Plan Review Details - Permit 20050603
Plan Review Stops For Permit 20050603
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By jwitmer Date 2020-06-29 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2020-06-29 Time 08:04 Sent To  
Notes
2020-06-29 08:54:312017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050603
 ADD: 3507 BROADWAY
 CONT: RG & VC GENERAL CONTRACTING
 TEL: 561-667-2065
 E-MAIL: CONSTRUCTION [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 29TH/ 2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES UNDER THE HEADING
 TRADES ADDITIONAL PARKING AND FA?ADE RENOVATIONS. THE
 HEADING FOR DISCERPTION OF WORK WAS LEFT BLANK. THE
 ONLY PARKING SPACES ARE SHOWN ON THE SURVEY/ SITE PLAN.
 THERE IS NO NOTATION OF WHAT ADDITIONAL PARKING IS TO
 TAKE PLACE. THE SURVEY/ SITE PLAN DOES NOT SHOW THE
 REQUIRED STRIPING OF THE PARKING LOT.
 ACCESSIBLE PARKING SPACE / STALL PAINTING. 2017
 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES. EACH
 PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL BE
 MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN ADJACENT
 ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 2A) SHEET A-1 SHOWS A DETAIL FOR THE INSTALLATION OF
 HARDIE-PLANK SIDING. PLEASE PROVIDE THE PRODUCT
 APPROVAL FOR THIS SYSTEM EITHER A MIAMI-DADE NOA OR
 FLORIDA PRODUCT APPROVAL.
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(C) PANEL WALLS: HARDIE-PLANK WALL SYSTEMS, WALL
 LOUVERS, EFIS SYSTEMS,
  
 2B) WITHIN THE PRODUCT APPROVAL PLEASE CIRCLE THE TYPE
 OF SUB-SYSTEM, INSTALLATION SYSTEM INTO SUBSTRATE,
 ANCHOR LENGTH & SPACING AND ASSOCIATED PRESSURES.
  
 2C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE
 PRODUCT APPROVAL. 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 4) SHEET A2 & A3 BOTH SHOW A PROPOSED ALUMINUM GATE
 &FENCE/ PANEL SYSTEM. NO DESIGN CRITERIA WAS GIVEN FOR
 THE PANEL SYSTEM, POST SIZE SQUARE OR ROUND, DEPTH OF
 POST IN THE GROUND, ANCHORING OF POST, NO INFORMATION
 ON THE GATE AND LATCHING SYSTEM. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-29 Cont ID  
Sent By ccarvaja Date 2020-06-29 Time 10:20 Rev Time 0.00
Received By ccarvaja Date 2020-06-23 Time 11:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By jwitmer Date 2020-06-29 Time 08:55 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By llouie Date 2020-06-25 Time   Rev Time  
Received By llouie Date 2020-06-25 Time   Sent To  
Notes
2020-06-25 15:22:18** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) AN UPDATED, SIGNED AND SEALED SURVEY BY A FLORIDA
 REGISTERED LAND SURVEYOR IS MISSING FROM THE PERMIT
 SUBMITTAL.
  
 2.) CLARIFY THE SCOPE OF WORK IN THE PERMIT
 APPLICATION. THE SCOPE INDICATES PARKING AREA
 IMPROVEMENTS; ADDITIONALLY, THE PROPOSED 6 FT. HIGH
 FENCE/WALL TO THE EAST AND WEST SIDES OF THE PROJECT
 AND THE REMOVAL OF THE EXISTING SIDEWALK ALONG THE EAST
 SIDE OF THE BUILDING ARE NOT MENTIONED (ALTHOUGH
 DETECTED IN THE SITE PLAN). SEPARATE PERMITS ARE
 REQUIRED FOR SOME OF THESE IMPROVEMENTS.
  
 3.) SHOW EXTENT OF THE SIDEWALK REMOVAL TO EXTEND THE
 FOUNDATION PLANTING ALONG THE EAST SIDE OF THE
 BUILDING. A SITE PLAN SHOULD CLEARLY ILLUSTRATE THE
 PROPOSED LAYOUT FOR THE PROJECT.
  
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: PARKING AREA
 IMPROVEMENTS, INSTALLATION OF FENCE/GATE.
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * SCOPE OF WORK DOES NOT EXCEED 50% OF IMPROVEMENT
 VALUE (PAPA) OF THE EXISTING STRUCTURE.
  
 * Z = BMUD-TYPE I
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved