2020-06-04 09:03:03 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| RE E3606.3 |
| 2.A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| RE E3607.3 |
| 3.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| 4.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| 5.VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 |
| 6.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE |
| EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC |
| 107.2.1 |
| 7.A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| FEEDER OR BRANCH CIRCUIT. NEC 225.30 |
| 8.PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| CIRCUIT. NEC 250.32; FBC RE3607.3 |
| 9.ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB |
| FBC 107.2.1; NEC 230.2; FBC RE E3601.2 |
| 10.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC |
| 107.2.1 |
| 11.NOTES AND SCOPE ON PLANS CONFLICT |
| 12.SHOW LOCATIONS OF ALL ELECTRICAL EQUIPMENT |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |