Plan Review Details - Permit 20050699
Plan Review Stops For Permit 20050699
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2020-07-13 Cont ID  
Sent By rmcphers Date 2020-07-13 Time 14:37 Rev Time 0.00
Received By rmcphers Date   Time   Sent To  
Notes
2020-07-13 14:40:11GENERATOR LOCATED INSIDE A PERMITTED BUILDING ADDITION
 - ALREADY APPROVED SHOWING A GENERATOR - UNDER PERMIT
 NUMBER 19110910

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-10 Cont ID  
Sent By rmcphers Date 2020-07-10 Time 10:07 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 15:34 Sent To  
Notes
2020-07-10 10:23:53REVISION TO 19110910
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEED A BUILDING PERMIT APPLICATION FILLED OUT FOR
 THE REVISION SHOWING THE ADDITIONAL JOB COST.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2020-06-11 Cont ID  
Sent By rmcphers Date 2020-06-11 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2020-06-11 Time 12:50 Sent To  
Notes
2020-06-11 13:00:35BUILDING THAT HOUSES THE GENERATOR - APPROVED ON PERMIT
 NUMBER 19110910

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-07-09 Cont ID  
Sent By jleahy Date 2020-07-09 Time 19:16 Rev Time 0.00
Received By jleahy Date 2020-07-09 Time 19:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-22 Cont ID  
Sent By jleahy Date 2020-06-22 Time 08:45 Rev Time 0.00
Received By jleahy Date 2020-06-20 Time 10:05 Sent To  
Notes
2020-06-22 08:47:20VALUE OF PERMIT IS LOW FOR THIS SIZE GENERATOR (41,000)
  
 PLEASE SUBMIT A SIGNED CONTRACT FOR WORK INVOLVED.
  
 SEE FIRST ELECTRICAL REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-10 Cont ID  
Sent By jleahy Date 2020-06-10 Time 15:18 Rev Time 0.00
Received By jleahy Date 2020-06-09 Time 11:37 Sent To  
Notes
2020-06-10 15:32:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE OF PERMIT IS LOW FOR A 90KW GENERATOR AND
 TRANSFER SWITCH. PLEASE SUBMIT A SIGNED CONTRACT FOR
 THE WORK INVOLVED. (41,000)
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-05-27 Cont ID  
Sent By pleduc Date 2020-05-27 Time   Rev Time 0.00
Received By pleduc Date 2020-05-27 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-10 Cont ID  
Sent By rmcphers Date 2020-07-10 Time 10:24 Rev Time 0.00
Received By rmcphers Date 2020-07-02 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-29 Cont ID  
Sent By cpuell Date 2020-06-29 Time 10:06 Rev Time 0.00
Received By cpuell Date 2020-06-16 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-11 Cont ID  
Sent By rmcphers Date 2020-06-11 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2020-05-22 Time 14:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-06-21 Cont ID  
Sent By medwards Date 2020-06-21 Time 17:49 Rev Time 0.00
Received By medwards Date 2020-06-21 Time 17:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-06-03 Cont ID  
Sent By medwards Date 2020-06-03 Time 08:18 Rev Time 0.00
Received By medwards Date 2020-06-02 Time 15:05 Sent To  
Notes
2020-06-03 08:19:161ST REVIEW FBC-2017 MECHANICAL
 PERMIT -20050699
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MASTER PERMIT 19110910 SHEET M-1 SPECS L2 AND L3
 LOUVERS IN THE GENERATOR ROOM TO BE 80X48. SHEET E10
 ?GENERATOR ROOM DETAIL? CALLS FOR THE EXHAUST LOUVER TO
 BE 108X108. PLEASE CLARIFY THIS FOR BOTH PROJECTS. FBC
 FS 107.2.1
  
 2) PLEASE PROVIDE CALCULATIONS FOR THE COMBUSTION AIR
 NEEDED FOR THIS GENERATOR AND THE MINIMUM SIZE OUTDOOR
 OPENING. FBC FG 304.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-10 Cont ID  
Sent By rmcphers Date 2020-07-10 Time 10:06 Rev Time 0.00
Received By rmcphers Date 2020-07-10 Time 10:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-06-21 Cont ID  
Sent By medwards Date 2020-06-21 Time 17:56 Rev Time 0.00
Received By medwards Date 2020-06-21 Time 17:55 Sent To  
Notes
2020-06-21 17:57:44DESIGNER MUST DIGITALLY SIGN AND SEAL SHEETS S1, S3,
 S3A

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-03 Cont ID  
Sent By medwards Date 2020-06-03 Time 08:20 Rev Time 0.00
Received By medwards Date 2020-06-03 Time 08:19 Sent To  
Notes
2020-06-03 08:21:39DESIGNER MUST SIGN AND SEAL THE DRAWINGS.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By kalexand Date 2020-06-23 Time   Rev Time 0.00
Received By   Date 2020-06-23 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By kalexand Date 2020-06-02 Time   Rev Time  
Received By kalexand Date 2020-06-02 Time   Sent To I
Notes
2020-06-02 12:12:46ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 6/2/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SURVEY INDICATING THE LOCATION OF
 THE GENERATORS WITH PROPER SETBACK REQUIREMENTS.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  