| 20050442 3800 WASHINGTON RD 212 |
| |
| 2ND REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| 1. SECOND REQUEST: FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY |
| CREATED OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE |
| SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED |
| ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS. |
| PLEASE NOTE, THE SUBMITTED DOCUMENTS ARE SCANNED, THE |
| SCANNED DIGITAL SIGNATURE CANNOT BE VERIFIED. |
| |
| 2. NEW COMMENT: PLAN SHEET A.2; THE REFURBISHMENT OF |
| THE EXISTING SHOWER DOES NOT INCLUDE REPLACEMENT OF THE |
| SHOWER LINER. THE EXISTING LINER SHALL BE TESTED AND |
| SHALL MEET ALL REQUIREMENTS OF FBC PL 417.5.2 |
| INCLUDING, BUT NOT LIMITED TO SLOPE TO THE DRAIN. IF |
| DEEMED DEFICIENT BY THE PLUMBING INSPECTOR IT SHALL BE |
| REPLACED. A DRAWING OF RECORD WILL BE REQUIRED |
| INDICATING THE NEW LINER. |
| |
| 3. NEW COMMENT: PLAN SHEET A.2; THE REFURBISHMENT OF |
| THE EXISTING SHOWER DOES NOT INCLUDE REPLACEMENT OF THE |
| CONTROL VALVE. THE EXISTING CONTROL VALVE SHALL BE |
| TESTED AND SHALL MEET ALL REQUIREMENTS OF FBC PL 424.3 |
| INCLUDING, BUT NOT LIMITED TO BEING ANTI-SCALD. IF |
| DEEMED DEFICIENT BY THE PLUMBING INSPECTOR IT SHALL BE |
| REPLACED. A DRAWING OF RECORD WILL BE REQUIRED |
| INDICATING THE CONTROL VALVE CONFORMING TO FBC PL |
| 424.3.. |
| |
| 4. NEW COMMENT: MASTER BATH TUB IS BEING REMOVED AND |
| REPLACED WITH A SHOWER. THIS WILL REQUIRE MODIFICATION |
| OF WATER PIPING AND IN WALL CONTROL VALVE. PER WPB FBC |
| 107.2.1, INDICATE ON THE PLANS AND SPECIFY THE CONTROL |
| VALVE TO COMPLY WITH FBC PL 424.3; INDIVIDUAL SHOWER |
| AND TUB-SHOWER COMBINATION VALVES SHALL BE |
| BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION |
| BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER |
| COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE |
| EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF |
| THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD |
| ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| UTILIZED FOR COMPLIANCE WITH THIS SECTION. |
| |
| 5. NEW COMMENT: MASTER BATH TUB IS BEING REMOVED AND |
| REPLACED WITH A SHOWER. THIS WILL REQUIRE MODIFICATION |
| OF THE BELOW SLAB PIPING. PER WPB FBC 107.2.1, SUBMIT A |
| SLAB REPAIR DETAIL FOR REVIEW SHOWING COMPLIANCE WITH |
| THE REQUIREMENTS OF FBC CHAPTER 7. SHOW TYPE OF |
| MATERIAL OF SHOWER DRAIN PIPE. PROVIDE ASSEMBLY HAVING |
| A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE |
| USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AND |
| THE ELIMINATED TUB DRAIN OPENING AS REQUIRED BY FBC |
| 714.4.1 THROUGH 714.4.4.1.2. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20050442 3800 WASHINGTON RD 212 |
| |