2020-05-25 10:20:29 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20050410 |
| ADD: 123 DATURA ST. |
| CONT: FINE LINE CONSTRUCTION |
| TEL: 561-582-7880 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. MAY 25, 2020 |
| ACTION: DENIED |
| |
| 1) SHEET ALS1.1: |
| |
| 1A) REVISION # 4 SHOWS THE OCCUPANT LOAD GOING FROM 93 |
| TO 166. JUST TO THE RIGHT OF THIS STATEMENT IS ANOTHER |
| REVISION # 4 FOR PLUMBING FIXTURE CALCULATIONS BUT THE |
| OCCUPANT LOAD WAS NOT CHANGED TO THE 166 OCCUPANTS, IT |
| IS STILL AT 93. PLEASE UPDATE PLANS FOR OCCUPANT LOAD |
| AND REQUIRED FIXTURE COUNT PER THE 2017 FBC-B TABLE |
| 2902.1. |
| |
| 1B) PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-EXISTING |
| BUILDING CODE SECTION 1012.8 ACCESSIBILITY CODE. |
| EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR |
| OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE |
| PROVISIONS OF THE FLORIDA ACCESSIBILITY CODE. |
| THE LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE |
| 2017 FBC-ACCESSIBILITY CODE; |
| 1B)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| SEATING SPACES AND STANDING SPACES AT THE DINING |
| SURFACES SHALL COMPLY WITH 902. |
| |
| 1B)(2) 226.2 DISPERSION. DINING SURFACES AND WORK |
| SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| SURFACES AND WORK SURFACES. |
| |
| 1B)(3) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR |
| SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| |
| 1B)(4) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| COUNTERS, AND WHERE COVERED BY THE ADA SCOPING |
| PROVISIONS, EMPLOYEE WORK STATIONS. |
| |
| 1B)(5)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR |
| FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 1B)(5)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 2) THE PLANS ALS1.1 SHOW REVISION 2 & 3 AS A NEW DOOR |
| OPENING BETWEEN TENANT SPACES BEING COMBINED INTO ONE |
| SPACE AND NEW ACCESSIBLE RAMP AND GUARDRAIL SYSTEM. |
| PLEASE NOTE THERE ARE NO DIMENSIONS IN THIS AREA OF THE |
| PLAN. |
| 2A) PLEASE SHOW COMPLIANCE WITH THE NEW DOORWAY BETWEEN |
| TENANT SPACES AND COMPLIANCE WITH THE ACCESSIBILITY |
| CODE SECTION 404.2.4.3 AND FIGURE 404.2.4.3. RECESSED |
| DOORS. |
| |
| 2B) PLEASE PROVIDE THE HEIGHT OF THE RAMP AND SLOPE OF |
| THE RAMP. PLEASE ALSO PROVIDE THE WIDTH OF THE RAMP |
| FROM THE INTERIOR SIDE OF THE HANDRAIL OR GUARDRAIL. |
| 2017 ACCESSIBILITY CODE SECTIONS: |
| 405.2 SLOPE. |
| 405.3 CROSS SLOPE. |
| 405.5 CLEAR WIDTH. |
| 405.6 RISE |
| 405.7.5 DOORWAYS |
| 405.8 HANDRAILS |
| 405.9 EDGE PROTECTION |
| |
| 3A) SHEET ALS1.1 SHOW REVISION # 1 WITH THE CLOSURE OF |
| ENTRY DOORS. PLEASE PROVIDE A DETAIL OF THIS AREA, IT |
| LOOKS LIKE THIS MAY HAVE NEW STOREFRONT WINDOW WALL |
| SYSTEM. IF SO PLEASE SHOW COMPLIANCE WITH COMPONENTS |
| AND CLADDING. |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| |
| |
| 3B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| 3D) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 4) IF REVISION # 1 IS NEW COMPONENTS AND CLADDING THEN |
| PLEASE PROVIDE THE WIND DESIGN CRITERIA. 2017 FBC-B |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 4.2. RISK CATEGORY. |
| |
| 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| |
| 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 4.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 4.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 5) SHEET ALS1.1 ON THE EAST SIDE OF THE BUILDING THE |
| FLOOR PLAN SHOW A EXTERIOR DOOR, RAMP AND HANDRAIL, ARE |
| THESE EXISTING OR NEW? |
| IF NEW SHOW COMPLIANCE WITH THE SAME CODE SECTIONS AS |
| COMMENT 2B. |
| |
| 6) THE PERMIT APPLICATION INDICATES A CHANGE OF |
| OCCUPANCY BUT NO VALUE WAS GIVEN FOR THE 4 REVISIONS |
| AND WORK TO BE COMPLETED UNDER THIS PERMIT. THE VALUE |
| OF WORK WILL NEED TO BE INCREASED TO SHOW THE TRUE |
| VALUE OF THIS PROJECT. |
| |
| 109.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF |
| THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 7) DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO |
| MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR |
| THE DESIGNER OF RECORD ON THEIR LETTERHEAD ARE TO |
| PROVIDE ON THEIR LETTERHEAD HOW THEY ARE GOING TO SPEND |
| THE 20% DISPROPORTIONATE FUNDS IN THE ORDER LISTED |
| BELOW. 2017 FBC-ACCESSIBILITY CODE: |
| |
| |
| 8) 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| BUILDING CODE (2003 EDITION). |
| 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| |
| 9) IMPACT FEES - DIGITAL SUBMITTALS: |
| PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS |
| OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] . |
| PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| |
| 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |