Plan Review Details - Permit 20050544
Plan Review Stops For Permit 20050544
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-03 Cont ID  
Sent By pvalenti Date 2020-06-03 Time 09:11 Rev Time 0.00
Received By pvalenti Date 2020-06-03 Time 09:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-21 Cont ID  
Sent By rmcphers Date 2020-05-21 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2020-05-21 Time 09:17 Sent To  
Notes
2020-05-21 09:55:57ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS AND FASTENER TESTING FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL (-60) - SEE NOTE NUMBER 9 (ADDITIONAL
 ATTACHMENTS) AND NOTE NUMBER 11 (FASTENER TESTING) ON
 THE PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND
 DESIGN DATA USED PER 2017 FBC AND ASCE 7-10 - WIND
 SPEED - EXPOSURE - RISK CATEGORY - ETC.
  
 FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL
 SIGNATURE
 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-03 Cont ID  
Sent By pvalenti Date 2020-06-03 Time 09:18 Rev Time 0.00
Received By pvalenti Date 2020-06-03 Time 09:06 Sent To  
Notes
2020-06-03 08:25:00ROUTED TO PV DESK TO UPLOAD TO PROJECTDOX AND REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-21 Cont ID  
Sent By rmcphers Date 2020-05-21 Time 10:14 Rev Time 0.00
Received By rmcphers Date 2020-05-18 Time 15:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-03 Cont ID  
Sent By pvalenti Date 2020-06-03 Time 09:11 Rev Time 0.00
Received By pvalenti Date 2020-06-03 Time 09:06 Sent To  
Notes
2020-06-03 09:15:41PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED:
  
 THE CONTRACTOR PROVIDED ORIGINAL (PAPER) ENGINEER'S
 SIGNED/SEALED FASTENER SPACING LETTER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-21 Cont ID  
Sent By rmcphers Date 2020-05-21 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2020-05-21 Time 10:04 Sent To  
Notes
2020-05-21 10:14:06SEE BUILDING PLAN REVIEW