Plan Review Details - Permit 20050267
Plan Review Stops For Permit 20050267
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-05 Cont ID  
Sent By pvalenti Date 2020-09-05 Time 11:30 Rev Time 0.00
Received By pvalenti Date 2020-09-05 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-04 Cont ID  
Sent By rmcdouga Date 2020-09-04 Time 08:57 Rev Time 0.00
Received By rmcdouga Date 2020-09-04 Time 08:57 Sent To  
Notes
2020-09-04 09:01:39PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS AND GENERATOR TO PAD
 ANCHORING DETAILS. FBC 107 THIS COMMENT HAS NOT BEEN
 ADDRESSED. THE LETTER FROM THE ELECTRICAL CONTRACTOR IS
 NOT ACCEPTABLE. PREFABRICATED GENERATOR PADS REQUIRE
 ENGINEERING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 11:54 Rev Time 0.00
Received By rmcdouga Date 2020-06-02 Time 11:54 Sent To  
Notes
2020-06-02 11:55:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS AND GENERATOR TO PAD
 ANCHORING DETAILS. FBC 107

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-15 Cont ID  
Sent By jleahy Date 2020-06-15 Time 09:00 Rev Time 0.00
Received By jleahy Date 2020-06-15 Time 08:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-08-27 Cont ID  
Sent By lcrespo Date 2020-08-27 Time 17:46 Rev Time 0.00
Received By lcrespo Date 2020-08-27 Time 17:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-10 Cont ID  
Sent By medwards Date 2020-06-10 Time 16:41 Rev Time 0.00
Received By medwards Date 2020-06-10 Time 16:14 Sent To  
Notes
2020-06-10 16:43:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050267
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECS FOR THE TYPE OF PIPING USED.
 FBC FS 107.2.1
  
 2) PLEASE PROVIDE MODEL NUMBER AND SPECS FOR REGULATOR
 USED. FBC FS 107.2.1
  
 3) PLEASE PROVIDE GAS TABLE USED FOR SIZING THE 10 PSI
 PE GAS LINE. FBC FS 107.2.1
  
 4) PLEASE PROVIDE THE SPEC SHEETS FOR THE FLEXIBLE GAS
 LINE HOSE USED TO CONNECT THE GENERATOR. FBC FS 107.2.1
  
 5) PLEASE SHOW THAT THE GENERATOR IS COMPLYING WITH
 THE MANUFACTURER CLEARANCES FROM OPENABLE OPENINGS TO
 THE STRUCTURE. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-04 Cont ID  
Sent By rmcdouga Date 2020-09-04 Time 09:01 Rev Time 0.00
Received By rmcdouga Date 2020-08-24 Time 15:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-15 Cont ID  
Sent By jleahy Date 2020-06-15 Time 09:00 Rev Time 0.00
Received By jleahy Date 2020-06-01 Time 16:46 Sent To  
Notes
2020-06-15 09:01:34I DID NOT SEE AN APPLICATION IN THIS PACKAGE JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-19 Cont ID  
Sent By lmarchan Date 2020-05-19 Time 09:31 Rev Time 0.00
Received By lmarchan Date 2020-05-08 Time 17:53 Sent To  
Notes
2020-05-08 17:53:36ROUTED TO ZONING INBOX
  
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-27 Cont ID  
Sent By lcrespo Date 2020-08-27 Time 17:46 Rev Time 0.00
Received By lcrespo Date 2020-08-27 Time 17:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-10 Cont ID  
Sent By medwards Date 2020-06-10 Time 16:46 Rev Time 0.00
Received By medwards Date 2020-06-10 Time 16:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-05 Cont ID  
Sent By pvalenti Date 2020-09-05 Time 11:29 Rev Time 0.00
Received By pvalenti Date 2020-09-05 Time 11:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-09-04 Cont ID  
Sent By rmcdouga Date 2020-09-04 Time 08:55 Rev Time 0.00
Received By rmcdouga Date 2020-09-04 Time 08:55 Sent To  
Notes
2020-09-04 08:57:36PREFABRICATED GENERATOR PADS REQUIRE SIGNED AND SEALED
 PLANS FROM A FLORIDA LICENSED ENGINEER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-10 Cont ID  
Sent By medwards Date 2020-06-10 Time 16:46 Rev Time 0.00
Received By medwards Date 2020-06-10 Time 16:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-06-11 Time   Rev Time  
Received By   Date 2020-06-11 Time   Sent To I
Notes
2020-06-11 08:59:11ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 6/11/20
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. INDICATE GENERATOR SETBACK FROM PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved