Plan Review Stops For Permit 20050699 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
N |
Date |
2020-07-13 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-13 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2020-07-13 14:40:11 | GENERATOR LOCATED INSIDE A PERMITTED BUILDING ADDITION | | - ALREADY APPROVED SHOWING A GENERATOR - UNDER PERMIT | | NUMBER 19110910 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-07-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-10 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-09 |
Time |
15:34 |
Sent To |
|
|
Notes |
2020-07-10 10:23:53 | REVISION TO 19110910 | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) NEED A BUILDING PERMIT APPLICATION FILLED OUT FOR | | THE REVISION SHOWING THE ADDITIONAL JOB COST. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
N |
Date |
2020-06-11 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-06-11 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-06-11 |
Time |
12:50 |
Sent To |
|
|
Notes |
2020-06-11 13:00:35 | BUILDING THAT HOUSES THE GENERATOR - APPROVED ON PERMIT | | NUMBER 19110910 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2020-07-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-07-09 |
Time |
19:16 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-07-09 |
Time |
19:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2020-06-22 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-06-22 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-06-20 |
Time |
10:05 |
Sent To |
|
|
Notes |
2020-06-22 08:47:20 | VALUE OF PERMIT IS LOW FOR THIS SIZE GENERATOR (41,000) | | | | PLEASE SUBMIT A SIGNED CONTRACT FOR WORK INVOLVED. | | | | SEE FIRST ELECTRICAL REVIEW JLEAHY |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-06-10 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-06-10 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-06-09 |
Time |
11:37 |
Sent To |
|
|
Notes |
2020-06-10 15:32:11 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | PART VIII ELECTRICAL | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | VALUE OF PERMIT IS LOW FOR A 90KW GENERATOR AND | | TRANSFER SWITCH. PLEASE SUBMIT A SIGNED CONTRACT FOR | | THE WORK INVOLVED. (41,000) | | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2020-05-27 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-05-27 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-05-27 |
Time |
11:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-07-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-10 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-02 |
Time |
11:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-06-29 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2020-06-29 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2020-06-16 |
Time |
15:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-06-11 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-06-11 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-05-22 |
Time |
14:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2020-06-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-06-21 |
Time |
17:49 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-06-21 |
Time |
17:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-06-03 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-06-03 |
Time |
08:18 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-06-02 |
Time |
15:05 |
Sent To |
|
|
Notes |
2020-06-03 08:19:16 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT -20050699 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) MASTER PERMIT 19110910 SHEET M-1 SPECS L2 AND L3 | | LOUVERS IN THE GENERATOR ROOM TO BE 80X48. SHEET E10 | | ?GENERATOR ROOM DETAIL? CALLS FOR THE EXHAUST LOUVER TO | | BE 108X108. PLEASE CLARIFY THIS FOR BOTH PROJECTS. FBC | | FS 107.2.1 | | | | 2) PLEASE PROVIDE CALCULATIONS FOR THE COMBUSTION AIR | | NEEDED FOR THIS GENERATOR AND THE MINIMUM SIZE OUTDOOR | | OPENING. FBC FG 304.6 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-07-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-10 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-10 |
Time |
10:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-06-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-06-21 |
Time |
17:56 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-06-21 |
Time |
17:55 |
Sent To |
|
|
Notes |
2020-06-21 17:57:44 | DESIGNER MUST DIGITALLY SIGN AND SEAL SHEETS S1, S3, | | S3A |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-06-03 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-06-03 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-06-03 |
Time |
08:19 |
Sent To |
|
|
Notes |
2020-06-03 08:21:39 | DESIGNER MUST SIGN AND SEAL THE DRAWINGS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2020-06-23 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2020-06-23 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-06-02 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2020-06-02 |
Time |
|
Rev Time |
|
Received By |
kalexand |
Date |
2020-06-02 |
Time |
|
Sent To |
I |
|
Notes |
2020-06-02 12:12:46 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 6/2/20 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PLEASE PROVIDE A SURVEY INDICATING THE LOCATION OF | | THE GENERATORS WITH PROPER SETBACK REQUIREMENTS. | | | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST | | THAT IT BE SENT TO YOU BY EMAILING [email protected] | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | KIZZI ALEXANDRE, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1442 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|