Plan Review Details - Permit 20050796
Plan Review Stops For Permit 20050796
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By rmcdouga Date 2020-09-21 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2020-09-21 Time 07:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-01 Cont ID  
Sent By rmcdouga Date 2020-09-01 Time 13:11 Rev Time 0.00
Received By rmcdouga Date 2020-09-01 Time 13:07 Sent To  
Notes
2020-09-01 14:13:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE THE REQUIRED SOIL BEARING CAPACITY FOR THE
 STAIR STRUCTURE. FBC 1801.2 AND 1803

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-14 Cont ID  
Sent By jleahy Date 2020-09-14 Time 16:11 Rev Time 0.00
Received By jleahy Date 2020-09-14 Time 16:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-31 Cont ID  
Sent By jleahy Date 2020-08-31 Time 11:32 Rev Time 0.00
Received By jleahy Date 2020-08-31 Time 11:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-08-14 Cont ID  
Sent By pleduc Date 2020-08-14 Time   Rev Time 0.00
Received By pleduc Date 2020-08-13 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-21 Cont ID  
Sent By rmcdouga Date 2020-09-21 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2020-09-11 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-03 Cont ID  
Sent By lmarchan Date 2020-09-03 Time 15:27 Rev Time 0.00
Received By lmarchan Date 2020-08-12 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-14 Cont ID  
Sent By abelisle Date 2020-09-14 Time 05:41 Rev Time 0.00
Received By abelisle Date 2020-09-14 Time 05:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-25 Cont ID  
Sent By jesmith Date 2020-08-25 Time 13:32 Rev Time 0.00
Received By jesmith Date 2020-08-25 Time 08:49 Sent To  
Notes
2020-08-25 13:30:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050796 700 S ROSEMARY AVE # 140
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. SEE PLAN SHEET P000; ALL STORM DRAIN CONNECTIONS ARE
 SHOWN ON THE SITE/CIVIL DRAWINGS. PER WPB FBC 107.2.1,
 PROVIDE SAID DRAWINGS.
 2. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR STORM
 DRAIN SIZING INCLUDING THE EXISTING THAT THE NEW DRAIN
 IS TO CONNECT TO. INCLUDE THE IMPACT OF THE IRRIGATION
 SYSTEM ON THE DRAINAGE SYSTEM.
 3. PER WPB FBC 107.2.1, PROVIDE SPECIFIC SPECIFICATION
 AND TESTING STANDARDS FOR CORRUGATED PIPE AND FITTINGS
 SHOWING COMPLIANCE WITH FBC PL TABLES 702.1 AND 702.4.
 4. A PRESSURE VACUUM BREAKER IS REQUIRED FOR THE
 IRRIGATION POINT OF CONNECTION TO COMPLY WITH FBC PL
 SECTION 608.
 5. A SEPARATE PERMIT IS REQUIRED FOR THE IRRIGATION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20050796 700 S ROSEMARY AVE # 140
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By rmcdouga Date 2020-09-21 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2020-09-21 Time 11:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-01 Cont ID  
Sent By rmcdouga Date 2020-09-01 Time 13:07 Rev Time 0.00
Received By rmcdouga Date 2020-09-01 Time 13:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-03 Cont ID  
Sent By eschneid Date 2020-09-03 Time 14:57 Rev Time 0.25
Received By eschneid Date 2020-09-03 Time 14:17 Sent To  
Notes
***NONE***