Plan Review Details - Permit 20050733
Plan Review Stops For Permit 20050733
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-06-19 Cont ID  
Sent By shill Date 2020-06-19 Time 07:36 Rev Time 0.00
Received By shill Date 2020-06-19 Time 07:36 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-06-18 Cont ID  
Sent By shill Date 2020-06-18 Time 16:00 Rev Time 0.00
Received By shill Date 2020-06-18 Time 16:00 Sent To  
Notes
2020-06-18 16:00:43LETTER RECEIVED HAS LANGUAGE NOT CONSISTENT WITH THE
 ACKNOWLEDGEMENT REQUESTED IN PREVIOUS PLAN REVIEW,
 REQUESTED THAT IT BE REVISED

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By jwitmer Date 2020-06-09 Time 15:34 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-06-09 15:34:37PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2020-06-09 Time 15:30 Rev Time  
Received By   Date 2020-06-09 Time 15:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-18 Cont ID  
Sent By jleahy Date 2020-06-18 Time 13:14 Rev Time 0.00
Received By jleahy Date 2020-06-18 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-06-03 Cont ID  
Sent By pleduc Date 2020-06-03 Time   Rev Time 0.00
Received By pleduc Date 2020-06-02 Time 12:03 Sent To  
Notes
2020-06-03 13:37:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 2) DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 3) THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 4) WITH ANY REMOVAL OF WALLS, ENSURE CODE COMPLIANT
 SPRINKLER HEAD COVERAGE IS MAINTAINED.
  
 ANY REQUIRED FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-30 Cont ID  
Sent By lmarchan Date 2020-06-30 Time 08:40 Rev Time 0.00
Received By lmarchan Date 2020-06-30 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-06-25 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-01 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-06-25 Cont ID  
Sent By ccole Date 2020-06-25 Time 11:07 Rev Time 0.00
Received By ccole Date 2020-06-25 Time 10:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-29 Cont ID  
Sent By shill Date 2020-06-29 Time 08:51 Rev Time 0.00
Received By shill Date 2020-06-29 Time 08:51 Sent To  
Notes
2020-06-29 08:52:36PAPER ORIGINAL RECEIVED
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By ccole Date 2020-06-25 Time 11:07 Rev Time 0.00
Received By ccole Date 2020-06-25 Time 11:07 Sent To  
Notes
2020-06-25 11:09:56 
 THE PLAN REQUIRES AN ELECTRONIC SEAL AND SIGNATURE BY
 THE ARCHITECT OF RECORD- FL STATUTE 481.221 AND SECTION
 61G-16.005 FLORIDA ADMINISTRATIVE CODE.
  
  
  