Plan Review Details - Permit 20050783
Plan Review Stops For Permit 20050783
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-05-27 Cont ID  
Sent By cpuell Date 2020-05-27 Time 08:18 Rev Time 0.00
Received By cpuell Date 2020-05-27 Time 08:18 Sent To  
Notes
2020-05-27 08:19:05WORK BEING DONE ON ALL UNITS MAIN ADDRESS TO REMAIN

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-05-26 Cont ID  
Sent By cpuell Date 2020-05-26 Time 11:47 Rev Time 0.00
Received By cpuell Date 2020-05-26 Time 11:47 Sent To  
Notes
2020-05-26 11:51:55PLEASE EMAIL [email protected], INDICATING WHICH UNIT THE
 WORK IS BEING DONE ON.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-03-12 Cont ID  
Sent By rmcdouga Date 2021-03-12 Time 12:46 Rev Time 0.00
Received By rmcdouga Date 2021-03-12 Time 09:59 Sent To  
Notes
2021-03-12 12:46:25APPROVED WITH PROVISO
  
 1) SUBMIT ONE HOUR FIRE RATED UL LISTED FLOOR/CEILING
 ASSEMBLY FOR THE TENANT SEPARATIONS.
  
 2) THIS PROJECT IS SPECIFIED AS PROTECTED CONSTRUCTION.
 ALL LOAD BEARING WALLS ARE REQUIRED TO BE ONE HOUR FIRE
 PROTECTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-02-26 Cont ID  
Sent By rmcdouga Date 2021-02-26 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2021-02-26 Time 13:27 Sent To  
Notes
2021-02-26 11:37:03PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REPAIRS AND RENOVATIONS TO AN EXISTING HISTORIC
 APARTMENT BUILDING.
 6 UNITS TOTAL
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED. THE DESCRIPTION OF WORK ON THE APPLICATION
 DOES NOT MATCH THE SCOPE OF WORK SHOWN ON THE PLANS.
 FBC 107.2.1
  
 2) RESOLVED. [VALUE CHANGED TO $165,000.00. ] THE VALUE
 FOR THE WORK ON THE APPLICATION OF $10,000.00 IS VERY
 LOW FOR THE SCOPE OF WORK INDICATED BY THE PLANS. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. NOTE:
 A SEPARATE PERMIT IS REQUIRED FOR RE-ROOFING. DO NOT
 INCLUDE THAT VALUE. THIS PERMIT VALUE IS FOR THE
 BUILDING AND THE MEPS.
  
 3) RESOLVED. THE SCOPE OF WORK LIST THAT WAS SUBMITTED
 IS NOT SPECIFIC ENOUGH. SUBMIT A DETAILED SCOPE OF WORK
 WITH A COST BREAKDOWN FOR EACH ITEM. FBC 107.2.1 &
 109.3
  
 4) RESOLVED. THE COVERSHEET, CVR, SPECIFIES THAT THIS
 BUILDING IS ONE STORY AND HAS A MEAN ROOF HEIGHT OF
 15'. THE STRUCTURE IS THREE STORIES AND HAS A MEAN ROOF
 HEIGHT OF MORE THAN 30 FEET. PLEASE CORRECT. FBC
 107.2.1
  
 5) NOT RESOLVED. [THE REVISED COVER SHEET CVR IS
 MISSING THE DESIGN CRITERIA, THE COMPONENT AND CLADDING
 PRESSURES, STRUCTURAL LOADS AND THE ATTIC VENTILATION
 INFORMATION THAT WAS PROVIDED ON THE PREVIOUS CVR
 SHEET. THIS INFORMATION IS REQUIRED. FBC 107 ] THE
 COMPONENT AND CLADDING PRESSURES FOR THE EXTERIOR DOORS
 AND WINDOWS ON SHEET CVR WILL NEED TO BE INCREASED FOR
 THE CORRECTED BUILDING MEAN ROOF HEIGHT. IF USING WORST
 CASE C&C PRESSURES SPECIFY THE PRESSURES FOR WALL ZONE
 5 IN EXPOSURE C WITH THE 30 PLUS MRH. FBC TABLE
 1609.6(2)
  
 6) RESOLVED. THIS BUILDING HAS MORE THAN THE TWO UNITS
 ALLOWED BY THE 2017 FBC RESIDENTIAL CODE. THE 2017 FBC
 BUILDING IS THE APPROPRIATE CODE FOR THIS APARTMENT
 BUILDING. PLEASE CORRECT THE NOTE ON SHEET CRV. FBC
 107.2.1
  
 7) NOT RESOLVED. [THERE ARE STILL SOME ISSUES WITH THE
 SCHEDULES. COORDINATE THE PRODUCT APPROVALS THAT ARE
 BEING SUBMITTED FOR EACH DOOR AND WINDOW WITH THE ONES
 LISTED IN THE SCHEDULES. PLEASE CIRCLE OR HI-LIGHT THE
 SPECIFIC WINDOW AND DOOR TYPE, SIZE AND DESIGN PRESSURE
 IN EACH OF THE PRODUCT APPROVALS.] PLEASE UPDATE THE
 WINDOW AND DOOR SCHEDULES. THE WINDOW AND EXTERIOR DOOR
 SCHEDULES ARE MISSING SOME INFORMATION FOR SOME ITEMS
 AND SOME OF THE SPECIFIED PRODUCT APPROVAL NUMBERS ARE
 EXPIRED. FBC 107.2.1
  
 8) RESOLVED. THE ELEVATION SHOWS A CASEMENT WINDOW WITH
 A FIXED ARCHED WINDOW ABOVE IT. THESE WINDOWS ARE NOT
 SPECIFIED IN THE SCHEDULE AND THEIR PRODUCT APPROVALS
 WERE NOT SUBMITTED. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT WINDOW TYPES (GLASS TYPES),
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. THESE
 ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE
 DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. ONLY
 ONE SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY
 SUBMITTED DOCUMENTS.
  
 9) RESOLVED. SUBMIT THE PRODUCT APPROVALS FOR THE
 EXTERIOR METAL OUT SWING FRONT DOORS. FBC 107.3.4
  
 10) RESOLVED. SPECIFY WHERE THE STRUCTURAL MULLIONS
 WILL BE USED. MARK OR HI-LIGHT THE MULLION SIZE, SPAN
 AND TRIBUTARY AREA FOR EACH OPENING IN THE APPROPRIATE
 SPAN TABLES IN THE MULLION PRODUCT APPROVAL. FBC
 107.2.1 & 107.2.1.2
  
 11) RESOLVED. THE TOTAL BUILDING AREA TABULATION IS
 SPECIFIED AS 2,146 SQFT ON SHEET CVR AND THERE IS AN
 AREA CALCULATION SCHEDULE THAT HAS THE TOTAL AS 5390
 SQ.FT. PLEASE CLARIFY. FBC 107.2.1
  
 12) RESOLVED. THE OCCUPANCY TYPE IS LISTED AS
 RESIDENTIAL ON SHEET CVR. SPECIFY THE SPECIFIC
 OCCUPANCY TYPE. THIS APPEARS TO BE APARTMENTS, AN R-2
 OCCUPANCY. SEE FBC R310.
  
 13) NOT RESOLVED. [ THE NOTE WAS CHANGED TO TYPE VA
 PROTECTED AND SPRINKLERED. THIS IS NOT CORRECT. PER FBC
 TABLE 601 TYPE VA CONSTRUCTION REQUIRES THE BEARING
 WALLS, COLUMNS, FLOORS AND ROOF TO HAVE ONE HOUR FIRE
 RESISTIVE PROTECTION. THE PLANS DO NOT SHOW THIS. THE
 REVISED PLANS INDICATE THAT THE BUILDING WILL BE
 SPRINKLERED. FBC TABLE 504.4 ALLOWS FIRE SPRINKLERED
 R-2 OCCUPANCIES TO BE 3 STORIES ABOVE GRADE. THE
 CONSTRUCTION TYPE AS SHOWN ON THE PLANS IS VB,
 UNPROTECTED, SPRINKLERED. PLEASE CORRECT.] THE NOTES ON
 SHEET CVR, SPECIFY THIS BUILDING AS TYPE VB
 UNSPRINKLERED. FBC TABLE 504.4 LIMITS R-2 OCCUPANCIES
 OF TYPE VB CONSTRUCTION TO TWO STORIES AND THIS IS
 THREE STORIES. IT WOULD NEED TO BE SPRINKLERED OR OF
 TYPE VA CONSTRUCTION TO BE THREE STORIES. PLEASE
 CLARIFY.
  
 14) RESOLVED. PROVIDE A LIFE SAFETY EXITING PLAN. FBC
 107.2.3 & 107.3.5.1
  
 15) RESOLVED. [BUILDING IS TO BE FIRE SPRINKLERED.] FBC
 EXISTING BUILDING 804.2.2 IN BUILDINGS WITH OCCUPANCIES
 IN GROUPS A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1 AND
 S-2, WORK AREAS THAT HAVE EXITS OR CORRIDORS SHARED BY
 MORE THAN ONE TENANT OR THAT HAVE EXITS OR CORRIDORS
 SERVING AN OCCUPANT LOAD GREATER THAN 30 SHALL BE
 PROVIDED WITH AUTOMATIC SPRINKLER PROTECTION WHERE ALL
 OF THE FOLLOWING CONDITIONS OCCUR:
 1.THE WORK AREA IS REQUIRED TO BE PROVIDED WITH
 AUTOMATIC SPRINKLER PROTECTION IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING AS APPLICABLE TO NEW
 CONSTRUCTION; AND
 2. THE WORK AREA EXCEEDS 50 PERCENT OF THE FLOOR AREA.
 EXCEPTION: IF THE BUILDING DOES NOT HAVE SUFFICIENT
 MUNICIPAL WATER SUPPLY FOR DESIGN OF A FIRE SPRINKLER
 SYSTEM AVAILABLE TO THE FLOOR WITHOUT INSTALLATION OF A
 NEW FIRE PUMP, WORK AREAS SHALL BE PROTECTED BY AN
 AUTOMATIC SMOKE DETECTION SYSTEM THROUGHOUT ALL
 OCCUPIABLE SPACES OTHER THAN SLEEPING UNITS OR
 INDIVIDUAL DWELLING UNITS THAT ACTIVATES THE OCCUPANT
 NOTIFICATION SYSTEM IN ACCORDANCE WITH SECTIONS 907.4,
 907.5 AND 907.6 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 16) RESOLVED [FIRE ALARM TO BE INSTALLED.] FBC EXISTING
 BUILDING 804.4.1.6 GROUP R-2 A FIRE ALARM SYSTEM SHALL
 BE INSTALLED IN WORK AREAS OF GROUP R-2 APARTMENT
 BUILDINGS AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE FOR EXISTING GROUP R-2 OCCUPANCIES.
  
 17) NOT RESOLVED. [SUBMIT PLANS THAT HAVE BEEN SIGNED
 AND SEALED BY A FLORIDA LICENSED DESIGN PROFESSIONAL.]
 THESE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY A
 FLORIDA LICENSED DESIGN PROFESSIONAL. AN ARCHITECT
 SHOULD PREPARE AND SEAL THE ARCHITECTURAL DRAWINGS AND
 AN ENGINEER SHOULD PREPARE AND SEAL THE STRUCTURAL
 PLANS. FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING
 OF CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS.
  
 18) NOT RESOLVED. [THERE ARE SOME ISSUES WITH THE
 GUARDRAIL DRAWINGS ON THE PLANS. SEE MARKUPS ON SHEET
 A4. THE SPACE BETWEEN INTERMEDIATE RAILS IS REQUIRED TO
 REJECT A 4' SPHERE AND THE POST HEIGHT DIMENSION IS
 SHOWN TOO SHORT FOR A 42" GUARDRAIL. NO INFORNATION WAS
 PROVIDED FOR THE HANDRAILS. THE CONSTRUCTION DOCUMENTS
 AND SHOP DRAWINGS FOR THE HANDRAILS AND GUARDS FROM THE
 SPECIALTY ENGINEER CAN BE DEFERRED IF REQUESTED. THESE
 DOCUMENTS CAN BE SUBMITTED TO THE BUILDING DEPARTMENT
 FOR REVIEW AND APPROVAL ANY TIME PRIOR TO INSTALLATION.
 THEY WILL NEED TO BE REVIEWED AND APPROVED WITH A SHOP
 REVIEW STAMP BY THE DESIGNER OF RECORD BEFORE THEY ARE
 SUBMITTED.] PROVIDE GUARDRAIL AND HANDRAIL DETAILS FOR
 THE STAIRS AND BALCONIES. SHOW COMPLIANCE WITH FBC 1015
 & 1014.
  
 19) ADDITIONAL COMMENTS MAY BE GENERATED FROM THE
 RESPONSES TO THESE ITEMS. WHEN RESUBMITTING, IT IS
 HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM.
  
 NEW COMMENT:
  
 20) IN ADDITION TO THE TENANT SEPARATION WALLS THE
 FLOOR/CEILING ASSEMBLIES SEPARATING THE DIFFERENT
 TENANTS ARE ALSO REQUIRED TO BE OF ONE HOUR FIRE
 RESISTIVE CONSTRUCTION. PROVIDE DETAIL DRAWINGS WITH
 THEIR LISTING NUMBERS FOR APPROVED ONE HOUR FIRE RATED
 WALL AND FLOOR/CEILING ASSEMBLIES. SHOW COMPLIANCE WITH
 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-14 Cont ID  
Sent By rmcdouga Date 2020-12-14 Time 13:32 Rev Time 0.00
Received By rmcdouga Date 2020-12-10 Time 14:20 Sent To  
Notes
2020-12-11 16:50:13PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REPAIRS AND RENOVATIONS TO AN EXISTING HISTORIC
 APARTMENT BUILDING.
 6 UNITS TOTAL
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DESCRIPTION OF WORK ON THE APPLICATION DOES NOT
 MATCH THE SCOPE OF WORK SHOWN ON THE PLANS. FBC 107.2.1
  
 2) THE VALUE FOR THE WORK ON THE APPLICATION OF
 $10,000.00 IS VERY LOW FOR THE SCOPE OF WORK INDICATED
 BY THE PLANS. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. NOTE:
 A SEPARATE PERMIT IS REQUIRED FOR RE-ROOFING. DO NOT
 INCLUDE THAT VALUE. THIS PERMIT VALUE IS FOR THE
 BUILDING AND THE MEPS.
  
 3) THE SCOPE OF WORK LIST THAT WAS SUBMITTED IS NOT
 SPECIFIC ENOUGH. SUBMIT A DETAILED SCOPE OF WORK WITH A
 COST BREAKDOWN FOR EACH ITEM. FBC 107.2.1 & 109.3
  
 4) THE COVERSHEET, CVR, SPECIFIES THAT THIS BUILDING IS
 ONE STORY AND HAS A MEAN ROOF HEIGHT OF 15'. THE
 STRUCTURE IS THREE STORIES AND HAS A MEAN ROOF HEIGHT
 OF MORE THAN 30 FEET. PLEASE CORRECT. FBC 107.2.1
  
 5) THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS ON SHEET CVR WILL NEED TO BE
 INCREASED FOR THE CORRECTED BUILDING MEAN ROOF HEIGHT.
 IF USING WORST CASE C&C PRESSURES SPECIFY THE PRESSURES
 FOR WALL ZONE 5 IN EXPOSURE C WITH THE 30 PLUS MRH. FBC
 TABLE 1609.6(2)
  
 6) THIS BUILDING HAS MORE THAN THE TWO UNITS ALLOWED BY
 THE 2017 FBC RESIDENTIAL CODE. THE 2017 FBC BUILDING IS
 THE APPROPRIATE CODE FOR THIS APARTMENT BUILDING.
 PLEASE CORRECT THE NOTE ON SHEET CRV. FBC 107.2.1
  
 7) PLEASE UPDATE THE WINDOW AND DOOR SCHEDULES. THE
 WINDOW AND EXTERIOR DOOR SCHEDULES ARE MISSING SOME
 INFORMATION FOR SOME ITEMS AND SOME OF THE SPECIFIED
 PRODUCT APPROVAL NUMBERS ARE EXPIRED. FBC 107.2.1
  
 8) THE ELEVATION SHOWS A CASEMENT WINDOW WITH A FIXED
 ARCHED WINDOW ABOVE IT. THESE WINDOWS ARE NOT SPECIFIED
 IN THE SCHEDULE AND THEIR PRODUCT APPROVALS WERE NOT
 SUBMITTED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 WINDOW TYPES (GLASS TYPES), STRUCTURAL MULLIONS AND
 EXTERIOR DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF
 REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 9) SUBMIT THE PRODUCT APPROVALS FOR THE EXTERIOR METAL
 OUT SWING FRONT DOORS. FBC 107.3.4
  
 10) SPECIFY WHERE THE STRUCTURAL MULLIONS WILL BE USED.
 MARK OR HI-LIGHT THE MULLION SIZE, SPAN AND TRIBUTARY
 AREA FOR EACH OPENING IN THE APPROPRIATE SPAN TABLES IN
 THE MULLION PRODUCT APPROVAL. FBC 107.2.1 & 107.2.1.2
  
 11) THE TOTAL BUILDING AREA TABULATION IS SPECIFIED AS
 2,146 SQFT ON SHEET CVR AND THERE IS AN AREA
 CALCULATION SCHEDULE THAT HAS THE TOTAL AS 5390 SQ.FT.
 PLEASE CLARIFY. FBC 107.2.1
  
 12) THE OCCUPANCY TYPE IS LISTED AS RESIDENTIAL ON
 SHEET CVR. SPECIFY THE SPECIFIC OCCUPANCY TYPE. THIS
 APPEARS TO BE APARTMENTS, AN R-2 OCCUPANCY. SEE FBC
 R310.
  
 13) THE NOTES ON SHEET CVR, SPECIFY THIS BUILDING AS
 TYPE VB UNSPRINKLERED. FBC TABLE 504.4 LIMITS R-2
 OCCUPANCIES OF TYPE VB CONSTRUCTION TO TWO STORIES AND
 THIS IS THREE STORIES. IT WOULD NEED TO BE SPRINKLERED
 OR OF TYPE VA CONSTRUCTION TO BE THREE STORIES. PLEASE
 CLARIFY.
  
 14) PROVIDE A LIFE SAFETY EXITING PLAN. FBC 107.2.3 &
 107.3.5.1
  
 15) FBC EXISTING BUILDING 804.2.2 IN BUILDINGS WITH
 OCCUPANCIES IN GROUPS A, B, E, F-1, H, I, M, R-1, R-2,
 R-4, S-1 AND S-2, WORK AREAS THAT HAVE EXITS OR
 CORRIDORS SHARED BY MORE THAN ONE TENANT OR THAT HAVE
 EXITS OR CORRIDORS SERVING AN OCCUPANT LOAD GREATER
 THAN 30 SHALL BE PROVIDED WITH AUTOMATIC SPRINKLER
 PROTECTION WHERE ALL OF THE FOLLOWING CONDITIONS OCCUR:
 1.THE WORK AREA IS REQUIRED TO BE PROVIDED WITH
 AUTOMATIC SPRINKLER PROTECTION IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING AS APPLICABLE TO NEW
 CONSTRUCTION; AND
 2. THE WORK AREA EXCEEDS 50 PERCENT OF THE FLOOR AREA.
 EXCEPTION: IF THE BUILDING DOES NOT HAVE SUFFICIENT
 MUNICIPAL WATER SUPPLY FOR DESIGN OF A FIRE SPRINKLER
 SYSTEM AVAILABLE TO THE FLOOR WITHOUT INSTALLATION OF A
 NEW FIRE PUMP, WORK AREAS SHALL BE PROTECTED BY AN
 AUTOMATIC SMOKE DETECTION SYSTEM THROUGHOUT ALL
 OCCUPIABLE SPACES OTHER THAN SLEEPING UNITS OR
 INDIVIDUAL DWELLING UNITS THAT ACTIVATES THE OCCUPANT
 NOTIFICATION SYSTEM IN ACCORDANCE WITH SECTIONS 907.4,
 907.5 AND 907.6 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 16) FBC EXISTING BUILDING 804.4.1.6 GROUP R-2 A FIRE
 ALARM SYSTEM SHALL BE INSTALLED IN WORK AREAS OF GROUP
 R-2 APARTMENT BUILDINGS AS REQUIRED BY THE FLORIDA FIRE
 PREVENTION CODE FOR EXISTING GROUP R-2 OCCUPANCIES.
  
 17) THESE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY
 A FLORIDA LICENSED DESIGN PROFESSIONAL. AN ARCHITECT
 SHOULD PREPARE AND SEAL THE ARCHITECTURAL DRAWINGS AND
 AN ENGINEER SHOULD PREPARE AND SEAL THE STRUCTURAL
 PLANS. FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING
 OF CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 18) PROVIDE GUARDRAIL AND HANDRAIL DETAILS FOR THE
 STAIRS AND BALCONIES. SHOW COMPLIANCE WITH FBC 1015 &
 1014.
  
 19) ADDITIONAL COMMENTS MAY BE GENERATED FROM THE
 RESPONSES TO THESE ITEMS. WHEN RESUBMITTING, IT IS
 HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-03 Cont ID  
Sent By rmcdouga Date 2020-06-03 Time 14:31 Rev Time 0.00
Received By rmcdouga Date 2020-06-03 Time 14:31 Sent To  
Notes
2020-06-03 14:31:05PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE APPLICATION INDICATES THAT THE SCOPE OF WORK FOR
 THIS PERMIT IS TO REPAIR AND REPLACE ROTTEN WOOD
 RELATED TO A REROOF PERMIT. PRODUCT APPROVALS FOR ROOF
 COVERING MATERIALS WERE UPLOADED. THEY SHOULD BE WITH
 THE REROOFING PERMIT DOCUMENTS NOT THIS ONE. FBC
 107.2.1
  
 2) SUBMIT A DETAILED SCOPE OF WORK FOR THIS PROJECT.
 FBC 107.2.1
  
 3) SUBMIT PLANS SHOWING THE AREAS OF THE ROOF WHERE THE
 REPAIRS ARE NEED. THE ADDRESS OF THE PROPERTY AND THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE IS
 REQUIRED TO BE ON THE PLAN. FBC 107.2.1
  
 4) SIGNED AND SEALED TRUSS REPAIR DETAILS FROM AN
 ENGINEER WILL BE RQUIRED IF TRUSSES ARE REPAIRED. FBC
 107

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-03-09 Cont ID  
Sent By equinone Date 2021-03-09 Time 11:25 Rev Time 0.00
Received By equinone Date 2021-03-09 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-02-18 Cont ID  
Sent By equinone Date 2021-02-18 Time 16:17 Rev Time 0.00
Received By equinone Date 2021-02-18 Time 16:17 Sent To  
Notes
2021-02-18 16:19:20CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET E-6 ELECTRICAL RISER DIAGRAM: GROUNDING
 ELECTRODE CONDUCTOR IS TOO SMALL. IT NEEDS TO BE SIZED
 ON EQUIVALENT OF 2 SETS OF 3#600 (1200 KCMIL) CU.
 MINIMUM SIZE NEEDS TO BE 3/0 CU. NEC 250.66
 2) SHEET E-6 ELECTRICAL RISER DIAGRAM: PLEASE CLARIFY
 IF SERVICE CONDUCTORS WILL BE UNDERGROUND OR OVERHEAD.
 IT APPEARS THERE IS NOT ROOM TO MEET OVERHEAD
 CLEARANCES. FBC 107
 3) SHEET E-5 CALCULATED LOAD FOR METER CENTER ONLY
 INCLUDES THE 3 VA/SQUARE FOOT FOR GENERAL LIGHTING AND
 RECEPTACLES. IT NEEDS TO INCLUDE ALL LOADS LISTED IN
 220.84(C). NEC 220.84
 4) SHEET E-1: PLEASE SHOW LOCATION OF PANEL A FOR UNIT
 3. FBC 107, NEC 230.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By equinone Date 2020-12-01 Time 15:25 Rev Time 0.00
Received By equinone Date 2020-12-01 Time 15:25 Sent To  
Notes
2020-12-01 15:25:46CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: FAILED.
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CLARIFY SCOPE OF WORK FOR THE ELECTRICAL
 SYSTEMS FOR THIS PROJECT. THE DRAWINGS SEEM TO INDICATE
 EXTENSIVE NEW ELECTRICAL SYSTEMS, BUT THE BUILDING
 PERMIT SPECIFIES JUST REPLACING DAMAGED/ROTTEN WOOD FOR
 INSTALLATION OF NEW ROOF AND THE ELECTRICAL PERMIT
 MENTIONS GENERAL ELECTRICAL WORK WITH NO SPECIFICS.
 PLEASE CLARIFY WHAT IS EXISTING TO REMAIN AND WHAT IS
 NEW OR MODIFIED. FBC 107
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-03-09 Cont ID  
Sent By pleduc Date 2021-03-09 Time   Rev Time 0.00
Received By pleduc Date 2021-03-09 Time 09:45 Sent To  
Notes
2021-03-09 10:01:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE RESPONSE FROM THE FIRE SPRINKLER CONTRACTOR
 STATING A CODE SECTION FROM NFPA 13 MAY NOT
 SPECIFICALLY APPLY IN THIS INSTANCE.
  
 THE CODE SECTION QUOTED 8.15.3.2.3.1 FALLS UNDER
 8.15.3.2 NONCOMBUSTIBLULE CONSTRUCTION.
  
 THE PROPOSED STAIRS ARE WOOD/COMBUSTIBULE.
  
 A MORE SPECIFIC CODE INDICATES THAT FIRE SPRINKLESR
 SHALL BE INSTALLED UNDER COMBUSTIBLE STAIRS.
  
 PER NFPA 13
  
 8.15.3 STAIRWAYS.
  
 8.15.3.1 COMBUSTIBLE CONSTRUCTION. SPRINKLERS SHALL BE
 INSTALLED
 BENEATH ALL STAIRWAYS OF COMBUSTIBLE CONSTRUCTION.
 8.15.3.1.1 SPRINKLERS SHALL BE INSTALLED AT THE TOP OF
 COMBUSTIBLE
 STAIR SHAFTS.
 8.15.3.1.2* SPRINKLERS SHALL BE INSTALLED UNDER THE
 LANDINGS AT
 EACH FLOOR LEVEL.
 8.15.3.1.3 SPRINKLERS SHALL BE INSTALLED BENEATH THE
 LOWEST INTERMEDIATE
 LANDING.
  
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD, THIS PERMIT
 WILL BE PASSED WITH PROVISO TO ADDRESS THE STIAIR FIRE
 PROTECTION OF THE SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-02-22 Cont ID  
Sent By pleduc Date 2021-02-22 Time   Rev Time 0.00
Received By pleduc Date 2021-02-22 Time 09:39 Sent To  
Notes
2021-02-22 13:54:07 
  
 FAILED BY FIRE WITH COMMENTS:
  
  
 1) THE FP PLANS DO NOT INDICATE FIRE SPRINKLER
 PROTECTION UNDER THE INTERIOR EXIT STAIRS.
  
 PER NFPA 13,
  
 8.15.3 STAIRWAYS.
 8.15.3.1 COMBUSTIBLE CONSTRUCTION. SPRINKLERS SHALL BE
 INSTALLED
 BENEATH ALL STAIRWAYS OF COMBUSTIBLE CONSTRUCTION.
 8.15.3.1.1 SPRINKLERS SHALL BE INSTALLED AT THE TOP OF
 COMBUSTIBLE
 STAIR SHAFTS.
 8.15.3.1.2* SPRINKLERS SHALL BE INSTALLED UNDER THE
 LANDINGS AT
 EACH FLOOR LEVEL.
 8.15.3.1.3 SPRINKLERS SHALL BE INSTALLED BENEATH THE
 LOWEST INTERMEDIATE
 LANDING.
  
 FOR CLARIFICATION PRUPOSES, PLEASE INCLUDE A DETAILED
 REVIEW OF THE PROPOSED CONSTRUCTION AND THE PROTECTION
 OF THE STAIRWAYS PER THE CODE.
  
  
  
 2) WPB FEB 2021 SHEET A4 - THERE DOES NOT APPEAR TO BE
 A CLEAR INDICATION OF THE EXTERIOR EXIT STAIRWAY
 CONSTRUCTION MATERIAL. THERE IS AN INDICATION OF AN
 ALUMINUM RAILING, BUT NO THE STAIRWAY.
  
 PER NFPA 101
  
 30.2.2.3 STAIRS.
 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
  
 7.2.2.5 SPECIAL PROVISIONS FOR EXTERIOR STAIRS.
  
 7.2.2.5.1 LANDINGS. LANDINGS TO WHICH EGRESS DOORS LEAD
 SHALL
 BE APPROXIMATELY LEVEL [WITHIN 1 CM (3?8 IN.)] WITH THE
 ADJOINING
 DECK.
 7.2.2.5.2 EXTERIOR STAIRS SHALL BE PERMITTED TO BE USED
 AS A
 COMPONENT OF EGRESS WHERE THERE IS AN OBVIOUS ROUTE OR
 EGRESS
 DIRECTION SIGNAGE LEADING TO AN AREA OF SAFE REFUGE OR
 AN EMBARKATION
 AREA.
 7.2.2.5.3 EXTERIOR STAIRS SHALL BE CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIAL.
  
 7.2.2.5.5 EXTERIOR STAIRS SHALL COMPLY WITH THE
 REQUIREMENTS
 OF TABLE 7.2.2.5.5 AND SUBSEQUENT SECTIONS.
  
 FOR CLARIFICATION PURPOSES PLEASE REVIEW AND INCLUDE A
 DETAILED REVIEW OF THE PROPOSED CONSTRUCTION OR PROVIDE
 THE SHEET LOCATION CONTAINING THE REQUIRED INFORMATION.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-12-14 Cont ID  
Sent By pleduc Date 2020-12-14 Time   Rev Time 0.00
Received By pleduc Date 2020-12-11 Time 15:36 Sent To  
Notes
2020-12-14 16:01:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PLEASE PROVIDE A COMPLETE SCOPE OF WORK FOR THIS
 PROJECT.
  
 IT APPEARS THAT THE ENTIRE BUILDING IS BEING REMODELED
 WHICH WOULD BE REQUIRED TO BE CONSTRUCTED A A NEW
 OCCUPANCY.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2) THERE IS NO INDICATION OF COMPLAINCE WITH ANY FIRE
 CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND
 COMPLIANCE.
  
  
  
 3) PLEASE PROVIDE THE NEW OCCUPANCY TYPE AS IT APPEARS
 TO BE AN APARTMENT OCCUPANCY AND COMPLY WITH THE
 REQUIRMENTS OF NFPA 30.
  
 CHAPTER 30 NEW APARTMENT BUILDINGS
 30.1 GENERAL REQUIREMENTS.
 30.1.1 APPLICATION.
 30.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO NEW
 BUILDINGS OR PORTIONS THEREOF USED AS APARTMENT
 OCCUPANCIES. (SEE
 1.3.1.)
  
 PLEASE PROVIDE DETAILS
  
  
  
 4) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH
 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 INSTALLED IN
 ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3
 AND 30.3.5.4. IN
 BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE,
 SYSTEMS IN
 ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION
 OF
 SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES,
 SHALL BE
 PERMITTED.
  
 REQUIRED F.A.C. 61G ARE REQUIRED TO BE SUBMITTED WITH
 THIS MASTER PERMIT.
  
 PLEASE PROVIDE.
  
  
 5) THERE ARE NO INDICATIONS OF A FIRE ALARM SYSTEM.
  
 A FIRE SPRINKLER ALARM IS REQUIRED AND SHALL BE
 MONITORED.
  
 9.7.2 SUPERVISION.
 9.7.2.1* SUPERVISORY SIGNALS.
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED BY
 ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS
 SHALL BE INSTALLED
 AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72,
 NATIONAL FIRE
 ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY
 SIGNAL SHALL BE
 PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE
 SATISFACTORY
 OPERATION OF THE SPRINKLER SYSTEM.
 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE
 DISPLAYED EITHER AT
 A LOCATION WITHIN THE PROTECTED BUILDING THAT IS
 CONSTANTLY ATTENDED BY
 QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED
 RECEIVING
 FACILITY.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDEGMENT
  
  
 6) THERE APPEARS TO BE A SIGNLE EXIT FROM THE 3RD FL
 UNIT.
  
 2 ARE REQUIRED.
  
 30.2.4 NUMBER OF MEANS OF EGRESS.
 30.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL COMPLY
 WITH
 SECTION 7.4.
 30.2.4.2 THE MINIMUM NUMBER OF EXITS SHALL COMPLY WITH
 30.2.4.3, 30.2.4.4, OR 30.2.4.6.
 30.2.4.3 EVERY DWELLING UNIT SHALL HAVE ACCESS TO AT
 LEAST TWO
 SEPARATE EXITS REMOTELY LOCATED FROM EACH OTHER AS
 REQUIRED BY
 7.5.1.
 30.2.4.4 DWELLING UNITS SHALL BE PERMITTED TO HAVE
 ACCESS TO A
 SINGLE EXIT, PROVIDED THAT ONE OF THE FOLLOWING
 CONDITIONS IS MET:
 (1) THE DWELLING UNIT HAS AN EXIT DOOR OPENING DIRECTLY
 TO THE
 STREET OR YARD AT THE FINISHED GROUND LEVEL.
 (2) THE DWELLING UNIT HAS DIRECT ACCESS TO AN OUTSIDE
 STAIR THAT
 COMPLIES WITH 7.2.2 AND SERVES A MAXIMUM OF TWO UNITS,
 BOTH OF WHICH ARE LOCATED ON THE SAME STORY.
 (3) THE DWELLING UNIT HAS DIRECT ACCESS TO AN INTERIOR
 STAIR THAT
 SERVES ONLY THAT UNIT AND IS SEPARATED FROM ALL OTHER
 PORTIONS
 OF THE BUILDING BY FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE
 RESISTANCE RATING, WITH NO OPENING THEREIN.
  
 30.2.4.6 A SINGLE EXIT SHALL BE PERMITTED IN BUILDINGS
 WHERE THE
 TOTAL NUMBER OF STORIES DOES NOT EXCEED FOUR, PROVIDED
 THAT ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) THERE ARE FOUR OR FEWER DWELLING UNITS PER STORY.
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 30.3.5.
 (3) THE EXIT STAIRWAY DOES NOT SERVE MORE THAN ONE-HALF
 STORY
 BELOW THE LEVEL OF EXIT DISCHARGE.
 (4) THE TRAVEL DISTANCE FROM THE ENTRANCE DOOR OF ANY
 DWELLING
 UNIT TO AN EXIT DOES NOT EXCEED 35 FT (10.7 M).
 (5) THE EXIT STAIRWAY IS COMPLETELY ENCLOSED OR
 SEPARATED FROM
 THE REST OF THE BUILDING BY BARRIERS HAVING A MINIMUM
 1-HOUR
 FIRE RESISTANCE RATING.
 (6) ALL OPENINGS BETWEEN THE EXIT STAIRWAY ENCLOSURE
 AND THE
 BUILDING ARE PROTECTED WITH SELF-CLOSING DOOR
 ASSEMBLIES
 HAVING A MINIMUM 1-HOUR FIRE PROTECTION RATING.
 (7) ALL CORRIDORS SERVING AS ACCESS TO EXITS HAVE A
 MINIMUM 1-
 HOUR FIRE RESISTANCE RATING.
 (8) HORIZONTAL AND VERTICAL SEPARATION HAVING A MINIMUM
 ?-HOUR
 FIRE RESISTANCE RATING IS PROVIDED BETWEEN DWELLING
 UNITS.
  
 PLEASE CORRECT OR PROVIDE DETAILS IN COMPLIANCE.
  
  
 7) THERE ARE INDICATIONS OF STAIR EXIT PAST UNPROTECTD
 WINDOWS.
  
 30.2.2.3 STAIRS.
 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS.
 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE
 BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE
 RATING REQUIRED FOR
 ENCLOSED STAIRS WITH FIXED OR SELF-CLOSING OPENING
 PROTECTIVES,
 EXCEPT AS FOLLOWS:
 (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS
 BALCONY THAT HAS
 TWO REMOTE OUTSIDE STAIRWAYS OR RAMPS SHALL BE
 PERMITTED TO BE
 UNPROTECTED.
 (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT
 STORIES, INCLUDING
 THE STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED
 TO BE
 UNPROTECTED WHERE THERE IS A REMOTELY LOCATED SECOND
 EXIT.
 (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS
 SERVING THREE OR
 FEWER ADJACENT STORIES, INCLUDING THE STORY WHERE THE
 EXIT
 DISCHARGES, SHALL BE PERMITTED TO BE UNPROTECTED WHERE
 THERE IS
 A REMOTELY LOCATED SECOND EXIT.
 (4) THE FIRE RESISTANCE RATING OF A SEPARATION
 EXTENDING 10 FT (3050
 MM) FROM THE STAIRS SHALL NOT BE REQUIRED TO EXCEED 1
 HOUR
 WHERE OPENINGS HAVE A MINIMUM ?-HOUR FIRE PROTECTION
 RATING.
 (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED
 THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7 SHALL BE PERMITTED TO BE
 UNPROTECTED.
 7.2.2.6.3.2 WALL CONSTRUCTION REQUIRED BY 7.2.2.6.3.1
 SHALL EXTEND AS
 FOLLOWS:
 (1) VERTICALLY FROM THE FINISHED GROUND LEVEL TO A
 POINT 10 FT (3050
 MM) ABOVE THE TOPMOST LANDING OF THE STAIRS OR TO THE
 ROOFLINE,
 WHICHEVER IS LOWER
 (2) HORIZONTALLY FOR NOT LESS THAN 10 FT (3050 MM)
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE.
  
  
 8) THERE ARE NO INDICATIONS OF STAIR DETAILS IN
 COMPLIANCE WITH THE FIRE CODE.
  
 30.2.2.3 STAIRS.
 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
  
 7.2.2.4.5* HANDRAIL DETAILS.
  
 7.2.2.4.6 GUARD DETAILS
  
 PLEASE PROVIDE SPECIFIC DETAILS OF COMPLIANCE.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By fmittner Date 2020-12-07 Time 11:38 Rev Time 0.00
Received By fmittner Date 2020-12-07 Time 11:38 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-05-28 Cont ID  
Sent By fmittner Date 2020-05-28 Time 09:13 Rev Time 0.00
Received By fmittner Date 2020-05-28 Time 09:13 Sent To  
Notes
2020-05-28 09:13:46PASSED WITH PROVISO CONFIRMED BY OWNER VIA E-MAIL THAT
 PRODUCT APPROVAL FOR TILE WILL BE REVISED TO A TRUE
 BARREL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-03-12 Cont ID  
Sent By rmcdouga Date 2021-03-12 Time 12:50 Rev Time 0.00
Received By rmcdouga Date 2021-03-05 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-02 Cont ID  
Sent By lmarchan Date 2021-03-02 Time 13:53 Rev Time 0.00
Received By lmarchan Date 2021-02-11 Time 14:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-17 Cont ID  
Sent By cpuell Date 2020-12-17 Time 10:30 Rev Time 0.00
Received By cpuell Date 2020-11-21 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-03 Cont ID  
Sent By rmcdouga Date 2020-06-03 Time 14:31 Rev Time 0.00
Received By rmcdouga Date 2020-05-26 Time 13:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-12-14 Cont ID  
Sent By rmcdouga Date 2020-12-14 Time 13:32 Rev Time 0.00
Received By rmcdouga Date 2020-12-14 Time 13:32 Sent To  
Notes
2020-12-14 13:35:02THIS IS AN EXISTING HISTORIC 6 UNIT APARTMENT BUILDING
 AND THE PLANS DO NOT SHOW THE ADDTION OF ANY HABITABLE
 SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-03-10 Cont ID  
Sent By medwards Date 2021-03-10 Time 07:28 Rev Time 0.00
Received By medwards Date 2021-03-10 Time 06:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-02-18 Cont ID  
Sent By medwards Date 2021-02-18 Time 06:21 Rev Time 0.00
Received By medwards Date 2021-02-18 Time 06:21 Sent To  
Notes
2021-02-18 06:21:512ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20050783
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL PERMIT STILL DOES NOT HAVE A VALUE
 FOR THE PROJECT. THE 18,000.00 VALUE SHOWN ON ANOTHER
 DOCUMENT APPEARS TO BE LOW FOR THIS MECHANICAL PROJECT.
 PLEASE PROVIDE THE CORRECTED VALUE ON THE MECHANICAL
 PERMIT APPLICATION. FBC 107.2.1
  
 2) FIRST CYCLE REVIEW THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR EACH UNIT WAS REQUESTED. THE
 INFORMATION WAS NOT SUBMITTED THIS CYCLE. PLEASE
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR EACH UNIT ON THIS PROJECT. FBC EC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-23 Cont ID  
Sent By medwards Date 2020-11-23 Time 11:27 Rev Time 0.00
Received By medwards Date 2020-11-23 Time 10:16 Sent To  
Notes
2020-11-23 11:27:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050783
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL
 SYSTEMS FOR THIS PROJECT. THE DRAWINGS INDICATE TOTALLY
 NEW SYSTEMS. IF ALL SYSTEMS ARE NEW PLEASE PROVIDE THE
 LIKE FOR LIKE DOCUMENTATION FOR EACH UNIT REPLACED.
 CITY RECORDS INDICATE THERE ARE NO RECORDS THAT A HVAC
 SYSTEM HAS BEEN INSTALLED IN THESE APARTMENTS. PLEASE
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS.
 THE MECHANICAL PERMIT MUST ALSO INCLUDE THE VALUE OF
 THE PROJECT. FBC 107.2 FBC EC FBC EC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By lcrespo Date 2021-02-17 Time 10:43 Rev Time 0.00
Received By lcrespo Date 2021-02-17 Time 10:43 Sent To  
Notes
2021-02-17 10:45:1202/17/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-23 Cont ID  
Sent By lcrespo Date 2020-11-23 Time 17:26 Rev Time 0.00
Received By lcrespo Date 2020-11-23 Time 17:26 Sent To  
Notes
2020-11-23 17:26:4011/23/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 2. PLEASE PROVIDE SPECIFICATIONS FOR TANKLESS ELECTRIC
 WATER HEATER PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. THERE TWO TUBS AND ONE SHOWER THAT SHOW AIR
 ADMITANCE VALVES BEHIND THEM, THEY NEED TO HAVE AN
 ACCESS PANEL OR YOU CAN RE-VENT THEM PLEASE SHOW ON
 ISOMETRIC OR MAKE NOTES ON PLANS FOR ACCESSIBLE
 LOCATION PER THE 2017 FBC SEC. 918.5 ACCESS AND
 VENTILATION.
  
 4. ON ISOMETRIC P-4 AND P-2, UNIT 4 HAS THE KITCHEN IN
 A BATHROOM GROUP WET VENT AND IT MUST RUN DOWNSTREAM OF
 THE GROUP PER THE 2017 FBC SEC. 912.1 HORIZONTAL WET
 VENTS PERMITTED.
  
 5. ON ISOMETRIC P-4 RISER D 2?, UNIT 2 BATH AND
 KITCHEN, AND RISER 3? HAVE ENTRY TO THE BUILDING WITH
 THE CLEANOUT AND MUST BE VENTED THROUGH ROOF AND MUST
 HAVE A MINIMUM OF ONE STACK VENT OR VENT STACK EXTENDED
 TO THE OUTDOORS TO THE OPEN AIR PER THE FBC SEC. P
 918.7. SHOW COMPLIANCE WITH THE PLANS.
  
 6. ON ISOMETRIC P-4 CLEANOUT NOT SHOWN ON BATH AND
 KITCHEN WITHIN 10 FT OF ENTERING BUILDING PER THE PER
 THE 2017 FBC 708.1.3 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION.
  
 7. SHEET P-1 UNIT 1 HAS A STACKABLE WASHER AND DRYER
 AND ACCESS TO SHUT OFF VALVE MUST BE REACHABLE WITHOUT
 MOVING THE UNIT PLEASE MAKE NOT ON PLANS PER THE 2017
 FBC SEC. P 606.3. ACCESSIBLE SIGNIFIES ACCESS THAT
 REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR
 REMOVABLE OBSTRUCTION.
  
 8. SHEET P-1 UNIT 1 AND OTHERS DO NOT HAVE A WASHING
 MACHINE HOOK ARE THEY IN A DIFFERENT LOCATION, PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-03-16 Cont ID  
Sent By jgomez Date 2021-03-16 Time 16:44 Rev Time 0.00
Received By jgomez Date 2021-03-16 Time 16:32 Sent To  
Notes
2021-03-16 16:51:381- HARD COPY ARCHITECTURAL AND STRUCTURAL DRAWINGS WITH
 ENGINEER'S ORIGINAL SEAL/SIGNATURE MATCHED APPROVED
 ONES. DRAWINGS UPLOADED TO PROJECTDOX (VERSIONED).
 DRAWINGS SENT TO STORAGE. JG.
  
 2- ON 03/16/21 CONTRACTOR UPLOADED IN THE "SIGNATURE"
 FOLDER THE ELECTRICAL, PLUMBING AND MECHANICAL DRAWINGS
 MISSING THE DIGITAL SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-03-15 Cont ID  
Sent By jgomez Date 2021-03-15 Time 13:27 Rev Time 0.00
Received By jgomez Date 2021-03-15 Time 09:03 Sent To  
Notes
2021-03-15 13:39:031- NONE OF THE MECHANICAL PLANS HAVE THE SEAL/SIGNATURE
 OF THE ENGINEER OF RECORD. NEED TO UPLOAD ALL THE
 MECHANICAL DRAWINGS WITH THE ENGINEER'S DIGITAL
 SIGNATURE TO PROJECTDOX. NOTE: IT LOOKS LIKE THIS
 ENGINEER HAS A DIGITAL SIGNATURE. PLUMBING AND
 ELECTRICAL PLANS DONE BY SAME ENGINEER HAVE THE DIGITAL
 SIGNATURE.
  
 2- ELECTRICAL DRAWINGS E-2, E-3, E-4, E-5 AND E-7 NEED
 THE ENGINEER'S DIGITAL SIGNATURE. NEED TO UPLOAD THESE
 DRAWINGS WITH THE ENGINEER'S DIGITAL SIGNATURE TO
 PROJECTDOX.
  
  
 3- PLUMBING DRAWINGS P-3, P-5, P-6, P-7, P-8, P-9 AND
 P-10 NEED THE ENGINEER'S DIGITAL SIGNATURE. NEED TO
 UPLOAD THESE DRAWINGS WITH THE ENGINEER'S DIGITAL
 SIGNATURE TO PROJECTDOX.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-03-12 Cont ID  
Sent By rmcdouga Date 2021-03-12 Time 12:46 Rev Time 0.00
Received By rmcdouga Date 2021-03-12 Time 12:46 Sent To  
Notes
2021-03-12 12:50:10THE ARCHITECTURAL AND STRUCTURAL PLANS ARE NOT SIGNED
 AND SEALED BY AN ARCHITECT OR ENGINEER AS REQUIRED.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-02-25 Cont ID  
Sent By rmcdouga Date 2021-02-25 Time 11:39 Rev Time 0.00
Received By rmcdouga Date 2021-02-25 Time 11:39 Sent To  
Notes
2021-02-25 11:39:38ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT'S OR ENGINEER'S DIGITAL SIGNATURE ON
 THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS.
 NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 471 & 61G15, FS481 & 61G1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-12-10 Cont ID  
Sent By rmcdouga Date 2020-12-10 Time 14:57 Rev Time 0.00
Received By rmcdouga Date 2020-12-10 Time 14:57 Sent To  
Notes
2020-12-10 14:59:47PLANS ARE NOT SIGNED AND SEALED BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-06-03 Cont ID  
Sent By rmcdouga Date 2020-06-03 Time 14:31 Rev Time 0.00
Received By rmcdouga Date 2020-06-03 Time 14:31 Sent To  
Notes
2020-06-03 14:32:51NO DOCUMENTS FROM AN ARCHITECT OR ENGINEER WERE
 SUBMITTED.

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-02 Cont ID  
Sent By fmittner Date 2021-03-02 Time 10:46 Rev Time 0.00
Received By fmittner Date 2021-03-02 Time 10:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By fmittner Date 2020-12-07 Time 11:38 Rev Time 0.00
Received By fmittner Date 2020-12-07 Time 11:38 Sent To  
Notes
2020-12-07 11:38:42NEED SITE PLAN SHOWING PARKING
 NEED LANDSCAPE PLAN SUBMITTED AS SEPARATE PERMIT