Plan Review Details - Permit 20050502
Plan Review Stops For Permit 20050502
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-19 Cont ID  
Sent By rmcdouga Date 2020-08-19 Time 07:27 Rev Time 0.00
Received By rmcdouga Date 2020-08-19 Time 07:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By cthroop Date 2020-08-03 Time 14:29 Rev Time 0.00
Received By rmcdouga Date 2020-08-03 Time 14:29 Sent To  
Notes
2020-08-03 14:36:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 COMMENTS FOR THE PREVIOUS REVIEW WERE NOT ADDRESSED.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 FBC 107
 1) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED IS
 NOT ACCEPTABLE FOR THE FOLLOWING REASONS:
 A) THE SCHEDULE ON THE DRAWINGS SPECIFIES THE REQUIRED
 MINIMUM WEIGHT FOR THE 22KW GENERATOR AS 466 LBS. AND
 THE SPECIFICATIONS FOR YOUR GENERATOR HAS A WEIGHT OF
 445 LBS.
 B) THE SCHEDULE ON THE DRAWINGS SPECIFIES THE ALLOWABLE
 WIND LOAD PRESSURES FOR THE GENERATOR, BUT THE REQUIRED
 WIND LOAD PRESSURES FOR THE SITE IT WILL BE INSTALLED
 ARE NOT PROVIDED. SEE GENERAL NOTE #2 ON THE DRAWING
 THAT STATES THAT THE REQUIRED PRESSURES FOR THE SITE OR
 TO BE DETERMINED BY OTHERS.
2020-08-03 14:31:30PLAN REVIEW GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 GENERATOR PAD
  
 1) STRUCTURAL DETAIL OF THE PRE-CAST GENERATOR PAD
 SHALL HAVE A VALID DIGITAL SIGNATURE OF THE DESIGN
 PROFESSIONAL PER FS 471 & FAC 61G15.
 2) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR WITH A
 VALID DIGITAL SIGNATURE OF THE DESIGN PROFESSIONAL AS
 REQUIRED FOR THE GENERATOR PAD ENGINEERING PER FBC
 107.3.5.3 AND R301.2.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By rmcdouga Date 2020-06-09 Time 16:13 Rev Time 0.00
Received By rmcdouga Date 2020-06-09 Time 16:13 Sent To  
Notes
2020-06-09 16:15:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A GENERATOR PAD DRAWING WITH GENERATOR TO PAD
 ANCHORING DETAILS. FBC 107

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-19 Cont ID  
Sent By jleahy Date 2020-06-19 Time 14:19 Rev Time 0.00
Received By jleahy Date 2020-06-19 Time 08:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-07-31 Cont ID  
Sent By lcrespo Date 2020-07-31 Time 13:24 Rev Time 0.00
Received By lcrespo Date 2020-07-31 Time 13:24 Sent To  
Notes
2020-07-31 13:24:1507/31/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 12:45 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 12:45 Sent To  
Notes
2020-06-17 12:47:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050502
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS AN EXISTING GAS METER, I CANNOT REVIEW THIS
 PROJECT UNTIL THE ENTIRE GAS SYSTEM HAS BEEN SUBMITTED.
 PLEASE SUBMIT A LEGIBLE DRAWING SHOWING GAS PRESSURE OF
 THE CURRENT EXISTING GAS SYSTEM, A HOUSE LAYOUT WITH
 THE GAS LINES SHOWN. PLEASE INCLUDE ALL REGULATORS AND
 SHUT OFF VALVES. PROVIDE THE SPECS FOR THE REGULATORS
 USED. PROVIDE PIPE SIZES, TYPE OF MATERIAL USED. PLEASE
 ALSO INCLUDE THE GAS TABLE NUMBER USED FOR EACH TYPE OF
 PIPING IN THIS SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-19 Cont ID  
Sent By rmcdouga Date 2020-08-19 Time 07:27 Rev Time 0.00
Received By rmcdouga Date 2020-08-10 Time 10:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-03 Cont ID  
Sent By cthroop Date 2020-08-03 Time 14:32 Rev Time 0.00
Received By cthroop Date 2020-07-23 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-19 Cont ID  
Sent By jleahy Date 2020-06-19 Time 14:19 Rev Time 0.00
Received By jleahy Date 2020-06-01 Time 16:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-31 Cont ID  
Sent By lcrespo Date 2020-07-31 Time 13:24 Rev Time 0.00
Received By lcrespo Date 2020-07-31 Time 13:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-18 Cont ID  
Sent By medwards Date 2020-06-18 Time 11:52 Rev Time 0.00
Received By medwards Date 2020-06-18 Time 11:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-13 Cont ID  
Sent By jgomez Date 2020-08-13 Time 14:48 Rev Time 0.00
Received By jgomez Date 2020-08-13 Time 14:48 Sent To  
Notes
2020-08-13 14:48:45ENGINEER DRAWING MATCHES ONE UPLOADED TO PROJECTDOX.
 CONCRETE PAD ENGINEERING DRAWING WITH EMBOSSED SEAL AND
 ORIGINAL SIGNATURE SENT TO STORAGE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By rmcdouga Date 2020-08-03 Time 14:30 Rev Time 0.00
Received By cthroop Date 2020-08-03 Time 14:27 Sent To  
Notes
2020-08-03 14:32:22PLAN REVIEW GENERATOR - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) DESIGN PROFESSIONALS DIGITAL SIGNATURE IS REQUIRED
 ON ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC
 61G15
  
 2) DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 3) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 4) FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
 NOTE: YOU MAY PROVIDE A PAPER PLAN WITH WET SIGNATURE
 AND SEAL PRIOR TO PERMIT.
  
  
2020-08-03 14:31:22THE PREFAB GENERATOR PAD DRAWINGS ARE NOT DIGITALLY
 SIGNED BY THE ENGINEER. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 PAPER DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-18 Cont ID  
Sent By medwards Date 2020-06-18 Time 11:51 Rev Time 0.00
Received By medwards Date 2020-06-18 Time 11:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-06-11 Time   Rev Time  
Received By   Date 2020-06-11 Time   Sent To I
Notes
***NONE***