2020-05-26 08:27:35 | REVIEWED BY JERRY SMITH. |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20050353 1815 FLORIDA AVE |
| |
| GAS COMMENTS: APPROVED |
| |
| ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| INSPECTOR'S APPROVAL |
| BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM |
| THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO |
| AVOID VOIDING OF THE PERMIT. |
| |
| CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR |
| MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL |
| GAS INSPECTION. |
| CALL 561-805-6692 FOR FURTHER INFORMATION. |
| |
| PROVISO |
| 1. REGARDING LOW PRESSURE PIPING TO POOL HEATER, |
| 400,000 BTU DEMAND EXCEEDS THAT ALLOWED FOR ? INCH PIPE |
| BY TABLE FBC FG 402.4(2). THE REGULATOR AND PIPING FROM |
| THE REGULATOR SHALL BE SIZED TO SUPPORT 400,000 BTUS |
| AND MAY BE REDUCED TO ACCOMMODATE THE APPLIANCE INLET |
| SIZE AT THE INLET WITH USE OF REDUCING FITTINGS AND |
| NIPPLE CONFORMING TO FBC FG 403.10.4 (BUSHINGS ARE |
| PROHIBITED). PER WPB FBC 107.2.1, MAKE CORRECTION TO |
| COMPLY. |
| 2. REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER FBC FG |
| 410.1. DOCUMENTATION PROVIDED DOES NOT INDICATE SAID |
| APPROVAL PER WPB FBC 107.2.1 AND 107.3.4.1, PROVIDE AS |
| A DEFERRED SUBMITTAL, THE MANUFACTURER?S SPECIFICATIONS |
| FOR THE PRESSURE REGULATORS WHICH SUPPORT THE |
| REQUIREMENTS OF FBC FG 410.1. THE DOCUMENTS SHALL BE |
| SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL |
| INSPECTION. PROCEED AT YOUR OWN RISK. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |