Plan Review Details - Permit 20050500
Plan Review Stops For Permit 20050500
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By rmcdouga Date 2020-07-20 Time 13:00 Rev Time 0.00
Received By rmcdouga Date 2020-07-20 Time 13:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By rmcdouga Date 2020-06-09 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2020-06-09 Time 15:48 Sent To  
Notes
2020-06-09 15:50:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. FBC 107

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-18 Cont ID  
Sent By jleahy Date 2020-06-18 Time 14:34 Rev Time 0.00
Received By jleahy Date 2020-06-18 Time 14:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By tklarge Date 2020-06-25 Time 07:53 Rev Time 0.00
Received By tklarge Date 2020-06-25 Time 07:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 11:04 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 11:04 Sent To  
Notes
2020-06-17 11:07:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050500
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS PLAN SHOWS AN EXISTING GAS METER, I CANNOT
 REVIEW THIS PROJECT UNTIL THE ENTIRE GAS SYSTEM HAS
 BEEN SUBMITTED. PLEASE SUBMIT A LEGIBLE DRAWING SHOWING
 GAS PRESSURE OF THE CURRENT EXISTING GAS SYSTEM, A
 HOUSE LAYOUT WITH THE GAS LINES SHOWN. PLEASE INCLUDE
 ALL REGULATORS AND SHUT OFF VALVES. PROVIDE THE SPECS
 FOR THE REGULATORS USED. PROVIDE PIPE SIZES, TYPE OF
 MATERIAL USED. PLEASE ALSO INCLUDE THE GAS TABLE NUMBER
 USED FOR EACH TYPE OF PIPING IN THIS SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-20 Cont ID  
Sent By rmcdouga Date 2020-07-20 Time 13:00 Rev Time 0.00
Received By rmcdouga Date 2020-07-13 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-18 Cont ID  
Sent By jleahy Date 2020-06-18 Time 14:34 Rev Time 0.00
Received By jleahy Date 2020-06-01 Time 16:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 11:08 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 11:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-20 Cont ID  
Sent By shill Date 2020-07-20 Time 15:49 Rev Time 0.00
Received By shill Date 2020-07-20 Time 15:49 Sent To  
Notes
2020-07-20 15:49:48PROVISO: MAIL ORIGINAL ENGINEERING TO ME (FPL APPT
 TOMORROW)
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-20 Cont ID  
Sent By rmcdouga Date 2020-07-20 Time 13:00 Rev Time 0.00
Received By rmcdouga Date 2020-07-20 Time 13:00 Sent To  
Notes
2020-07-20 13:03:01THE GENERATOR PAD ENGINEERING IS NOT DIGITALLY SIGNED.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 11:09 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 11:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-06-11 Time   Rev Time  
Received By   Date 2020-06-11 Time   Sent To I
Notes
***NONE***