Plan Review Details - Permit 20050569
Plan Review Stops For Permit 20050569
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-26 Cont ID  
Sent By rmcdouga Date 2020-05-26 Time 13:42 Rev Time 0.00
Received By rmcdouga Date 2020-05-26 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 14:40 Rev Time 0.00
Received By cthroop Date 2020-07-06 Time 14:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-08 Cont ID  
Sent By jleahy Date 2020-06-08 Time 14:34 Rev Time 0.00
Received By jleahy Date 2020-06-08 Time 14:30 Sent To  
Notes
2020-06-08 14:40:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BU
  
 ILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO ELECTRICAL RISER DIAGRAM SHOWN. 215.5
  
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE. AND NEW
 EQUIPMENT NEC 215.5; FBC 107.2.1
  
 2) VALUE OF GENERATOR TRANSFER SWITCH AND LABOR IS LOW.
 PLEASE SUBMIT A SIGNED CONTRACT WITH THE OWNER.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3) PLAN WILL NEED TO BE SIGNED BY QUALIFIER.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 14:40 Rev Time 0.00
Received By cthroop Date 2020-07-06 Time 14:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-05 Cont ID  
Sent By medwards Date 2020-06-05 Time 14:54 Rev Time 0.00
Received By medwards Date 2020-06-05 Time 14:03 Sent To  
Notes
2020-06-05 14:54:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT -20050569
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS A SINGLE FAMILY RESIDENCE, PLEASE USE THE
 GAS TABLES REFERENCED IN CHAPTER 24 OF THE FBC RES
 CODE.
  
 2) PLEASE SHOW THE GAS PRESSURE AT THE METER ON THE
 DRAWING. FBC FS 107.2.1
  
 3) PLEASE PROVIDE SPECS FOR THE RV61 REGULATOR SHOWN ON
 THE DRAWING. FBC FS 107.2.1
  
 4) WHEN USING THE GAS TABLES IN THE RESIDENTIAL CODE
 PLEASE CHECK THE PRESSURE DROP OF THE SYSTEM ALONG WITH
 THE FLEX-HOSE REFERENCED ON THE DRAWING. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 14:40 Rev Time 0.00
Received By cthroop Date 2020-06-22 Time 14:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-08 Cont ID  
Sent By jleahy Date 2020-06-08 Time 14:41 Rev Time 0.00
Received By jleahy Date 2020-05-21 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 14:38 Rev Time 0.00
Received By cthroop Date 2020-07-06 Time 14:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-05 Cont ID  
Sent By medwards Date 2020-06-05 Time 14:56 Rev Time 0.00
Received By medwards Date 2020-06-05 Time 14:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 14:40 Rev Time 0.00
Received By cthroop Date 2020-07-06 Time 14:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-26 Cont ID  
Sent By rmcdouga Date 2020-05-26 Time 13:43 Rev Time 0.00
Received By rmcdouga Date 2020-05-26 Time 13:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-06-01 Cont ID  
Sent By rthermid Date 2020-06-01 Time   Rev Time  
Received By rthermid Date 2020-06-01 Time   Sent To I
Notes
***NONE***