Plan Review Details - Permit 20050859
Plan Review Stops For Permit 20050859
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-19 Cont ID  
Sent By rmcdouga Date 2020-06-19 Time 09:29 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2020-06-02 Time 09:58 Sent To  
Notes
2020-06-02 10:56:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DRAWING DOES NOT HAVE THE ADDRESS OF THE PROJECT
 AND DOES NOT SPECIFY THE REQUIRED DESIGN PRESSURES. THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE IS
 REQUIRED ON THE DRAWING. FBC 107
  
 2) THE TABLES IN THE PRODUCT APPROVALS FOR THE SINGLE
 HUNG WINDOW AND THE FIXED GLASS WINDOW HAVE NOT BEEN
 MARKED TO SPECIFY WHICH SIZE, GLASS TYPE AND DESIGN
 PRESSURES ARE APPLICABLE. FBC 107
  
 3) THE ITEMS THAT WERE MARKED IN THE TABLES FOR THE
 MULLION HAD THE WRONG OPENING HEIGHT AND DESIGN
 PRESSURES. I MARKEDUP THE CORRECT ONES. FBC 107

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-19 Cont ID  
Sent By rmcdouga Date 2020-06-19 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2020-06-16 Time 15:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2020-06-01 Time 08:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-06-19 Cont ID  
Sent By rmcdouga Date 2020-06-19 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2020-06-19 Time 09:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2020-06-02 Time 09:58 Sent To  
Notes
2020-06-02 10:05:22THE WINDLOAD CHART FROM THE ENGINEER IS REQUIRED TO
 HAVE AN ORIGINAL HANDWRITTEN SIGNATURE IF A PAPER
 DOCUMENT IS SUBMITTED AND A DIGITAL SIGNATURE IS
 REQUIRED FOR ELECTRONICALLY SUBMITTED DOCUMENTS. FS 471
 & FAC 61G15