Plan Review Details - Permit 20041096
Plan Review Stops For Permit 20041096
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-06-23 Cont ID  
Sent By medwards Date 2020-06-23 Time 15:29 Rev Time 0.00
Received By medwards Date 2020-06-23 Time 15:24 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-06-05 Cont ID  
Sent By medwards Date 2020-06-05 Time 10:03 Rev Time 0.00
Received By medwards Date 2020-06-05 Time 07:41 Sent To  
Notes
2020-06-05 10:05:003RD REVIEW FBC-2017 MECHANICAL
 PERMIT-20041096
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MODEL NUMBER OF THE REGULATOR
 USED AT EACH LOCATION IN THIS SYSTEM. FBC FS 107.2.1
  
 2) PLEASE PROVIDE SPECS. AND SHOW FLEXIBLE CONNECTOR
 USED TO CONNECT THE GENERATOR TO THE GAS LINE. FBC FS
 107.2.1
  
 3) THERE IS A MEASUREMENT OF 49? ON THE DRAWING, IS
 THIS THE LONGEST LENGTH TO THE MOST REMOTE APPLIANCE?
 IF NOT, WHY IS IT ON THE DRAWING? FBC FS 107.2.1
  
 4) PLEASE CLEAN THE DRAWING UP IN THE AREA OF THE
 METER, I CANNOT SEE ALL THE CONNECTIONS AND PIPE SIZES
 IN THIS AREA. FBC FS 107.2.1
  
 5) THERE IS A REFERENCE OF 3 TABLES USED TO SIZE THIS
 PIPING SYSTEM. TABLE 402.4(18) IS FOR CSST, I DO NOT
 SEE CSST ON THIS DRAWING. PLEASE SHOW ON THE DRAWING
 WHERE THE CSST IS TO BE USED IN THIS SYSTEM. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-05-14 Cont ID  
Sent By jpearson Date 2020-05-14 Time 15:13 Rev Time 0.00
Received By jpearson Date 2020-05-14 Time 13:51 Sent To  
Notes
2020-05-14 13:51:34REVIEWED BY JERRY SMITH.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20041096 140 MONROE DR
  
 GAS COMMENTS: DENIED
 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE RANGE
 PER FBC FG 304.1
 2.SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM FBC FG 402.4.1, 402.4.2
 3.PER WPB FBC 107.2.1, SHOW PE TO GALVANIZED RIGID
 PIPING TRANSITION ON RISER DIAGRAM.
 4.PER WPB FBC 107.2.1, PROVIDE THE MATERIAL AND TABLE
 USED IN SIZING PIPING DOWNSTREAM OF MP REGULATOR(S).
 INDICATE ON THE PLAN THE DISTANCE FROM REGULATOR TO
 APPLIANCE.
 5.PER WPB FBC 107.2.1, PROVIDE DETAIL OF MP REGULATOR
 WITH SHUTOFF VALVE, UNION AND OTHER REQUIRED
 ACCESSORIES. COMPLY WITH FBC FG 410.2.
 6.PER WPB FBC 107.2.1, PROVIDE SITE W/BUILDING AND
 POOL/DIMENSIONED BUILDING PLAN VIEW DRAWING SHOWING
 BUILDING AND LAYOUT INCLUSIVE OF ROOMS, DOORS AND
 WINDOWS, LOCATIONS OF GAS APPLIANCES, PIPE ROUTING AND
 METER. INDICATE ON THE PLAN IF THE TANKLESS WATER
 HEATER IS REPLACING AN EXISTING TANKLESS WATER HEATER
 OR IS IT REPLACING A STORAGE TANK TYPE WATER HEATER OR
 IS IT BEING ADDED TO THE EXISTING HOT WATER SYSTEM?
 INDICATE ON THE APPLICATION IN THE DESCRIPTION OF WORK.
 IF REPLACING OR SUPPLEMENTING, IDENTIFY AND SHOW
 LOCATION OF THE EXISTING WATER HEATER. SHOW HORIZONTAL
 DISTANCE FROM ANY OUTSIDE APPLIANCE EXHAUST TO NEAREST
 WINDOW OR OPERATING DOOR. THE HOUSE PLAN CAN BE HAND
 DRAWN. A PLAN OF RECORD IS AVAILABLE FROM THE WPB
 BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON AT
 561-805-6684; EMAIL [email protected].
 7.PROVIDE SHUTOFF VALVE ON THE SUPPLY SIDE OF THE METER
 PER FBC FG 409.2.
 8.PER WPB FBC 107.2.1, ALL PLANS SHALL BE BEAR THE
 PRINTED NAME AND SIGNATURE OF THE DESIGNER.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE REVIEW OF SUBMITTED CORRECTIONS.
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20041096 140 MONROE DR
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-25 Cont ID  
Sent By rmcdouga Date 2020-06-25 Time 14:17 Rev Time 0.00
Received By rmcdouga Date 2020-06-15 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-12 Cont ID  
Sent By lmarchan Date 2020-06-12 Time 09:25 Rev Time 0.00
Received By lmarchan Date 2020-05-29 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-14 Time   Rev Time 0.00
Received By jgomez Date 2020-04-28 Time 16:39 Sent To  
Notes
2020-05-05 16:39:37CONVERTED TO DIGITAL. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By rmcdouga Date 2020-06-25 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2020-06-25 Time 14:02 Sent To  
Notes
2020-06-25 14:17:19APPROVED BY JERRY SMITH.

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-14 Cont ID  
Sent By jpearson Date 2020-05-14 Time 15:14 Rev Time 0.00
Received By jpearson Date 2020-05-14 Time 13:51 Sent To  
Notes
2020-05-14 13:51:17REVIEWED BY JERRY SMITH.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20041096 140 MONROE DR
  
  
  
 PLUMBING COMMENTS: DENIED
 1.PER WPB FBC 107.2.1, PROVIDE A PLAN VIEW DRAWING
 SHOWING BUILDING LAYOUT. INDICATE ON THE PLAN IF THE
 TANKLESS WATER HEATER IS REPLACING AN EXISTING TANKLESS
 WATER HEATER OR IS IT REPLACING A STORAGE TANK TYPE
 WATER HEATER OR IS IT BEING ADDED TO THE EXISTING HOT
 WATER SYSTEM? INDICATE ON THE APPLICATION IN THE
 DESCRIPTION OF WORK. IF REPLACING OR SUPPLEMENTING,
 IDENTIFY AND SHOW LOCATION OF THE EXISTING WATER
 HEATER. PROVIDE A WATER RISER DIAGRAM. THE HOUSE PLAN
 CAN BE HAND DRAWN. A PLAN OF RECORD IS AVAILABLE FROM
 THE WPB BUILDING DEPARTMENT BY CONTACTING CRAIG
 MCPHERSON AT 561-805-6684; EMAIL [email protected].
 2.PER WPB FBC 107.2.1, ALL PLANS SHALL BE BEAR THE
 PRINTED NAME AND SIGNATURE OF THE DESIGNER.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE REVIEW OF SUBMITTED CORRECTIONS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20041096 140 MONROE DR
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-23 Cont ID  
Sent By medwards Date 2020-06-23 Time 15:32 Rev Time 0.00
Received By medwards Date 2020-06-23 Time 15:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-05 Cont ID  
Sent By medwards Date 2020-06-05 Time 10:07 Rev Time 0.00
Received By medwards Date 2020-06-05 Time 10:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-14 Cont ID  
Sent By jpearson Date 2020-05-14 Time 15:15 Rev Time 0.00
Received By jpearson Date 2020-05-14 Time 15:15 Sent To  
Notes
2020-05-14 15:14:57PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481