2020-06-08 15:02:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050552 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) ON THE APPLICATION IT INDICATES THAT YOU ARE |
| INSTALLING AN ENTIRELY NEW GAS SYSTEM AT THIS |
| RESIDENCE. PLEASE REMOVE THE WORD EXISTING FROM THE GAS |
| LINE PIPING RISER DIAGRAM. FBC FS 107.2.1 |
| |
| 2) PLEASE PROVIDE A DRAWING WITH THE SHUT OFFS, UNION |
| FITTINGS, DRIP LEGS, VENTING OF INDOOR REGULATORS. |
| PLEASE SHOW THAT EACH HAVE A WAY OF ACCESSING EACH. FBC |
| FS 107.2.1 |
| |
| 3) IS ANY OF THIS NEW PIPING SYSTEM INSTALLED INDOORS |
| UNDERGROUND? FBC RES G2415.14 |
| |
| 4) PLEASE PROVIDE SPECS ON THE GENERATOR AND FLEXIBLE |
| GAS LINE CONNECTING THE GENERATOR TO THE GAS LINE. FBC |
| FS 107.2.1 |
| |
| 5) THIS APPEARS TO BE A 2PSI SYSTEM WITH MP REGULATORS |
| ALONG THE PIPING SYSTEM TO REDUCE PRESSURE TO EACH |
| APPLIANCE. PLEASE PROVIDE THE LONGEST LENGTH TO THE |
| MOST REMOTE APPLIANCE (WHICH APPEARS TO BE THE NEW |
| TANKLESS WATER HEATER) ON THE 2LB SYSTEM. PLEASE ALSO |
| SHOW WHERE THE PIPING MATERIAL CHANGES FROM PE TO GALV. |
| GOING TO THE WATER HEATER. FBC FS 107.2.1 |
| |
| 6) PLEASE SHOW THE REGULATOR LOCATION FOR THE WATER |
| HEATER. FBC RES G2421.1 |
| |
| 7) PLEASE SHOW DISTANCE FROM THE METER TO THE ?? JOINT |
| FOR THE EXISTING PE FOR THE INTERIOR. FBC FS 107.2.1 |
| |
| 8) PLEASE PROVIDE THE CONCRETE SLAB DETAIL DRAWING AND |
| THE TIE DOWN SYSTEM FOR THE GENERATOR. FBC FS 107.2.1 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |