Plan Review Details - Permit 20050823
Plan Review Stops For Permit 20050823
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-14 Cont ID  
Sent By ppetty Date 2020-08-14 Time 09:31 Rev Time 0.00
Received By ppetty Date 2020-08-14 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-29 Cont ID  
Sent By ppetty Date 2020-05-29 Time 09:34 Rev Time 0.00
Received By ppetty Date 2020-05-29 Time 09:19 Sent To  
Notes
2020-05-29 09:34:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 2.PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC 107.1,
 107.2.1, 107.3.5.1.2
 3.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4.PROVIDE LOCATION OF 200A PANEL NEC 230.70
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-14 Cont ID  
Sent By ppetty Date 2020-08-14 Time 09:31 Rev Time 0.00
Received By ppetty Date 2020-08-12 Time 12:49 Sent To  
Notes
2020-08-12 12:49:14ROUTED TO ELECTRICAL BIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-29 Cont ID  
Sent By ppetty Date 2020-05-29 Time 09:34 Rev Time 0.00
Received By ppetty Date 2020-05-28 Time 10:11 Sent To  
Notes
2020-05-28 10:11:48ROUTED TO ELECTRICAL BIN