Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-23 Cont ID  
Sent By pvalenti Date 2020-07-23 Time 14:27 Rev Time 0.00
Received By pvalenti Date 2020-07-23 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By rmcdouga Date 2020-06-09 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2020-06-09 Time 16:17 Sent To  
Notes
2020-06-09 16:18:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A GENERATOR PAD DRAWING WITH GENERATOR TO PAD
 ANCHORING DETAILS. FBC 107

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-18 Cont ID  
Sent By jleahy Date 2020-06-18 Time 14:09 Rev Time 0.00
Received By jleahy Date 2020-06-18 Time 14:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By medwards Date 2020-07-24 Time 10:54 Rev Time 0.00
Received By medwards Date 2020-07-24 Time 10:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 10:19 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 10:19 Sent To  
Notes
2020-06-17 10:19:561ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050524
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS PLAN SHOWS AN EXISTING GAS METER, I CANNOT
 REVIEW THIS PROJECT UNTIL THE ENTIRE GAS SYSTEM HAS
 BEEN SUBMITTED. PLEASE SUBMIT A LEGIBLE DRAWING SHOWING
 GAS PRESSURE OF THE CURRENT EXISTING GAS SYSTEM, A
 HOUSE LAYOUT WITH THE GAS LINES SHOWN. PLEASE INCLUDE
 ALL REGULATORS AND SHUT OFF VALVES. PROVIDE THE SPECS
 FOR THE REGULATORS USED. PROVIDE PIPE SIZES, TYPE OF
 MATERIAL USED. PLEASE ALSO INCLUDE THE GAS TABLE NUMBER
 USED FOR EACH TYPE OF PIPING IN THIS SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-24 Cont ID  
Sent By lmarchan Date 2020-07-24 Time 10:57 Rev Time 0.00
Received By lmarchan Date 2020-07-23 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-18 Cont ID  
Sent By jleahy Date 2020-06-18 Time 14:12 Rev Time 0.00
Received By jleahy Date 2020-06-01 Time 16:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-24 Cont ID  
Sent By medwards Date 2020-07-24 Time 10:54 Rev Time 0.00
Received By medwards Date 2020-07-24 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 10:20 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 10:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By medwards Date 2020-07-24 Time 10:54 Rev Time 0.00
Received By medwards Date 2020-07-24 Time 10:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 10:21 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 10:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-06-08 Cont ID  
Sent By rthermid Date 2020-06-08 Time   Rev Time  
Received By rthermid Date 2020-06-08 Time   Sent To I
Notes
2020-06-08 10:25:06PASSED WITH THIS NOTE:
  
 PER THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT CODE - MECHANICAL EQUIPMENT SHALL NOT BE
 CLOSER THAN 4 FEET FROM SIDE PROPERTY LINE.