Plan Review Details - Permit 20050724
Plan Review Stops For Permit 20050724
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2020-07-23 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-29 Cont ID  
Sent By rmcdouga Date 2020-06-29 Time 12:52 Rev Time 0.00
Received By rmcdouga Date 2020-06-29 Time 12:44 Sent To  
Notes
2020-06-29 12:52:41PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW: THE PREVIOUS
 REVIEW COMMENT WAS NOT ADDRESSED.
  
 1) PROVIDE DETAILS FOR THE EXISTING CONCRETE GENERATOR
 SLAB WITH GENERATOR TO SLAB ANCHORING DETAILS. IF IT IS
 A PREFABRICATED PLAN IT MUST BE COMPATIBLE WITH THE NEW
 GENERATOR OR BE REPLACED. FBC 107

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-26 Cont ID  
Sent By rmcdouga Date 2020-05-26 Time 13:48 Rev Time 0.00
Received By rmcdouga Date 2020-05-26 Time 13:48 Sent To  
Notes
2020-05-26 13:51:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE DETAILS FOR THE EXISTING CONCRETE GENERATOR
 SLAB WITH GENERATOR TO SLAB ANCHORING DETAILS. IF IT IS
 A PREFABRICATED PLAN IT MUST BE COMPATIBLE WITH THE NEW
 GENERATOR OR BE REPLACED. FBC 107

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 16:07 Rev Time 0.00
Received By jleahy Date 2020-07-13 Time 16:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-08 Cont ID  
Sent By jleahy Date 2020-06-08 Time 14:48 Rev Time 0.00
Received By jleahy Date 2020-06-08 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2020-07-14 Time 08:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 16:15 Rev Time 0.00
Received By jleahy Date 2020-06-24 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-08 Cont ID  
Sent By jleahy Date 2020-06-08 Time 14:48 Rev Time 0.00
Received By jleahy Date 2020-05-21 Time 15:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2020-07-23 Time 13:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 16:08 Rev Time 0.00
Received By jleahy Date 2020-07-13 Time 16:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-08 Cont ID  
Sent By jleahy Date 2020-06-08 Time 14:48 Rev Time 0.00
Received By jleahy Date 2020-06-08 Time 14:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By Kalexand Date 2020-07-08 Time   Rev Time 0.00
Received By   Date 2020-07-08 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By kalexand Date 2020-06-02 Time   Rev Time  
Received By kalexand Date 2020-06-02 Time   Sent To I
Notes
2020-06-02 12:07:33ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 6/2/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SURVEY INDICATING LOCATION OF
 GENERATOR AND PROPER SETBACKS.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved