Plan Review Details - Permit 20050956
Plan Review Stops For Permit 20050956
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2020-07-23 Time 13:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-06-08 Cont ID  
Sent By rmcdouga Date 2020-06-08 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2020-06-08 Time 16:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By cthroop Date 2020-07-24 Time 16:16 Rev Time 0.00
Received By cthroop Date 2020-07-24 Time 15:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-11 Cont ID  
Sent By jpearson Date 2020-06-11 Time 14:11 Rev Time 0.00
Received By jpearson Date 2020-06-11 Time 10:10 Sent To  
Notes
2020-06-11 14:11:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW THAT IS DESIGNED
 BY AND SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR DESIGNED BY AND SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. A DIGITAL PLAN
 REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY,
 A SIGNED OR SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO
 THE BUILDING DEPARTMENT WHEN ALL TRADES ARE APPROVED.
 WPB FBC 107.1; FS 471/481, FS 471.003(2)(H); 471.025;
 WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By cthroop Date 2020-07-24 Time 16:08 Rev Time 0.00
Received By cthroop Date 2020-07-24 Time 15:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-12 Cont ID  
Sent By cthroop Date 2020-06-12 Time 11:50 Rev Time 0.00
Received By cthroop Date 2020-06-12 Time 11:30 Sent To  
Notes
2020-06-12 11:55:27PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SEPERATE GAS PERMIT REQUIRED.
 PERMITS
 105.1 REQUIRED.
  
 2. PROVIDE GAS PLAN.
 107.2 CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE GAS RISER DIAGRAHM.
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-R SEC.
 G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE
 USED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.
  
 9. SUBMIT A COPY OF THE MANUFACTURER?S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC-RES. SEC.G2408.1.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-24 Cont ID  
Sent By cthroop Date 2020-07-24 Time 16:19 Rev Time 0.00
Received By cthroop Date 2020-07-14 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-12 Cont ID  
Sent By cthroop Date 2020-06-12 Time 11:55 Rev Time 0.00
Received By cthroop Date 2020-06-01 Time 16:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By medwards Date 2020-07-20 Time 13:43 Rev Time 0.00
Received By medwards Date 2020-07-20 Time 13:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-06-08 Cont ID  
Sent By medwards Date 2020-06-08 Time 13:46 Rev Time 0.00
Received By medwards Date 2020-06-08 Time 13:19 Sent To  
Notes
2020-06-08 13:46:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050956
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UPLOAD THE PERMIT APPLICATIONS FOR THIS
 PROJECT. FBC FS 107.2.1
  
 2) PLEASE PROVIDE THE SPECS FOR THE RANGE AND SHOW THAT
 IT IS SUITED FOR A RESIDENTIAL INSTALLATION. FBC RES
 M1901.2
  
 3) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR THIS
 RANGE IN THIS SPACE. FBC RES G2407.5
  
 4) PLEASE PROVIDE HOOD SPECS FOR THE HOOD RECOMMENDED
 FOR THIS RANGE. FBC RES M1503.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By cthroop Date 2020-07-24 Time 16:18 Rev Time 0.00
Received By cthroop Date 2020-07-24 Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-06-12 Cont ID  
Sent By cthroop Date 2020-06-12 Time 11:50 Rev Time 0.00
Received By cthroop Date 2020-06-12 Time 11:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By medwards Date 2020-07-20 Time 13:46 Rev Time 0.00
Received By medwards Date 2020-07-20 Time 13:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-08 Cont ID  
Sent By medwards Date 2020-06-08 Time 13:49 Rev Time 0.00
Received By medwards Date 2020-06-08 Time 13:46 Sent To  
Notes
***NONE***