Plan Review Details - Permit 20050706
Plan Review Stops For Permit 20050706
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By jwitmer Date 2020-09-21 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2020-09-21 Time 16:19 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-06-01 Cont ID  
Sent By jwitmer Date 2020-06-01 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2020-06-01 Time 07:59 Sent To  
Notes
2020-06-01 08:00:54ASBESTOS COMMERCIAL.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-21 Cont ID  
Sent By jwitmer Date 2020-09-21 Time 16:44 Rev Time 0.00
Received By jwitmer Date 2020-09-21 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By jwitmer Date 2020-07-13 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2020-07-13 Time 09:02 Sent To  
Notes
2020-07-12 21:08:35IN REVIEW. 07/13/2020 J. WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-06-01 Cont ID  
Sent By jwitmer Date 2020-06-01 Time 08:55 Rev Time 0.00
Received By jwitmer Date 2020-06-01 Time 07:59 Sent To  
Notes
2020-06-01 08:54:58BUILDING PROVISO:
 SHEET A2.1.1 DETAIL 1
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL
 BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE
 GRIPPING SURFACE, NOT CENTERLINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-23 Cont ID  
Sent By fgiaquin Date 2020-07-23 Time 23:04 Rev Time 0.00
Received By fgiaquin Date 2020-07-23 Time 22:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-08 Cont ID  
Sent By jpearson Date 2020-06-08 Time 15:04 Rev Time 0.00
Received By jpearson Date 2020-06-08 Time 14:51 Sent To  
Notes
2020-06-08 15:08:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL 11LA IS SHOWN AS A 150 AMP PANEL WITH OVER 200
 AMPS PER PHASE. PROVIDE CLARIFICAITON AND/OR
 CORRECTIONS. NEC 310.15, 408.30; WPB FBC 107.2.1
 2. PROVIDE RISER DIARAM OF EXISTING SERVICE TO THIS
 FLOOR. NEC 215.5; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By pleduc Date 2020-09-22 Time   Rev Time 0.00
Received By pleduc Date 2020-09-22 Time 11:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-07-09 Cont ID  
Sent By pleduc Date 2020-07-09 Time   Rev Time 0.00
Received By pleduc Date 2020-07-09 Time 10:19 Sent To  
Notes
2020-07-09 10:23:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-05-22 Cont ID  
Sent By pleduc Date 2020-05-22 Time   Rev Time 0.00
Received By pleduc Date 2020-05-22 Time 13:12 Sent To  
Notes
2020-05-22 13:38:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-22 Cont ID  
Sent By ccarvaja Date 2020-09-22 Time 12:10 Rev Time 0.00
Received By ccarvaja Date 2020-09-18 Time 06:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-23 Cont ID  
Sent By fgiaquin Date 2020-07-23 Time 23:04 Rev Time 0.00
Received By fgiaquin Date 2020-07-08 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-25 Cont ID  
Sent By shill Date 2020-06-25 Time 09:30 Rev Time 0.00
Received By shill Date 2020-05-21 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-06-01 Cont ID  
Sent By medwards Date 2020-06-01 Time 14:16 Rev Time 0.00
Received By medwards Date 2020-06-01 Time 13:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-23 Cont ID  
Sent By jesmith Date 2020-07-23 Time 11:53 Rev Time 0.00
Received By jesmith Date 2020-07-23 Time 11:43 Sent To  
Notes
2020-07-23 11:53:0820050706 505 S FLAGLER DR FL 11
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By jesmith Date 2020-06-25 Time 09:29 Rev Time 0.00
Received By shill Date 2020-06-25 Time 09:12 Sent To  
Notes
2020-06-25 09:30:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050706 505 S FLAGLER DR FL 11
  
 PLUMBING COMMENTS: DENIED
 PLAN SHEET PO.1 INDICATES A TANKLESS WATER HEATER ABOVE
 THE CEILING TO PROVIDE HOT WATER TO LAVATORY. THE RISER
 DIAGRAM SHOWS A VALVED DEDICATED HOT WATER LINE FROM
 DISTRIBUTION TO SUPPLY THE LAVATORIES. PER WPB FBC
 107.2.1, CLARIFY.
  
 PROVISO:
 RE: PLAN SHEET A2.1.1PER FBC ACC 609.4, GRAB BARS SHALL
 BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20050706 505 S FLAGLER DR FL 11
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-21 Cont ID  
Sent By jwitmer Date 2020-09-21 Time 16:43 Rev Time 0.00
Received By jwitmer Date 2020-09-21 Time 16:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-23 Cont ID  
Sent By jesmith Date 2020-07-23 Time 12:19 Rev Time 0.00
Received By jesmith Date 2020-07-23 Time 12:13 Sent To  
Notes
2020-07-23 12:19:37PLAN SHEETS CVR AND A2.1.1 REQUIRE DIGITAL SIGNATURES

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-01 Cont ID  
Sent By medwards Date 2020-06-01 Time 14:23 Rev Time 0.00
Received By medwards Date 2020-06-01 Time 14:19 Sent To  
Notes
***NONE***