Plan Review Details - Permit 20051006
Plan Review Stops For Permit 20051006
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-10 Cont ID  
Sent By jleahy Date 2020-09-10 Time 12:40 Rev Time 0.00
Received By jleahy Date 2020-09-10 Time 12:40 Sent To  
Notes
2020-09-10 12:41:09DID CONCRETE SLAB AS PART OF THE ELECTRICAL REVIEW
 JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By rmcdouga Date 2020-06-09 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2020-06-09 Time 16:05 Sent To  
Notes
2020-06-09 16:06:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ONLY PART OF THE GENERATOR PAD DRAWING WAS UPLOADED.
 THE ENTIRE DOCUMENT IS REQUIRED. FBC 107

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-19 Cont ID  
Sent By jleahy Date 2020-06-19 Time 12:50 Rev Time 0.00
Received By jleahy Date 2020-06-19 Time 08:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-08-31 Cont ID  
Sent By medwards Date 2020-08-31 Time 13:53 Rev Time 0.00
Received By medwards Date 2020-08-31 Time 13:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-18 Cont ID  
Sent By medwards Date 2020-06-18 Time 14:38 Rev Time 0.00
Received By medwards Date 2020-06-18 Time 14:00 Sent To  
Notes
2020-06-18 14:38:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMPLETE CONCRETE PAD DESIGN, THE
 ONE IN THIS SUBMITTAL WAS CUT OFF AND CAN ONLY SEE HALF
 OF THE DOCUMENT. FBC FS 107.2.1
  
 2) PLEASE SHOW THE SIZE OF THE PIPE AND THE MATERIAL OF
 THE PIPE LEAVING THE METER AND SUPPLYING THE GAS LOAD
 TO THE HOUSE. FBC FS 107.2.1
  
 3) IS THE EXISTING GAS SERVICE A 2 PSI SYSTEM? IF SO,
 PLEASE SHOW THE MP REGULATOR FOR THE APPLIANCES. FBC FS
 107.2.1
  
 4) WHAT TYPE OF CONNECTION IS BEING USED BETWEEN THE PE
 PIPING AND THE GENERATOR? IF A HOSE IS USED PLEASE
 PROVIDE THE SPECS AND IDENTIFY THE HOSE USED. PLEASE
 SHOW PRESSURE DROP.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-10 Cont ID  
Sent By jleahy Date 2020-09-10 Time 12:41 Rev Time 0.00
Received By jleahy Date 2020-08-24 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-19 Cont ID  
Sent By jleahy Date 2020-06-19 Time 12:50 Rev Time 0.00
Received By jleahy Date 2020-06-01 Time 15:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-31 Cont ID  
Sent By medwards Date 2020-08-31 Time 13:55 Rev Time 0.00
Received By medwards Date 2020-08-31 Time 13:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-18 Cont ID  
Sent By medwards Date 2020-06-18 Time 14:38 Rev Time 0.00
Received By medwards Date 2020-06-18 Time 14:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-10 Cont ID  
Sent By jleahy Date 2020-09-10 Time 13:54 Rev Time 0.00
Received By jleahy Date 2020-09-10 Time 13:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-31 Cont ID  
Sent By medwards Date 2020-08-31 Time 13:54 Rev Time 0.00
Received By medwards Date 2020-08-31 Time 13:54 Sent To  
Notes
2020-08-31 13:55:08PLEASE SEE ORIGINAL SIGNATURE REVIEW COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By rmcdouga Date 2020-06-09 Time 16:06 Rev Time 0.00
Received By rmcdouga Date 2020-06-09 Time 16:06 Sent To  
Notes
2020-06-09 16:07:53THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE
 GENERATOR PAD DRAWINGS. FS 741 & FAC 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2020-06-05 Cont ID  
Sent By rthermid Date 2020-06-05 Time   Rev Time  
Received By rthermid Date 2020-06-05 Time   Sent To I
Notes
***NONE***