Plan Review Details - Permit 20050066
Plan Review Stops For Permit 20050066
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-19 Cont ID  
Sent By lmarchan Date 2020-06-19 Time 09:52 Rev Time 0.00
Received By lmarchan Date 2020-06-17 Time 14:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-18 Cont ID  
Sent By lcrespo Date 2020-05-18 Time 07:21 Rev Time 0.00
Received By lcrespo Date 2020-05-13 Time 17:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-06-19 Cont ID  
Sent By lcrespo Date 2020-06-19 Time 08:39 Rev Time 0.00
Received By lcrespo Date 2020-06-19 Time 08:39 Sent To  
Notes
2020-06-19 08:39:5106/19/20 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-18 Cont ID  
Sent By lcrespo Date 2020-05-18 Time 07:21 Rev Time 0.00
Received By lcrespo Date 2020-05-18 Time 07:21 Sent To  
Notes
2020-05-18 07:24:201ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE
 WORK SECTION ON THE PERMIT APPLICATION.
  
 2. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE.
  
 3. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT THE
 DEPARTMENT OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT
 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE
 PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY
 REQUIREMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  