Plan Review Details - Permit 20050839
Plan Review Stops For Permit 20050839
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-12-03 Cont ID  
Sent By rmcphers Date 2020-12-03 Time 13:29 Rev Time 0.00
Received By rmcphers Date 2020-12-03 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-11-13 Cont ID  
Sent By rmcphers Date 2020-11-13 Time 10:47 Rev Time 0.00
Received By rmcphers Date 2020-11-13 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 12:14 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 11:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-15 Cont ID  
Sent By rmcphers Date 2020-09-15 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2020-09-15 Time 14:38 Sent To  
Notes
2020-09-15 14:57:09SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CANNOT USE A "NAMI" APPROVED CERTIFICATION FOR THE
 SINGLE HUNG WINDOWS. MUST USE A MIAMI DADE OR FLORIDA
 STATE APPROVED PRODUCT APPROVAL. PLEASE PROVIDE
 COMPLETE (FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVALS FOR THE NEW EXTERIOR WINDOWS, ROOFING SYSTEM
 TO BE USED ETC.. PRODUCT APPROVALS NEED TO BE REVIEWED
 AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD
 (ARCHITECT).
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING SYSTEM TO BE USED.
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND
 SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY
 REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE
 PRODUCT APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By rmcphers Date 2020-07-22 Time 12:40 Rev Time 0.00
Received By rmcphers Date 2020-07-22 Time 11:10 Sent To  
Notes
2020-07-22 12:40:17SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS,
 ROOFING SYSTEM TO BE USED ETC.. PRODUCT APPROVALS NEED
 TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD (ARCHITECT).
 2) PLEASE PROVIDE A SIGNED AND SEALED SURVEY/SITE PLAN
 SHOWING THE BUILDING SETBACKS, EASEMENTS, LOT DRAINAGE
 ETC.
 3) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING SYSTEM TO BE USED.
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND
 SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY
 REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE
 PRODUCT APPROVAL.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-22 Cont ID  
Sent By fgiaquin Date 2020-07-22 Time 19:50 Rev Time 0.00
Received By fgiaquin Date 2020-07-22 Time 19:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-01-14 Cont ID  
Sent By jgomez Date 2021-01-14 Time 09:41 Rev Time 0.00
Received By jgomez Date 2021-01-06 Time 10:17 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-12-03 Cont ID  
Sent By rmcphers Date 2020-12-03 Time 13:30 Rev Time 0.00
Received By rmcphers Date 2020-11-23 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-11-13 Cont ID  
Sent By rmcphers Date 2020-11-13 Time 10:48 Rev Time 0.00
Received By rmcphers Date 2020-11-03 Time 16:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2020-10-20 Time 13:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-18 Cont ID  
Sent By shill Date 2020-09-18 Time 06:03 Rev Time 0.00
Received By shill Date 2020-09-08 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-10 Cont ID  
Sent By cpuell Date 2020-08-10 Time 12:56 Rev Time 0.00
Received By cpuell Date 2020-07-01 Time 08:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-02-04 Cont ID  
Sent By lmarchan Date 2021-02-04 Time 11:40 Rev Time 0.00
Received By lmarchan Date 2021-01-19 Time 08:44 Sent To  
Notes
2021-02-04 11:40:312/4/21 NO FEES DUE PER IMPACT OFFICE. LEM
2021-01-19 22:46:4501/19/21 READY TO BE REVIWED. EMAILED PBC IMPACT FEES
 OFFICE. QUESTIONNAIRE UPLOADED. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By rmcphers Date 2020-07-22 Time 12:40 Rev Time 0.00
Received By rmcphers Date 2020-07-22 Time 12:40 Sent To  
Notes
2020-07-22 12:41:21PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-10-28 Cont ID  
Sent By medwards Date 2020-10-28 Time 07:17 Rev Time 0.00
Received By medwards Date 2020-10-28 Time 07:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-09-16 Cont ID  
Sent By medwards Date 2020-09-16 Time 08:31 Rev Time 0.00
Received By medwards Date 2020-09-16 Time 07:25 Sent To  
Notes
2020-09-16 08:29:392ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20050839
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW RETURN AIR PATH FOR THE PROPOSED FAMILY
 ROOM. FBC FS 107.2.1
  
 2) PLEASE SHOW THE RETURN AIR IS A BALANCED. MAKE SURE
 THE RETURN AIR DUCTS ARE 1 ? TIMES THE CROSS SECTIONAL
 AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE
 ROOM. FBC RES M1602.3
  
 3) PLEASE PROVIDE DISTANCE OF RETURN AIR GRILL TO
 COOKING APPLIANCE IN THE KITCHEN. FBC RES M1602.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By medwards Date 2020-07-15 Time 09:34 Rev Time 0.00
Received By medwards Date 2020-07-15 Time 09:03 Sent To  
Notes
2020-07-15 09:34:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050839
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PLEASE PROVIDE THE ENERGY CALCS AND THE
 MANUAL J FOR THE NEW MECHANICAL SYSTEM. FBC EC
 101.5.1.1.2
  
 2) PLEASE SHOW RETURN AIR PATH FOR THE PROPOSED FAMILY
 ROOM. FBC RES M1602.3
  
 3) PLEASE SHOW TERMINATION FOR THE DRYER DUCT. PLEASE
 PROVIDE THE DEVELOPED LENGTH OF THE DRYER DUCT. FBC FS
 107.2.1
  
 4) PLEASE PROVIDE INFORMATION FOR THE BATH EXHAUST FANS
 AND THE LOCATION OF EXTERIOR TERMINATION. FBC FS
 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-10-21 Cont ID  
Sent By ccole Date 2020-10-21 Time 09:18 Rev Time 0.00
Received By ccole Date 2020-10-21 Time 07:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-09-09 Cont ID  
Sent By ccole Date 2020-09-09 Time 11:00 Rev Time 0.00
Received By ccole Date 2020-09-09 Time 09:55 Sent To  
Notes
2020-09-09 11:04:352ND REVIEW FBC-2017 RES.
 PERMIT-20050839
 9/9/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A5.0: COMMENT #3 FROM THE 1ST REVIEW STILL
 EXISTS. THE REQUESTED SPECS FOR THE RHEEM TANKLESS
 WATER HEATER WERE NOT SUBMITTED. REVIEW OF THE SPECS ON
 THE RHEEM WEBSITE INDICATE THE SELECTED RETEX-13 IS
 UNDERSIZED AND WILL NOT PROVIDE ADEQUATE HOT WATER TO
 THE FIXTURES. ON PAGE 2 OF THE MANUFACTURER'S SPECS THE
 SIZING GUIDE CHART INDICATES THE UNIT WILL PROVIDE
 MAXIMUM 2.0 GPM FLOW WITH AN INLET WATER TEMPERATURE OF
 70 DEGREES F. LIKEWISE THE TEMPERATURE RISE CHART ON
 PAGE 1 INDICATES 2.0 GPM FLOW FOR A TEMPERATURE RISE OF
 44 DEGREES F. PLEASE REFER TO TABLE P2903.1 FBC RES.
 FOR REQUIRED GPM FLOW RATES AND PRESSURES AT FIXTURE
 OUTLET DISCHARGES, AND THE RHEEM RETEX AVERAGE GPM
 USAGE CHART ON PAGE 1 OF THE SPECS- PLEASE SELECT A
 HEATER WITH ADEQUATE CAPACITY.
  
 2) A5.0: PLEASE NOTE THAT THE DISTANCE FROM THE SHOWER
 TRAP TO THE LAVATORY VENT IN THE MASTER BATH SHALL NOT
 EXCEED 8 FT PER TABLE P3105.1 FBC RES.
  
 3) A1.0: PLEASE NOTE THAT SHOWER WIDTH IS MEASURED FROM
 THE FINISHED INTERIOR AT A HEIGHT EQUAL TO THE TOP OF
 THE THRESHOLD AND AT A POINT TANGENT TO ITS CENTERLINE
 AND SHALL BE CONTINUED TO A HEIGHT OF NOT LESS THAN 70
 INCHES ABOVE THE SHOWER DRAIN OUTLET- SECTION P2708.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By ccole Date 2020-07-17 Time 16:52 Rev Time 0.00
Received By ccole Date 2020-07-17 Time 15:20 Sent To  
Notes
2020-07-17 16:53:411ST REVIEW FBC-2017 RES.
 PERMIT-20050839
 7/17/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.0: PROVIDE THE WIDTH OF THE SHOWER IN THE
 COMMON BATHROOM- SECTION P2708.1 FBC RES, AND THE
 FIXTURE CLEARANCE WIDTHS FOR THE TOILETS PER FIGURE
 R307.1 FBC RES.
  
 2) A5.0: PROVIDE A SHOWER PAN DETAIL- SECTIONS P2709.1
 & P2709.2 FBC RES.
  
 3) A5.0: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR
 THE NEW TANKLESS WATER HEATER AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION P2801.3 & TABLE C404.2 FBC EC.
  
 4) A5.0: PROVIDE A WATER RISER DRAWING SHOWING THE
 PIPING RUNS TO AND FROM THE NEW WATER HEATER, POINTS OF
 CONNECTION TO THE EXISTING SUPPLY PIPES, AND PIPING
 RUNS TO THE NEW FIXTURES- SECTION 107.3.5.3 WPB. PLEASE
 INCLUDE THE SUPPLY LINES TO THE DISHWASHER AND
 REFRIGERATOR ICE MAKER. INDICATE HOW THE DISHWASHER
 SUPPLY LINE WILL BE PROTECTED FROM BACKFLOW PER
 SECTIONS 2717.1 AND 2902.1 FBC RES, AND PROVIDE A WATER
 HAMMER ARRESTOR AND BACKFLOW PREVENTER FOR THE SUPPLY
 LINE TO THE ICE MAKER- SEE SECTIONS P2902.1 AND
 P2903.5.
  
 5) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2021-01-14 Cont ID  
Sent By jgomez Date 2021-01-14 Time 09:37 Rev Time 0.00
Received By jgomez Date 2021-01-13 Time 11:26 Sent To  
Notes
2021-01-14 09:38:18FLAT ROOF NOA 20-0110.11 SYSTEM TYPE E(17) ON PAGE 40
 OF 48.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2020-12-03 Cont ID  
Sent By rmcphers Date 2020-12-03 Time 13:29 Rev Time 0.00
Received By rmcphers Date 2020-12-03 Time 13:29 Sent To  
Notes
2020-12-03 13:30:38ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
 5TH REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL( SUCH AS (E1, E2, E3 ETC)) - IF NEEDED PLEASE
 PROVIDE SIGNED AND SEALED ADDITIONAL ATTACHMENT DETAILS
 FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND
 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE - SEE
 GENERAL LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL.
 ---- OR IN WRITING ASK FOR THE ROOFING TO BE A DEFERRED
 PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2020-11-13 Cont ID  
Sent By rmcphers Date 2020-11-13 Time 10:47 Rev Time 0.00
Received By rmcphers Date 2020-11-13 Time 10:47 Sent To  
Notes
2020-11-13 10:48:29ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
 4TH REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL( SUCH AS (E1, E2, E3 ETC)) - IF NEEDED PLEASE
 PROVIDE SIGNED AND SEALED ADDITIONAL ATTACHMENT DETAILS
 FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND
 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE - SEE
 GENERAL LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL.
 ---- OR IN WRITING ASK FOR THE ROOFING TO BE A DEFERRED
 PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 12:18 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 12:18 Sent To  
Notes
2020-10-29 12:34:19ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL( SUCH AS (E1, E2, E3 ETC)) - IF NEEDED PLEASE
 PROVIDE SIGNED AND SEALED ADDITIONAL ATTACHMENT DETAILS
 FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND
 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE - SEE
 GENERAL LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL.
 ---- OR IN WRITING ASK FOR THE ROOFING TO BE A DEFERRED
 PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-09-15 Cont ID  
Sent By rmcphers Date 2020-09-15 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2020-09-15 Time 14:57 Sent To  
Notes
2020-09-15 14:57:53SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By rmcphers Date 2020-07-22 Time 12:41 Rev Time 0.00
Received By rmcphers Date 2020-07-22 Time 12:41 Sent To  
Notes
2020-07-22 12:41:50SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 12:14 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 12:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By rmcphers Date 2020-09-15 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2020-09-15 Time 15:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-06 Cont ID  
Sent By shill Date 2020-07-06 Time 15:45 Rev Time 0.00
Received By shill Date 2020-07-06 Time 15:45 Sent To  
Notes
2020-07-06 15:45:42PLANS UPLOADED ARE DIGITALLY SIGNED, PAPER NOT
 NECESSARY
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By rthermid Date 2020-09-15 Time   Rev Time 0.00
Received By rthermid Date 2020-09-15 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By rthermid Date 2020-08-05 Time   Rev Time  
Received By rthermid Date 2020-08-05 Time   Sent To I
Notes
2020-08-05 11:38:14ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 8/5/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A MARKED SURVEY OF THE PROPERTY
 INDICATING THE SETBACKS TO THE PROPERTY LINES OF THE
 ADDITION
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH