 Rev Time 0.00
Received By rmcdouga Date 2020-06-22 Time 12:04 Sent To  
Notes
2020-06-22 12:21:08PLAN
 REVIEW COMMENTS
 5TH REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - PREVIOUS COMMENTS WERE NOT
 ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (REPEAT COMMENT. THE WINDLOAD CALCULATIONS ARE NOT
 DIGITALLY SIGNED.) SUBMIT REQUIRED COMPONENT AND
 CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE
 BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE
 DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE
 ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE
 SUBMITTED. FS 471 & FAC 61G15 THESE DOCUMENTS ARE
 SUBMITTED ELECTRONICALLY, THEREFORE, THE ENGINEER IS
 REQUIRED TO DIGITALLY SIGN THE DESIGN PRESSURE CHART.
  
 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS
 SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS
 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107
 ( NEW NOTE: SEE PAGES 28 AND 29 OF THE MULLION PRODUCT
 APPROVAL. THIS IS RECTANGULAR LOADING. THE MULL LENGTH
 IS 62 INCHES. THE OPENING WIDTH IS 36 INCHES + 36
 INCHES + THE MULL WIDTH = 72 + MULL WIDTH. IF THE EXACT
 SIZES ARE NOT LISTED IN THE CHART USE THE NEXT HIGHEST.
 THE MULL THAT IS USED IS REQUIRED TO HAVE DESIGN
 PRESSURES THAT ARE HIGHER THAN THE PRESSURES REQUIRED
 FOR THE OPENING. IF THE REQUIRED OPENING PRESSURES ARE
 +65.9 PSF, -120.8 PSF THEN THE MULLION DESIGN PRESSURES
 ARE REQUIRED TO BE GREATER THAN THAT.)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-06-19 Cont ID  
Sent By rmcdouga Date 2020-06-19 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2020-06-19 Time 08:29 Sent To  
Notes
2020-06-19 08:45:43PLAN
 REVIEW COMMENTS
 4TH REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - PREVIOUS COMMENTS WERE NOT
 ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (REPEAT COMMENT. THE WINDLOAD CALCULATIONS ARE NOT
 DIGITALLY SIGNED.) SUBMIT REQUIRED COMPONENT AND
 CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE
 BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE
 DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE
 ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE
 SUBMITTED. FS 471 & FAC 61G15 THESE DOCUMENTS ARE
 SUBMITTED ELECTRONICALLY, THEREFORE, THE ENGINEER IS
 REQUIRED TO DIGITALLY SIGN THE DESIGN PRESSURE CHART.
  
 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS
 SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS
 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107
 ( NEW NOTE: SEE PAGES 28 AND 29 OF THE MULLION PRODUCT
 APPROVAL. THIS IS RECTANGULAR LOADING. THE MULL LENGTH
 IS 62 INCHES. THE OPENING WIDTH IS 36 INCHES + 36
 INCHES + THE MULL WIDTH = 72 + MULL WIDTH. IF THE EXACT
 SIZES ARE NOT LISTED IN THE CHART USE THE NEXT HIGHEST.
 THE MULL THAT IS USED IS REQUIRED TO HAVE DESIGN
 PRESSURES THAT ARE HIGHER THAN THE PRESSURES REQUIRED
 FOR THE OPENING. IF THE REQUIRED OPENING PRESSURES ARE
 +65.9 PSF, -120.8 PSF THEN THE MULLION DESIGN PRESSURES
 ARE REQUIRED TO BE GREATER THAN THAT.)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-06-08 Cont ID  
Sent By rmcdouga Date 2020-06-08 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2020-06-08 Time 08:56 Sent To  
Notes
2020-06-08 09:14:19PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - PREVIOUS COMMENTS WERE NOT
 ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT REQUIRED COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE OPENINGS THAT HAVE BEEN PREPARED BY A
 FLORIDA LICENSED ENGINEER. THE DOCUMENTS ARE REQUIRED
 TO BE DIGITALLY SIGNED BY THE ENGINEER IF SUBMITTED
 ELECTRONICALLY AND THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE IF PAPER DOCUMENTS ARE SUBMITTED. FS 471 &
 FAC 61G15 THESE DOCUMENTS ARE SUBMITTED ELECTRONICALLY,
 THEREFORE, THE ENGINEER IS REQUIRED TO DIGITALLY SIGN
 THE DESIGN PRESSURE CHART.
  
 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS
 SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS
 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107
  
 3) SUBMIT A RESPONSE LETTER SPECIFYING HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-04 Cont ID  
Sent By rmcdouga Date 2020-06-04 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2020-06-04 Time 07:55 Sent To  
Notes
2020-06-04 07:55:05PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - PREVIOUS COMMENTS WERE NOT
 ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT REQUIRED COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE OPENINGS THAT HAVE BEEN PREPARED BY A
 FLORIDA LICENSED ENGINEER. THE DOCUMENTS ARE REQUIRED
 TO BE DIGITALLY SIGNED BY THE ENGINEER IF SUBMITTED
 ELECTRONICALLY AND THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE IF PAPER DOCUMENTS ARE SUBMITTED. FS 471 &
 FAC 61G15
  
 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS
 SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS
 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 11:35 Rev Time  
Received By rmcdouga Date 2020-06-02 Time   Sent To  
Notes
2020-06-02 11:35:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT REQUIRED COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE OPENINGS THAT HAVE BEEN PREPARED BY A
 FLORIDA LICENSED ENGINEER. THE DOCUMENTS ARE REQUIRED
 TO BE DIGITALLY SIGNED BY THE ENGINEER IF SUBMITTED
 ELECTRONICALLY AND THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE IF PAPER DOCUMENTS ARE SUBMITTED. FS 471 &
 FAC 61G15
  
 2) THE DESIGN PRESSURE CAPACITY FOR THE MULLION THAT IS
 SPECIFIED ON SHEET 5 OF 25 OF THE PRODUCT APPROVAL IS
 35.3 PSF. THIS IS TOO LOW. PLEASE REVISE. FBC 107

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 11:53 Rev Time 0.00
Received By rmcdouga Date 2020-07-15 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-06-22 Cont ID  
Sent By rmcdouga Date 2020-06-22 Time 12:56 Rev Time 0.00
Received By rmcdouga Date 2020-06-19 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-19 Cont ID  
Sent By rmcdouga Date 2020-06-19 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2020-06-16 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-08 Cont ID  
Sent By rmcdouga Date 2020-06-08 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2020-06-04 Time 13:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-04 Cont ID  
Sent By rmcdouga Date 2020-06-04 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2020-06-02 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2020-06-01 Time 16:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 11:53 Rev Time 0.00
Received By rmcdouga Date 2020-07-23 Time 11:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2020-06-22 Cont ID  
Sent By rmcdouga Date 2020-06-22 Time 12:04 Rev Time 0.00
Received By rmcdouga Date 2020-06-22 Time 12:04 Sent To  
Notes
2020-06-22 12:55:59THE ELECTRONICALLY SUBMITTED WINDLOAD CHART FROM THE
 ENGINEER IS NOT DIGITALLY SIGNED. FS471 & FAC61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-06-19 Cont ID  
Sent By rmcdouga Date 2020-06-19 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2020-06-19 Time 08:46 Sent To  
Notes
2020-06-19 08:47:25THE ELECTRONICALLY SUBMITTED WINDLOAD CHART FROM THE
 ENGINEER IS NOT DIGITALLY SIGNED. FS471 & FAC61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-06-08 Cont ID  
Sent By rmcdouga Date 2020-06-08 Time 09:08 Rev Time 0.00
Received By rmcdouga Date 2020-06-08 Time 09:08 Sent To  
Notes
2020-06-08 09:09:27SIGNED AND SEALED WINDLOAD CALCULATIONS ARE REQUIRED
 FOR THIS HIGH RISE IN EXPOSURE D. THE DOCUMENTS ARE
 REQUIRED TO BE DIGITALLY SIGNED BY THE ENGINEER IF
 SUBMITTED ELECTRONICALLY AND THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE IS REQUIRED IF PAPER DOCUMENTS
 ARE SUBMITTED. FS 471 & FAC 61G15
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-06-04 Cont ID  
Sent By rmcdouga Date 2020-06-04 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2020-06-04 Time 07:55 Sent To  
Notes
2020-06-04 07:55:35SIGNED AND SEALED WINDLOAD CALCULATIONS ARE REQUIRED
 FOR THIS HIGH RISE IN EXPOSURE D. THE DOCUMENTS ARE
 REQUIRED TO BE DIGITALLY SIGNED BY THE ENGINEER IF
 SUBMITTED ELECTRONICALLY AND THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE IS REQUIRED IF PAPER DOCUMENTS
 ARE SUBMITTED. FS 471 & FAC 61G15
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2020-06-02 Time 11:35 Sent To  
Notes
2020-06-02 11:36:49SIGNED AND SEALED WINDLOAD CALCULATIONS ARE REQUIRED
 FOR THIS HIGH RISE IN EXPOSURE D. THE DOCUMENTS ARE
 REQUIRED TO BE DIGITALLY SIGNED BY THE ENGINEER IF
 SUBMITTED ELECTRONICALLY AND THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE IS REQUIRED IF PAPER DOCUMENTS
 ARE SUBMITTED. FS 471 & FAC 61G15
  