Plan Review Stops For Permit 20050996 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-09-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-09-05 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-09-05 |
Time |
11:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-08-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-08-03 |
Time |
12:02 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-08-03 |
Time |
12:02 |
Sent To |
|
|
Notes |
2020-08-03 12:10:25 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1A) THE GENERATOR PAD THAT WAS UPLOADED ON 7/22 IS NOT | | FOR THE 27 KW, MODEL RG027 GENERATOR. THE ONE THAT WAS | | UPLOADED THE FIRST TIME IS THE CORRECT ONE. IT WAS JUST | | NOT THE COMPLETE SHEET. PART OF THE SHEET WAS CUT OFF. | | FBC 107 ALSO SEE SIGNATURE COMMENT. | | | | ORIGINAL COMMENT: 1) ONLY PART OF THE GENERATOR PAD | | DRAWING WAS UPLOADED. THE ENTIRE DOCUMENT IS REQUIRED. | | FBC 107 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-06-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-06-09 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-06-09 |
Time |
16:10 |
Sent To |
|
|
Notes |
2020-06-09 16:10:37 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) ONLY PART OF THE GENERATOR PAD DRAWING WAS UPLOADED. | | THE ENTIRE DOCUMENT IS REQUIRED. FBC 107 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-06-18 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-06-18 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-06-18 |
Time |
13:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2020-08-26 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-08-26 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-08-26 |
Time |
16:15 |
Sent To |
|
|
Notes |
2020-08-26 16:30:56 | 08/26/20 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2020-07-30 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-07-30 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-07-30 |
Time |
16:59 |
Sent To |
|
|
Notes |
2020-07-30 16:59:42 | 07/30/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF | | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. | | | | 2. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT | | INSTALLED IF INSIDE GENERATOR MAKE NOTE PER THE 2017 | | FBC RES. SEC. G2419.2. | | | | 3. PLEASE SHOW THE SHUTOFF VALVE ON GAS ISOMERIC PER | | THE 2017 FBC FG SEC. 409.4 OR 2017 FBC RES. SEC. | | G2401.1.3. | | | | 4. PLEASE SHOW AND LABEL THE REGULATOR ON GAS ISOMERIC | | PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC RES. SEC. | | G2401.1.3. | | | | 5. PLEASE SHOW THE PE LINES ON THE SIDE OF EXIT ON THE | | METER NOT THE INLET PER THE WPB AMENDMENTS TO THE FBC | | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 6. THE GENERATOR ON THE ISOMETRIC SAYS 27 KW, PLEASE | | CHANGE TO BTU'S AND BELOW YOU HAVE 330 BTU'S WHICH AT | | FULL LOAD A 27 KW SHOULD BE 359 BTU'S SO RECALCULATE | | AND CHANGE TOTAL BTU'S PER THE WPB AMENDMENTS TO THE | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | [email protected] | | 561-701-6437 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-06-12 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-06-12 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-06-12 |
Time |
14:25 |
Sent To |
|
|
Notes |
2020-06-12 14:55:47 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20050996 | | | | CODES IN EFFECT: | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) . THIS SUBMISSION DOES NOT SHOW ANY EXISTING GAS | | LINE FOR THIS PROJECT. PLEASE PROVIDE A COMPLETE GAS | | LINE DIAGRAM SHOWING ALL THE EXISTING APPLIANCES AND | | GAS LINES. INCLUDE PIPE MATERIAL AND PIPE SIZES ALONG | | WITH ANY REGULATORS AND GAS PRESSURES FOR THE ENTIRE | | SYSTEM. PLEASE SHOW A DETAIL OF THE CONNECTION OF THE | | NEW GAS LINE FOR THE GENERATOR TO THE EXISTING GAS | | LINE. | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-09-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-09-05 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-08-21 |
Time |
09:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-08-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-08-03 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-07-22 |
Time |
16:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-06-18 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-06-18 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-06-01 |
Time |
15:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2020-08-26 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-08-26 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-08-26 |
Time |
16:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2020-07-30 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-07-30 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-07-30 |
Time |
16:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-06-12 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-06-12 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-06-12 |
Time |
14:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-09-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-09-05 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-09-05 |
Time |
11:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-08-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-08-03 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-08-03 |
Time |
12:10 |
Sent To |
|
|
Notes |
2020-08-03 12:13:18 | THE PREFAB GENERATOR PAD DRAWINGS THAT WERE SUBMITTED | | ELECTRONICALLY DO NOT HAVE THE ENGINEER'S DIGITAL | | SIGNATURE. THE CONTRACTOR HAS THE OPTION TO SUBMIT | | ELECTRONIC GENERATOR PAD DRAWINGS WITH THE ENGINEER'S | | DIGITAL SIGNATURE OR SUBMIT PAPER DRAWINGS AT THE CITY | | BUILDING DEPARTMENT WITH THE ENGINEER'S ORIGINAL | | HANDWRITTEN SIGNATURE AND SEAL FOR REVIEW AND APPROVAL | | BEFORE THE PERMIT CAN BE ISSUED. FS 471 AND FAC 61G 15. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-06-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-06-09 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-06-09 |
Time |
16:10 |
Sent To |
|
|
Notes |
2020-06-09 16:12:01 | THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE | | GENERATOR PAD DRAWING. FS471 & FAC 61G15 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-06-11 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2020-06-11 |
Time |
|
Rev Time |
|
Received By |
kalexand |
Date |
2020-06-11 |
Time |
|
Sent To |
I |
|
Notes |
|
|