Plan Review Stops For Permit 20051006 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-09-10 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-09-10 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-09-10 |
Time |
12:40 |
Sent To |
|
|
Notes |
2020-09-10 12:41:09 | DID CONCRETE SLAB AS PART OF THE ELECTRICAL REVIEW | | JLEAHY |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-06-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-06-09 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-06-09 |
Time |
16:05 |
Sent To |
|
|
Notes |
2020-06-09 16:06:06 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) ONLY PART OF THE GENERATOR PAD DRAWING WAS UPLOADED. | | THE ENTIRE DOCUMENT IS REQUIRED. FBC 107 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-06-19 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-06-19 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-06-19 |
Time |
08:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2020-08-31 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-08-31 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-08-31 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-06-18 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-06-18 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-06-18 |
Time |
14:00 |
Sent To |
|
|
Notes |
2020-06-18 14:38:43 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT | | | | CODES IN EFFECT: | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE A COMPLETE CONCRETE PAD DESIGN, THE | | ONE IN THIS SUBMITTAL WAS CUT OFF AND CAN ONLY SEE HALF | | OF THE DOCUMENT. FBC FS 107.2.1 | | | | 2) PLEASE SHOW THE SIZE OF THE PIPE AND THE MATERIAL OF | | THE PIPE LEAVING THE METER AND SUPPLYING THE GAS LOAD | | TO THE HOUSE. FBC FS 107.2.1 | | | | 3) IS THE EXISTING GAS SERVICE A 2 PSI SYSTEM? IF SO, | | PLEASE SHOW THE MP REGULATOR FOR THE APPLIANCES. FBC FS | | 107.2.1 | | | | 4) WHAT TYPE OF CONNECTION IS BEING USED BETWEEN THE PE | | PIPING AND THE GENERATOR? IF A HOSE IS USED PLEASE | | PROVIDE THE SPECS AND IDENTIFY THE HOSE USED. PLEASE | | SHOW PRESSURE DROP. | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-09-10 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-09-10 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-08-24 |
Time |
15:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-06-19 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-06-19 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-06-01 |
Time |
15:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2020-08-31 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-08-31 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-08-31 |
Time |
13:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-06-18 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-06-18 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-06-18 |
Time |
14:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-09-10 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-09-10 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-09-10 |
Time |
13:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-08-31 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-08-31 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-08-31 |
Time |
13:54 |
Sent To |
|
|
Notes |
2020-08-31 13:55:08 | PLEASE SEE ORIGINAL SIGNATURE REVIEW COMMENTS. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-06-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-06-09 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-06-09 |
Time |
16:06 |
Sent To |
|
|
Notes |
2020-06-09 16:07:53 | THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE | | GENERATOR PAD DRAWINGS. FS 741 & FAC 61G15 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-06-05 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2020-06-05 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2020-06-05 |
Time |
|
Sent To |
I |
|
Notes |
|
|