Plan Review Details - Permit 20050508
Plan Review Stops For Permit 20050508
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-04 Cont ID  
Sent By jgomez Date 2020-09-04 Time 15:04 Rev Time 0.00
Received By jgomez Date 2020-09-04 Time 14:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-26 Cont ID  
Sent By jgomez Date 2020-06-26 Time 09:58 Rev Time 0.00
Received By jgomez Date 2020-06-26 Time 09:43 Sent To  
Notes
2020-06-26 10:04:48RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R23
 SUBMITTED:
 A) SELECTED ASSEMBLY W-62 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY NOTE #9
 ON PAGE 3 OF 67 OF PRODUCT APPROVAL SUBMITTED. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-23 Cont ID  
Sent By pvalenti Date 2020-06-23 Time 08:18 Rev Time 0.00
Received By pvalenti Date 2020-06-22 Time 16:22 Sent To  
Notes
2020-06-23 08:22:03PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107, PROVIDE ENGINEER'S SIGNED AND SEALED LETTER
 WITH CALCULATIONS SHOWING THE REQUIRED FASTENER SPACING
 FOR THE CORNER ZONES.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-09-04 Cont ID  
Sent By aborngra Date 2020-09-04 Time 14:09 Rev Time 0.00
Received By aborngra Date 2020-09-04 Time 14:09 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-06-18 Cont ID  
Sent By aborngra Date 2020-06-18 Time 16:25 Rev Time 0.00
Received By aborngra Date 2020-06-18 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-04 Cont ID  
Sent By jgomez Date 2020-09-04 Time 15:04 Rev Time 0.00
Received By jgomez Date 2020-09-02 Time 16:56 Sent To I
Notes
2020-09-02 16:47:33ROUTED TO ZONING BIN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-26 Cont ID  
Sent By jgomez Date 2020-06-26 Time 10:04 Rev Time 0.00
Received By jgomez Date 2020-06-25 Time 17:05 Sent To I
Notes
2020-06-25 17:05:32ROUTED TO ROOFING BIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-23 Cont ID  
Sent By pvalenti Date 2020-06-23 Time 08:22 Rev Time 0.00
Received By pvalenti Date 2020-06-18 Time 15:36 Sent To  
Notes
2020-06-18 15:36:39ROUTED TO HISTORIC