Plan Review Details - Permit 20041170
Plan Review Stops For Permit 20041170
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-08-24 Cont ID  
Sent By jwitmer Date 2020-08-24 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2020-08-24 Time 08:30 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 10:34 Rev Time 0.00
Received By jwitmer Date 2020-08-12 Time 14:31 Sent To  
Notes
2020-08-17 10:34:04PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-05-17 Cont ID  
Sent By jwitmer Date 2020-05-17 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2020-05-17 Time 07:48 Sent To  
Notes
2020-05-17 12:29:52PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-24 Cont ID  
Sent By jwitmer Date 2020-08-24 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2020-08-24 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-14 Cont ID  
Sent By jwitmer Date 2020-08-14 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2020-08-12 Time 14:31 Sent To  
Notes
2020-08-14 08:00:572017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20041170
 ADD: 6821 NORTON AVE.
 CONT: COASTAL WINDOWS & DOORS
 TEL: 561-842-7000
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRIDAY AUGUST 14TH, 2020
 ACTION: BUILDING PROVISO/ DEFERRED SUBMITTAL,
 1) THE DESIGNER OF RECORD HAS REQUESTED THE SHOP
 DRAWINGS FOR THE SPIRAL STAIR AND HANDRAIL TO BE A
 DEFERRED SUBMITTAL. SHOP DRAWINGS ARE TO BE IN
 COMPLIANCE WITH THE 2017 FBC-B 1011.10. THE DESIGNER OF
 RECORD IS TO REVIEW AND IF APPROVED APPLY HIS SHOP
 DRAWING STAMP OF APPROVAL BEFORE THE CONTRACTOR
 SUBMITTING THE SHOP DRAWINGS TO THE BUILDING DEPARTMENT
 FOR APPROVAL.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-17 Cont ID  
Sent By jwitmer Date 2020-05-17 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2020-05-17 Time 07:48 Sent To  
Notes
2020-05-17 12:28:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20041170
 ADD: 6821 NORTON AVE.
 CONT: COASTAL WINDOWS & DOORS
 TEL: 561-842-7000
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY MAY 17, 2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 INDICATES REMODELING IN THE FIRST FLOOR OCCUPANCY,
 WHEREAS THE COVERSHEET C-1 UNDER THE SCOPE OF WORK NOTE
 # 1 REMODEL OF THE 1ST FL. AND RESTROOM & NOTE 2
 INDICATES THE REMODEL OF THE 2ND FLOOR. THERE IS A
 DISCREPANCY BETWEEN THE PERMIT APPLICATION AND THE 2ND
 FLOOR. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY IN THE DESCRIPTION OF WORK TO BE
 ACCOMPLISHED UNDER THIS PERMIT.
  
 2) SHEET A-1:
  
 2A) THE PLANS SHEET A-1 INDICATE UNDER THE HEADING
 PROJECT DATA THE OCCUPANCY TYPE IS A-3 BUT THE OCCUPANT
 LOAD IS TAKEN AS A BUSINESS OCCUPANCY 1350 SQ. FT. /
 100 SQ. FT. (OCCUPANT LOAD FACTOR/ TABLE 1004.1.2.).
 PLEASE REVIEW TABLE 11004.1.2 EXHIBIT GALLERIES (A-3)
 OCCUPANT LOAD FACTOR IS TO BE TAKEN AT 30 NET. PLEASE
 UPDATE THE OCCUPANT LOAD (NET).
 2017 FBC-B 201: FLOOR AREA, NET. THE ACTUAL OCCUPIED
 AREA NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS
 CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS
 AND CLOSETS.
  
 2B) THE PLANS SHEET A-1 INDICATE UNDER THE HEADING
 PROJECT DATA THE OCCUPANCY TYPE IS A-3 BUT IF UNDER
 COMMENT # 1 THE WORK TO BE ACCOMPLISHED UNDER THIS
 PERMIT IS THE REMODEL OF BOTH THE 1ST & 2ND FLOOR THEN
 THIS SHOULD BE CONSIDERED A MIXED USE OCCUPANCY, 1ST
 FLOOR A-3 AND THE 2ND FLOOR R-3. SEE THE 2017 FBC-B
 SECTION 508.1 & TABLE 707.3.10.
  
 2C) THE PLAN SHEET A-1 INDICATES UNDER THE HEADING
 PROJECT DATA THE PLAN IS SILENT TO THE 2ND FLOOR
 OCCUPANCY WHERE THE 2ND FLOOR PLAN DOES INDICATE WORK
 TO BE ACCOMPLISHED IN THIS SET OF PLAN DOCUMENTS, NOTES
 3, 4 & 5. THE PROJECT DATA DOES NOT INDICATE THE TYPE
 OF OCCUPANCY THE 2ND FLOOR HOUSES NOR THE PROPOSED
 OCCUPANT LOAD. SEE 2017 FBC-B SECTIONS 310.5 & TABLE
 1004.1.2.
  
 2D) SHEET A-1 SHOWS ONLY ONE MEANS OF EGRESS TO THE 2ND
 STORY R-3 RESIDENCE, AN EXTERIOR STAIR. SHEET A-1 ALSO
 HAS A NOTE ABOUT A NEW STOREFRONT IN THE FORMER
 OVERHEAD DOOR OPENING. THERE ARE NO ELEVATION DRAWINGS
 OF THIS SIDE VIEW BUT THE PLANS FAIL TO SHOW COMPLIANCE
 WITH SECTION 1027.6 EXTERIOR EXIT STAIRWAY PROTECTION.
 YOU CAN ALSO SEE THE 2015 IBC CODE COMMENTARY FIGURE
 1027.6(1) WHERE WITHIN THE VERTICAL CROSSED HATCHED
 LINES NO OPENINGS EXCEPT FOR 1 HOUR RATED DOORS AND
 OPENINGS OUTSIDE OF THE STAIR AND LANDINGS BUT WITHIN
 10 FEET OF EITHER THE STAIR OR LANDING ? HOUR OPENING
 PROTECTIVES ARE REQUIRED. THIS WAS NOT ADDRESSED UNDER
 THE PERMIT 20031278.
  
 2E) SHEET A-1 GIVE THE WIND DESIGN CRITERIA BUT NOT THE
 PRESSURES FOR THE NEW EXTERIOR DOOR AND WINDOW OPENINGS
 FOR THE 1ST FLOOR AND 2ND FLOOR.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 2E)(1-3.) COMPLIED.
  
 2E)(4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2E)(5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 2E)(6.) TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
  
 4) GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 5A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) SHEET A-1 TOILET ACCESSORY SCHEDULE:
 6A) BOTH GB & GB-1 BOTH STATE THE GRAB BAR IS TO BE
 INSTALLED @ 33 INCHES A.F.F. ?CENTERLINE OF GRAB BAR.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 6B) TPH TOILET PAPER HOLDER INDICATES IT IS TO BE
 MOUNTED MIN. / MAX. 36 INCHES FROM THE REAR WALL.
 2017 ACCESSIBILITY CODE SECTION 604.7. TOILET PAPER
 DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7-9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTER LINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND THE GRAB BARS.
  
 7) THE FLOOR PLAN SHOWS A SINGLE WATER FOUNTAIN. PLEASE
 SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE. 211.2
 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7.
  
 8) THE 2ND FLOOR (A-1) PLAN STATES WITH NOTE 3 THAT A
 NEW DOORWAY TO THE ADDED FOR ACCESS TO THE ROOF DECK.
 THE PLANS DO NOT PROVIDE ANY STRUCTURAL SHEETS AND OR
 DETAILS HOW THIS WILL OCCUR. THE SHEET A-1 DOES NOT
 EVEN LET US KNOW IF THIS BUILDING IS CBS CONSTRUCTION
 OR WOOD FRAME. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9) COMPLIED. 7/16/2020 TEL. MEETING ARCH. JIM PAINE
  
 10) THIS NOTE IS TO BE DISCUSSED WITH THE BUILDING
 OFFICIAL, THE SECOND FLOOR COMMON PATH OF TRAVEL FOR
 THE 2ND FLOOR IS TO THE MOST REMOTE POINT OF THE 2ND
 FLOOR TO THE EXIT DISCHARGE, THE BOTTOM OF THE STAIRS.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-27 Cont ID  
Sent By jleahy Date 2020-08-27 Time 15:26 Rev Time 0.00
Received By jleahy Date 2020-08-27 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-01 Cont ID  
Sent By jleahy Date 2020-06-01 Time 15:28 Rev Time 0.00
Received By jleahy Date 2020-06-01 Time 15:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-05-15 Cont ID  
Sent By pleduc Date 2020-05-15 Time   Rev Time 0.00
Received By pleduc Date 2020-05-15 Time 13:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-27 Cont ID  
Sent By lmarchan Date 2020-08-27 Time 15:28 Rev Time 0.00
Received By jleahy Date 2020-08-20 Time 14:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-20 Cont ID  
Sent By lcrespo Date 2020-08-20 Time 08:57 Rev Time 0.00
Received By lcrespo Date 2020-08-12 Time 16:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-12 Cont ID  
Sent By lmarchan Date 2020-08-12 Time 15:33 Rev Time 0.00
Received By lmarchan Date 2020-08-07 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-15 Cont ID  
Sent By tklarge Date 2020-06-15 Time 12:20 Rev Time 0.00
Received By tklarge Date 2020-05-14 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-08-17 Cont ID  
Sent By medwards Date 2020-08-17 Time 11:47 Rev Time 0.00
Received By medwards Date 2020-08-17 Time 11:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-08-17 Cont ID  
Sent By medwards Date 2020-08-10 Time 16:11 Rev Time 0.00
Received By medwards Date 2020-08-17 Time 11:45 Sent To  
Notes
2020-08-10 16:11:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20041170
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE BUILDING REVIEWERS COMMENTS FROM 1ST
 CYCLE REVIEW. ACCORDING TO HIS REVIEW THIS PROJECT IS
 AN A-3 WITH A R-3 ABOVE. PLEASE SHOW VENTILATION AND
 ENERGY CALCS BASED ON THE A-3 AND NUMBER OF OCCUPANTS
 BASED ON AREA.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-05-27 Cont ID  
Sent By medwards Date 2020-05-27 Time 11:02 Rev Time 0.00
Received By medwards Date 2020-05-27 Time 10:41 Sent To  
Notes
2020-05-27 11:05:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20041170
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) PLEASE SEE BUILDING REVIEWER COMMENTS, I CAN?T DO A
 COMPLETE REVIEW UNTIL THOSE QUESTIONS ARE ANSWERED.
  
 2) PLEASE PROVIDE ENERGY CALCULATIONS FOR THIS PROJECT
 AND MANUAL J CALCULATIONS.
 FBC EC C403.2.1
 3) PROVIDE VENTILATION CALCULATIONS FOR AHU-2. FBC M
 403.3.1.1
  
 4) PLEASE SHOW THE RETURN AIR PATH FOR (EXISTING
 BEDROOM #1) FBC FS 107.2.1
  
 5) AHU-1 CFM SUPPLY IS 1400; SHEET MP.1 SHOWS 1641
 CFM?S PLEASE CORRECT THIS. FBC FS 107.2.1
  
 6) PLEASE SHOW THE MANUFACTURE RECOMMENDATIONS FOR
 ANCHORAGE OF THE APPLIANCES. FBC FS 107.2.1
  
 7) PLEASE PROVIDE INFORMATION ON THIS BUILDING; FIRE
 SEPARATION BETWEEN 1ST AND 2ND FLOOR; TYPE OF FLOOR FOR
 2ND FLOOR; TYPE OF CEILING FOR 1ST FLOOR. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By lcrespo Date 2020-08-20 Time 08:56 Rev Time 0.00
Received By lcrespo Date 2020-08-20 Time 08:56 Sent To  
Notes
2020-08-20 08:57:1308/20/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-06-15 Cont ID  
Sent By tklarge Date 2020-06-15 Time 12:20 Rev Time 0.00
Received By tklarge Date 2020-06-15 Time 10:11 Sent To  
Notes
2020-06-15 12:16:591) SHOW ALL THE NEW AND RELOCATED PLUMBING FIXTURES ON
 THE WATER RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 2) THE TOILET ROOM DOOR APPEARS TO SWING INTO THE CLEAR
 FLOOR SPACE FOR THE DRINKING FOUNTAIN. DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED
 FOR ANY FIXTURE PER 2017 FBC-ACCESS. SEC.602.2.3.
 3) SHT. MP.1 - NEW BATH SANITARY RISER - THE WASHING
 MACHINE CANNOT DISCHARGE INTO A HORIZONTAL WET VENT PER
 FBC-PLUMBING SEC.912.1. THE WASHING MACHINE SHALL
 CONNECT TO THE HORIZONTAL DRAIN DOWNSTREAM OF THE WATER
 CLOSET.
 4) SHT.MP-1 - 1ST FLOOR BATH SANITARY RISER - THE
 DRINKING FOUNTAIN AND THE SINK CANNOT DISCHARGE INTO A
 HORIZONTAL WET VENT PER 2017 FBC-PLUMBING SEC.
 912.1.THE DRINKING FOUNTAIN AND FUTURE SINK SHALL
 CONNECT TO THE HORIZONTAL DRAIN DOWNSTRAM OF THE STACK
 TO THE 2ND FLOOR.
 5) IN ORDER TO UTILIZE AN AIR ADMITTANCE VALVE THERE
 MUST BE A MINIMUM OF ONE STACK VENT OR VENT STACK
 EXTENDED TO THE OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC.918.7. SHOW COMPLIANCE ON THE PLANS.
 6) SUBMIT A DETAIL OF THE DRYWELL FOR THE CONDENSATE
 LINE.
 7) SHOW THE SHOWER DIMENSIONS ON THE PLANS. COMPLY WITH
 FBC-PLUMBING SEC. 417.4.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHOW BOTH TANKLESS WATER HEATERS ON THE WATER RISER
 ALONG WITH ALL CONNECTED FIXTURES. WPB AMEND. TO FBC
 SEC. 107.2.1.
 10) THE SANITARY RISER SHOWS A 1 INCH DRAIN FOR THE
 DRINKING FOUNTAIN. CLARIFY.
 11) SHT. A.1 - TOILET ACCESSORY SCHEDULE AND ELEVATIONS
 - THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER FBC-ACCESS. SEC.609.4.
 12) SHT. A.1 - THERE IS A NOTE BY THE GRAB BAR
 INSTALLATION DETAIL THAT REFERENCES THE 2010 FBC.
 DELETE THIS NOTE.
 13) SHT. A.1 - TYPICAL TOILET ROOM PLAN SHOWS THE
 CCLEAR FLOOR SPACE FOR THE WATER CLOSETAS 56 INCHES
 WIDE BY 60 INCHES DEEP.THE CLEAR FLOOR SPACE SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL PER FBC-ACCESS. SEC.604.3.1.
 14) THE TOILET PAPER HOLDER SHALL BE LOCATED IN
 ACCORDANCE WITH FBC-ACCESS. SEC.604.7. SHOW THE
 DIMENSIONS ON THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH BUILDING DIVISION
 401 CLEMATIS ST.
 P.O. BOX 3147
 WEST PALM BEACH, FL.33402
 [email protected]
 P: 561-805-6692
 F: 561-805-6676
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-10 Cont ID  
Sent By medwards Date 2020-08-10 Time 16:14 Rev Time 0.00
Received By medwards Date 2020-08-10 Time 16:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-27 Cont ID  
Sent By medwards Date 2020-05-27 Time 11:08 Rev Time 0.00
Received By medwards Date 2020-05-27 Time 11:08 Sent To  
Notes
2020-05-27 11:11:041ST CYCLE SIGNATURE REVIEW IS APPROVED. THE NEXT CYCLE
 DRAWINGS WILL NEED TO BE REVIEWED.